Haier Super Aqua Monobloc Air to Water Heat Pump
Haier Commercial Air Conditioning
Address: No.1 Haier Road, Hi-tech Zone, Qingdao 266101 P.R.China
Contacts: Tel: +86-532-8893-6938 | B2B Website: www.haierac.com | B2C Website: www.haier.com
Version 1.0, November 2020
What is Haier Super Aqua?
The Haier Super Aqua air to water heat pump utilizes free renewable energy from the outside air as its heat source. It provides space cooling, heating, and domestic hot water (DHW). This energy-efficient and environmentally-friendly solution significantly reduces energy consumption, running costs, and CO2 emissions compared to conventional oil and gas boilers.
System Diagram Description: A cross-section illustration of a house shows the integrated Haier Super Aqua system. Components include:
- ♨️ Radiator: Connected to the heating system.
- ?️ Fan Coil: Distributes conditioned air.
- ?️ Underfloor Heating: Integrated into the living room floor.
- ?️ Wired Controller: Wall-mounted unit for system management.
- ? DHW Tank: Stores domestic hot water.
- ? DHW PCB: Electronic control component for hot water.
- ? Haier Super Aqua: The outdoor heat pump unit.
Red lines represent heating/hot water circuits, blue lines represent cooling circuits, and arrows indicate airflow.
Why Choose Haier Super Aqua?
MONOBLOC Design
The Monobloc unit integrates all components into a single outdoor unit, simplifying installation and maintenance.
Total Comfort
Haier Super Aqua Monobloc provides an integrated solution for year-round comfort. It offers leaving water temperatures ranging from 5°C to 60°C, ensuring comfortable cooling and heating. Domestic hot water production is guaranteed throughout the year. The optional terminal box ATW-A01 allows for external management of DHW production.
Application Types: The system can be configured for various applications:
- Water Temperature Range: 5°C to 60°C
- Fan Coil units
- Heating Radiators
- Underfloor Heating
Low Sound Level: Multiple noise reduction measures are implemented to ensure quiet operation.
- Compressor: Encased in soundproof material and mounted on anti-vibration mounts for reduced noise and vibration.
- Axial Fan: Features a brushless DC motor and an aerodynamically optimized impeller for quiet performance.
- Pipeline Design: Optimized internal pipeline structure minimizes noise and vibration.
The sound power level of the 5kW unit is only 59dB(A) (noise measured within 1 meter).
A 'Quiet Mode' is available for enhanced quiet operation, particularly during nighttime hours.
Environmentally-friendly
Haier Super Aqua air to water heat pumps leverage free renewable energy from the outside air. This energy-efficient and environmentally-friendly solution substantially reduces energy consumption, running costs, and CO2 emissions compared to conventional oil and gas boilers.
Energy Efficiency Example: 2kW of air source energy can produce 3kW of heat, powered by 1kW of electricity.
Refrigerant Type: All Super Aqua products use the future refrigerant R32, which has a significantly reduced environmental impact compared to older refrigerants like R410A. The Global Warming Potential (GWP) for R32 is 675, compared to 2088 for R410A.
Key Features
Energy Saving
Full DC Inverter Technology: Features a twin rotary compressor with a variable frequency stepless speed control motor for enhanced energy efficiency. The water-cooled canned rotor pump contributes to lower sound levels and higher efficiency.
Control Technology: Compares 'Step speed' common drive control with Haier's '180° vector drive control' for the inverter, highlighting superior performance and efficiency.
High Reliability
Intelligent Anti-freezing Technology: Multi-sensor protection prevents the water system from freezing in winter. When the water temperature drops below 3°C, the pump activates to maintain flow. A flow switch monitors water flow to prevent freezing in cooling mode by ensuring minimum flow rates.
Wide Operation Range: The system operates effectively with leaving water temperatures from 5°C to 60°C. The 5kW unit can provide a leaving water temperature of 60°C even when the outdoor ambient temperature is as low as -25°C.
Operating Range Graphs: Illustrate the relationship between outdoor ambient temperature and leaving water temperature for both heating and cooling modes.
- Heating: Can achieve 60°C leaving water at -25°C outdoor ambient.
- Cooling: Operates with leaving water temperatures from 5°C to 20°C across various outdoor temperatures.
Convenience
Easy Installation: The compact design of the Monobloc unit allows for installation even in spaces with limited room.
Easy Control: Features a modern, white touch screen controller with a clear, intuitive interface and backlight. A built-in weekly timer enables pre-set automatic control. Error codes are displayed, and a historical log aids in maintenance.
Wide Application
With capacity ranges from 5kW to 16kW, Haier Super Aqua is suitable for both residential buildings and small commercial applications such as cafes, restaurants, and hair salons. It is ideal for newly built homes with improved insulation and for renovations.
Application Scenarios: Images depict the units integrated into various settings: Home, Café & Restaurant, and Hair Salons.
Specifications & Dimensions
Model | AU052FYCRA(HW) | AU082FYCRA(HW) | AU112FYCRA(HW) | AU162FYCRA(HW) | ||
---|---|---|---|---|---|---|
Capacity (Heating LWT 35°C/OAT 7°C) | kW | 5.00 | 7.80 | 11.00 | 16.00 | |
Power input (Heating LWT 35°C/OAT 7°C) | kW | 0.99 | 1.77 | 2.61 | 3.86 | |
COP (Heating LWT 35°C/OAT 7°C) | 5.05 | 4.40 | 4.22 | 4.15 | ||
Capacity (Heating LWT 55°C/OAT 7°C) | kW | 5.00 | 7.01 | 9.99 | 14.01 | |
Power input (Heating LWT 55°C/OAT 7°C) | kW | 1.64 | 2.76 | 4.40 | 5.63 | |
COP (Heating LWT 55°C/OAT 7°C) | 3.05 | 2.54 | 2.27 | 2.49 | ||
SCOP (Space heating Average climate water outlet 35°C) | 4.59 | 3.87 | 4.35 | 4.00 | ||
ηs (Space heating Average climate water outlet 35°C) | % | 180 | 152 | 171 | 157 | |
Energy class (Space heating Average climate water outlet 35°C) | A+++ | A++ | A++ | A++ | ||
SCOP (Space heating Average climate water outlet 55°C) | 3.32 | 2.90 | 3.20 | 3.09 | ||
ηs (Space heating Average climate water outlet 55°C) | % | 130 | 113 | 125 | 121 | |
Energy class (Space heating Average climate water outlet 55°C) | A++ | A+ | A++ | A+ | ||
Capacity (Cooling LWT 18°C/OAT 35°C) | kW | 5.00 | 7.00 | 13.50 | 16.00 | |
Power input (Cooling LWT 18°C/OAT 35°C) | kW | 1.00 | 2.06 | 2.94 | 3.64 | |
EER (Cooling LWT 18°C/OAT 35°C) | 5.00 | 3.40 | 4.60 | 4.40 | ||
Capacity (Cooling LWT 7°C/OAT 35°C) | kW | 5.00 | 5.50 | 11.50 | 14.50 | |
Power input (Cooling LWT 7°C/OAT 35°C) | kW | 1.56 | 2.34 | 3.83 | 4.92 | |
EER (Cooling LWT 7°C/OAT 35°C) | 3.20 | 2.35 | 3.00 | 2.95 | ||
Outdoor operating temperature range | Heating | °C | -25-35 | -20-35 | -20-35 | -20-35 |
Cooling | °C | 10-46 | 10-46 | 10-46 | 10~46 | |
Leaving water temperature range | Heating | °C | 25-60 | 20-55 | 20-55 | 20~55 |
Cooling | °C | 5-20 | 5-20 | 5-20 | 5-20 | |
Water flow rate | L/min | 14.3 | 23.0 | 31.5 | 45.8 | |
Water piping connection | Inlet/Outlet inch | RC 3/4 | RC 1 | RC 1 | RC 1 | |
Quantity | 1 | 1 | 1 | 1 | ||
Compressor Type | DC inverter twin rotary | |||||
Refrigerant | Type | R32 | ||||
Net dimension (H×W×D) | mm | 760×920×372 | 965×950×370 | 1490×950×370 | 1490×950×370 | |
Packing dimension (H×W×D) | mm | 890×1045×488 | 1123×1023×480 | 1653×1023×480 | 1653×1023×480 | |
Net/Gross weight | kg | 69/80 | 87/97 | 145/157 | 145/157 | |
Sound power level | dB(A) | 61 | 64 | 67 | 68 | |
Power supply | (V/Hz/Ph) | 1, 220-240, 50/60 | ||||
Max. running current | A | 13.5 | 21.3 | 24.3 | 31.7 | |
Recommended circuit breaker | A | 20 | 30 | 32 | 40 | |
Accessory | Wired controller | YR-E27A (Standard) | ||||
DHW PCB | ATW-A01(Optional) | |||||
Filter | Standard |
Outline Dimensions:
- Diagram for AU052FYCRA(HW) showing dimensions: Height 760mm, Width 920mm, Depth 372mm.
- Diagram for AU082FYCRA(HW) showing dimensions: Height 965mm, Width 950mm, Depth 370mm.
- Diagram for AU112FYCRA(HW)/AU162FYCRA(HW) showing dimensions: Height 1490mm, Width 950mm, Depth 370mm.
Notes:
- Efficiency data is based on EN14511.
- LWT: Leaving water temperature; OAT: Outdoor air temperature.
- Sound level values are measured in a semi-anechoic room. Sound power level values are based on measurement of EN2012 under conditions of EN14825.
- Data may be changed without notice for future improvement on quality and performance.