GuideLed SL 13051.1/13052.1 CG-S Mounting and Operating Instructions

Target Group and Intended Application

Target group: Skilled electricians

Intended Application: Emergency Lighting, not suitable for private use.

Contents

  1. Conformity with standards
  2. Installation / Operation
  3. Technical Data
  4. Construction / Dimensional drawings
    1. SL 13051.1 CG-S
    2. SL 13052.1 CG-S
    3. Additional enclosure
  5. Addressing
  6. Service / Maintenance
  7. Disposal / Recycling
  8. General Safety Instructions

General Safety Instructions

Safety First:

⚠️ Attention! External voltage!

1 Conformity with standards

Luminaire for emergency lighting acc. to EN 60 598-2-22 for connection to safety luminaire systems acc. to EN 50172, DIN VDE 0100-560 and DIN VDE V 0108-100-1. Designed, manufactured and tested according to DIN EN ISO 9001.

IMPORTANT

The luminaire should be positioned so that prolonged staring into the luminaire at a distance closer than 1.15m is not expected.

2 Installation / Operation

For the mounting and operation of electrical apparatus, the respective national safety regulations as well as the general rules of engineering will have to be observed!

3 Technical Data

Parameter Value
Power input 220-240 V AC, 50/60 Hz, 176-275 V DC
Housing material PC, Aluminium
Housing colour White RAL 9016
Luminous flux phiE/phiNom at the end of rated operating time 100%
Light source HighPower LED 1 x 2.2 W
Insulation class II
Protection category acc. to EN 60529 SL 13051.1: After installation in the ceiling, the luminaire face is rated IP41 / module enclosure: IP 20
SL 13052.1: IP 41
Permissible ambient temperature -20 °C.. +40 °C
Terminals SL 13051.1: Push-in terminal 3 x 2 x 2.5 mm² (max. 6 A)
SL 13052.1: Push-in terminal 2 x 2.5 mm² for L + N (max. 6 A), screw terminal 2 x 2.5 mm² for PE
Weight 0.43 kg
Current consumption battery operation 20 mA
Connection power mains operation 8.0 VA / 3.9 W

4 Construction of the luminaire / Dimensional Drawings

4.1 GuideLed SL 13051.1 CG-S Recessed ceiling mounting

Mains cable connection: Fix with strain relief.

Ceiling cut out: Ø 64-68 mm.

Tension the clips.

Luminaire connection: Please observe polarity! Only connect LEDs if de-energised!

LEDs are ESD-sensitive ⚡.

Do not stare at the light source ⚠️.

Optional: Mount square bezel before luminaire mounting.

Luminaire for 5 lx vertical illumination of point of emphasis

Module enclosure: Needed height for introducing into the intermediate ceiling: approx. 100 mm.

4.2 GuideLed SL 13052.1 CG-S Ceiling mounting

Mains cable connection.

Set address of the module (chapter 6).

Fixing holes.

Orientate the lens to the point of emphasis (SL 13052.1).

Optional cable entries (IP20).

LEDs are ESD-sensitive ⚡.

Do not stare at the light source ⚠️.

4.3 GuideLed SL additional enclosure

Optional: For more space for wiring and cable entry, fix the optional available enclosure to the ceiling and connect it electrically. Introduce wiring into the luminaire and connect it. Fix the luminaire to the additional enclosure with the included screws. Now push the luminaire cover on the bottom part by attending to the right positioning (additional cable entries, 2).

5 Addressing

Special LED-Converter with integrated monitoring module for individual monitoring of luminaires (monitoring of the supply and automatic detection of faulty supply of the LED-module) with 20 addresses. The advanced switching and monitoring mode is only available in combination with CEAG CG-S-technology.

Address switch 1 Address switch 2 Luminaire address
0 0 Monitoring off
0 1 1
0 2 2
... ... ...
1 0 10
1 1 11
1 2 12
2 0 20
2 1 not permissible
2 2 not permissible
2 9 not permissible

6 Servicing / Maintenance

Observe the relevant national regulations applying to the maintenance, servicing and checking of electrical apparatus.

In case of returns, you need an RMA- number from us. For further information, see www.eaton.com.

The light source of this luminaire is not replaceable; when the light source reaches its end of life, the whole luminaire shall be replaced.

7 Disposal / Recycling

When disposing of defective devices, comply with valid regulations for recycling and waste disposal. Plastic parts are marked with corresponding symbols ♻️.

General Safety Instructions (Multilingual)

This section provides general safety instructions in multiple languages, including Bulgarian, Czech, Danish, German, Estonian, Greek, Spanish, French, Croatian, Italian, Latvian, Lithuanian, Hungarian, Dutch, Norwegian, Polish, Portuguese, Romanian, Russian, Slovak, Slovenian, Finnish, Swedish, and Turkish. Key safety points include:

Models: SL 13051.1, 13052.1 CG-S, Emergency Evacuation Safety Light, Emergency Evacuation, Safety Light

File Info : application/pdf, 16 Pages, 1.61MB

PDF preview unavailable. Download the PDF instead.

eaton-emergency-lighting-cps-safety-guideled-sl-13051.1-13052.1-cg-s-manual-en-de

References

Adobe PDF Library 16.0

Related Documents

Preview Eaton VisionGuard Operating Instructions
Comprehensive operating instructions for Eaton VisionGuard software, detailing installation, configuration, and usage for DualGuard-S and ZB-S emergency lighting systems.
Preview Eaton V-CG-SE 4-400W Operating Instructions
Comprehensive operating instructions for the Eaton V-CG-SE 4-400W electronic monitoring module, detailing its technical specifications, installation, mounting, and operational modes for safety lighting systems.
Preview Atlantic LED / Outdoor Wall CGLine+ Mounting and Operating Instructions
Comprehensive mounting and operating instructions for the Eaton Atlantic LED and Outdoor Wall CGLine+ emergency lighting luminaires. Covers installation, safety, operation, maintenance, technical data, and system monitoring for professional electricians.
Preview Eaton NexiTech LED CG-S Safety and Exit Sign Luminaires Datasheet
Comprehensive datasheet for Eaton's NexiTech LED CG-S series of safety and exit sign luminaires, detailing features, technical specifications, ordering information, and planning assistance for emergency illumination.
Preview Eaton ULTRALED 2-45/2-8 Emergency Lighting Installation and Operation Manual
Comprehensive manual for the Eaton ULTRALED 2-45 and ULTRALED 2-8 series emergency lighting fixtures. This guide covers installation, wiring, configuration, operation, autotest procedures, LED status indicators, and general safety instructions. It provides detailed textual descriptions of diagrams and technical specifications for these safety lighting products.
Preview Eaton Lighting Design Guide: Mains and Emergency Lighting
A comprehensive guide to lighting design, covering mains lighting principles, interior lighting considerations, and detailed requirements for emergency lighting systems. Includes standards, calculations, and practical design advice.
Preview Eaton ONVIF Camera Support for Smart Home Controller 2.0
Guide to supporting ONVIF cameras with the Eaton Smart Home Controller 2.0, including setup, troubleshooting, and the Camera Checker Tool.
Preview Eaton LoadStar-PS User and Installation Manual for Emergency Lighting Systems
This comprehensive user and installation manual provides detailed guidance for the Eaton LoadStar-PS central power system, designed for emergency lighting applications. It covers safety procedures, installation steps, operating modes, maintenance schedules, and technical specifications to ensure proper deployment and function.