SENECA T201DC100 Installation Manual
Preliminary Warnings
WARNING: The word WARNING followed by the symbol ! indicates conditions or actions that may endanger user safety. The word CAUTION followed by the symbol ! indicates conditions or actions that could damage the device or connected equipment. The warranty becomes void in case of improper use or alteration of the module or devices supplied by the manufacturer, necessary for correct operation, and if the instructions contained in this manual have not been followed.
WARNING: Before performing any operation, it is mandatory to read this manual in its entirety. The module must only be used by qualified technicians in the field of electrical installations. Specific documentation is available via the QR-CODE on page 1.
Only the manufacturer can repair the module or replace damaged components. The product is sensitive to electrostatic discharges; take appropriate measures during any operation.
Disposal of electrical and electronic waste (applicable in the European Union and in other countries that practice selective waste collection). The symbol present on the product or packaging indicates that the product must be taken to an authorized collection center for recycling of electrical and electronic waste.
Module Diagram
Housing: Black PA6 material.
Dimensions:
- Height: 68 mm
- Width: 36.7 mm
- Depth: 97 mm
- Connection terminal width: 21 mm
- Terminal block width: 26 mm
Preliminary Usage Instructions
The T201DC100 can be mounted anywhere in any position, respecting the intended ambient conditions. Use the supplied accessory for DIN rail mounting.
N.B.: Powerful magnetostatic fields can alter the measurement. Ensure the device is not placed near permanent magnets, electromagnets, or ferrous masses that produce strong magnetic field alterations. If the zero error is greater than declared, consider an alternative arrangement or orientation.
Technical Characteristics
Category | Specification | Details |
---|---|---|
REGULATIONS | EN61000-6-4 | Electromagnetic Compatibility (EMC) - Part 6-4: Generic standards - Emission standard for industrial environments. |
EN61000-6-2 | Electromagnetic Compatibility (EMC) - Part 6-2: Generic standards - Immunity for industrial environments. | |
EN60950 | Safety rules for electrical equipment for measurement, control, and laboratory use - Part 1: General requirements. | |
CONNECTIONS | Removable screw terminals, 4-way, 5 mm pitch, for 4 ÷ 20 mA loops. | |
SURGE CATEGORY | Bare conductor Category III (up to 300 V) Insulated conductor Category III (up to 600 V) |
|
RANGES | Monopolar: 0 – 10 A, Bipolar: -10 – 0 – +10 A Monopolar: 0 – 25 A, Bipolar: -25 – 0 – +25 A Monopolar: 0 – 50 A, Bipolar: -10 – 0 – +50 A Monopolar: 0 – 100 A, Bipolar: -25 – 0 – +100 A |
|
SUPERIMPOSED AC F (35 Hz) | Measurable peak value: -30 – +120 A Double half-wave rectified: -20 – 80 A Single half-wave rectified: -10 – 40 A |
|
AMBIENT CONDITIONS | Temperature: | -20 °C ÷ +70 °C |
Humidity: | 10% – 90% non-condensing. | |
Storage temperature: | -40 °C ÷ +85 °C | |
Protection index: | IP 20 | |
CONNECTIONS | TYPE | Removable terminal, 5 mm pitch, cables ≤ 2.5 mm², for 4 ÷ 20 mA loop. Tightening torque 7.0 Lb•inch = 0.8 N•m. Pass-through hole of 21 mm for current cable. |
LIMITS | Passive current loop: 4 ÷ 20 mA Internal failure / Overheat: 3.5 mA Under-range / Over-range: 3.6/21.0 mA Valid measurement: 3.8/20.5 mA |
|
LOOP VOLTAGE MIN. - MAX. | 6 V ÷ 28 V | |
OTHER PROTECTIONS | Polarity inversion Loop current limit in case of anomaly Protection against overheating |
|
MAXIMUM ERRORS | MEASUREMENT SECTION: | 0.1 % + 14 mA. |
OUTPUT SECTION: | 0.05 % + 4 μA. | |
TEMPERATURE COEFFICIENT | < 150 ppm/K. | |
ERROR FOR EMI | < 50 µA, test on bare bar Ø 10 mm | |
RESPONSE SPEED | Without filter: 100 ms With filter inserted: 600 ms |
Electrical Connections
ATTENTION: Cut off power before proceeding with wiring.
CURRENT OUTPUT FOR 4 ÷ 20 mA LOOP
It is possible to connect a voltage of maximum 28 V directly to the 4-20 mA loop at the output of the T201DC100.
Diagram:
- A diagram shows a loop with a current transducer (T201DC100) in series with a voltage source (Umax = 28V) and a current meter (mA).
CURRENT INPUT
ATTENTION: Ensure that the direction of the current flowing through the cable is as illustrated in the figure (entering).
To measure the current flowing through the cable, insert the cable into the central hole of the T201DC100 (as illustrated in the adjacent figure).
The maximum current that can be measured by the T201DC100 is 100 A.
To increase the current measurement sensitivity, insert the cable into the central hole of the T201DC100 multiple times, creating a series of turns. The sensitivity of the current measurement is proportional to the number of turns. Example: Set the lower scale, wind the wire around the hole 5 times, obtaining 4 turns. The full scale will be 5 times smaller, and the measurement will be more sensitive.
Arrange the turns symmetrically to maintain instrument accuracy.
Diagram:
- A diagram shows the T201DC100 with a cable passing through its central aperture. Arrows indicate the direction of current flow.
PARAMETERS VIA SWITCHES
Use the switches to select the scale (monopolar or bipolar) and to activate/deactivate the filter.
Monopolar Scale | Bipolar Scale | Filter | ||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
1 | 2 | 3 | 4 | Scale | 1 | 2 | 3 | 4 | Scale | 1 | 2 | 3 | 4 | Filter |
● | 0–10 A | ● | -10–10 A | ● | Deactivate | |||||||||
● | ● | 0–25 A | ● | ● | -25–25 A | ● | Activate | |||||||
● | ● | ● | 0–50 A | ● | ● | ● | -10–50 A | ● | KEY ON | |||||
● | ● | ● | ● | 0–100 A | ● | ● | ● | ● | -25–100 A |
Contact Information
SENECA s.r.l.; Via Austria, 26 – 35127 – PADOVA – ITALY; Tel. +39.049.8705359 - Fax +39.049.8706287
Technical Support: support@seneca.it
Product Information: sales@seneca.it
This document is the property of SENECA srl. Copying and reproduction are prohibited unless authorized. The content of this documentation corresponds to the products and technologies described. The data reported may be modified or supplemented for technical and/or commercial requirements.