1. APPLICATION
The ATEX Beacon Sounder series explosion-proof audio and visual caution spotlight fittings (hereinafter referred to as light fittings) are designed for use in Zone 1 and Zone 2 hazardous areas with explosive gas atmospheres (excluding coal mines) where IIA, IIB, and IIC explosive gases or vapors are present with T1 to T6 classifications. They are also suitable for Zone 21 and Zone 22 hazardous areas with combustible dust atmospheres.
These fittings are widely used for accident signal alarms or signal indications in environments such as chemical plants, stockrooms, fueling stations, oil drilling platforms, and the oil industry, where 10~24V DC/AC circuits are present.
2. CATALOGUE NUMBER LOGIC
The catalogue number logic for the ATEX Beacon Sounder is structured as follows:
- Product Type: ATEX Beacon Sounder
- Lamp Colour: R (Red), G (Green), Y (Yellow)
- Description: Explosion-proof audio and visual caution spotlight fittings
3. COMPLIANCES
The product complies with the following standards:
- EN 60079-0, EN 60079-1, EN 60079-11, EN 60079-31
- IEC 60079-0, IEC 60079-1, IEC 60079-11, IEC 60079-31
4. WORKING CONDITIONS
- Ambient temperature: -40°C to +55°C
- Atmospheric pressure: 80 kPa (0.8 bar) to 110 kPa (1.1 bar)
- Normal oxygen content: 21% v/v
- Relative humidity: ≤95%
- Applicable Zones: Zone 1, Zone 2; T1 to T6; and Zone 21, Zone 22
- Environment: Areas without gas or vapor that affects insulation performance.
- Pollution grade: 3
5. MAIN TECHNICAL PARAMETERS
Parameter | Specification |
---|---|
EX-MARK | II 2 G Ex d ib IIC T6 Gb II 2 D Ex t IIIC T80°C Db IP66 |
Inlet thread | 25X 1.5 (NPT3/4" or G3/4" with connector on request) |
RATED VOLTAGE | 10~24V DC/AC |
Sound intensity | 100~120dB (R=1m) |
Flash frequency | 70 times/min |
Ingress protection | IP66, IP67 (optional) |
6. MAIN STRUCTURES
- Enclosure: Die-casting copper-free aluminium with high-pressure static plastic spraying surface.
- Glass tube: High-strength borosilicate glass with light transmission ≥88%.
- Cable entries are supplied with plugs. Cable glands (DQM-II or DQM-III recommended) are available on request.
7. INSTALLATION
- Installation must be performed by a licensed professional.
- Before installation, verify that the parameters on the nameplate match the field environment.
- Remove the seal plug at the inlet entry, pass cables through the Ex-cable gland into the light fitting, and connect to the terminal. Ensure power connections are correct and secure lock bolts.
- For Zone 1 installations, only compound barrier cable glands are permitted. For Zone 2, both compound barrier and rubber seal cable glands are acceptable.
- The light fittings must be earthed internally and externally.
- Refer to Attached Drawing 2 for wiring details and the schematic diagram.
8. INSPECTION AND MAINTENANCE
- Regular maintenance is required to ensure product performance. Contact Watchgas for spare parts if needed.
- Always disconnect power before performing maintenance.
- Properly protect flameproof threads during maintenance.
- Ensure electrical clearance and creepage distances comply with standards.
- The 'intrinsic safety' buzzer control panel is encapsulated and must not be disassembled. Contact Watchgas for replacement if accidentally damaged.
9. OUTLINE DIMENSION (REFER TO ATTACHED DRAWING 1)
A technical drawing illustrating the physical dimensions of the ATEX Beacon Sounder. Key measurements shown include a total height of approximately 230mm, a main body diameter of approximately 116mm, and a base diameter of approximately 146mm.10. TRANSPORTATION
Take appropriate weatherproof measures during transportation.
11. STORAGE
- Store light fittings in a ventilated, non-dropping, and non-liquid warehouse.
- Recommended storage temperature: -40°C to +55°C.
- Recommended relative humidity: ≤95%.
- Keep surroundings free from corrosive gases that could damage metal and insulation.
12. ORDERING INFORMATION
When ordering, please specify the ordering code and quantity according to the catalogue number logic. Indicate any special requirements.
Diagrams
Product Image: A red, cylindrical, explosion-proof beacon sounder unit. It features a clear dome on top, a side-mounted speaker grille, and a robust base with electrical connection points. The unit is designed for hazardous environments.
Attached Drawing 1: A technical drawing illustrating the physical dimensions of the ATEX Beacon Sounder. Key measurements shown include a total height of approximately 230mm, a main body diameter of approximately 116mm, and a base diameter of approximately 146mm.
Attached Drawing 2: A diagram detailing the internal wiring and circuit board layout. It shows a circuit board with terminals labeled R1, R2 (for red light and buzzer), Y1, Y2 (for yellow light and buzzer), and G1, G2 (for green light and buzzer). The diagram illustrates connections for the lamp, circuit board components, enclosure, label, base, and glass cover. A note indicates that cutting the Y1 cable can mute the fault sound.
EU DECLARATION OF CONFORMITY
Company: WAROM TECHNOLOGY INCORPORATED COMPANY
Address: 555 BAOQIAN ROAD, JIADING, SHANGHAI, CHINA
Declaration of Conformity
We declare under our sole responsibility that the following products fulfill the relevant directives:
- ATEX directive 2014/34/EU
Explosion-proof audio and visual caution spotlight fittings: BBJ81
EX-MARK: II 2 G Ex d ib IIC T6 Gb, II 2 D Ex t IIIC T80°C Db IP66
Standards applied: EN 60079-0 (2009), EN 60079-11 (2007), EN 60079-1 (2007), EN 60079-31 (2009)
Certifications: EC type certificate: LCIE 11 ATEX 3111X, Quality notification: PTB 03 ATEX Q082-6 - EMC directive 2014/30/EU
Standards applied: EN 55015 (2013)
Place and date: SHANGHAI, Jan 20, 2022
Note: EC type certificate has been issued by LCIE (Laboratoire Central des Industries Electriques), 33. av du Général Leclerc, BP8, 92266 Fontenay-aux-Roses cedex, France.
FOR MORE INFORMATION
Website: www.watchgas.com
Email: info@watchgas.com
EUROPE
Klaverbaan 121
2908 KD Capelle aan den IJssel
The Netherlands
AMERICAS
313 N. State Hwy 342
Red Oak, TX 75154
APAC
Woods Square Tower 1,
12 Woodlands Square,
#11-71, Singapore 737715
DECLARATION
To ensure product performance, please do not alter the product structure or replace accessories without prior permission. Failure to do so may void the company's responsibility. (610464012501)