DeltaV™ Electronic Marshalling
DeltaV™ Electronic Marshalling offers a new level of control system I/O performance, providing unprecedented flexibility and ease of use. The CHARM I/O card (CIOC) supports up to 96 individually configurable channels and is designed for multi-core home run cables in centrally located marshalling cabinets. It can also be installed in field junction boxes to reduce system design and installation costs. All communications are fully redundant from the channel (CHARM) to the DeltaV controller.
Benefits
- I/O Anywhere You Need It: DeltaV CIOC provides unparalleled flexibility in control system I/O topology using standard Ethernet infrastructure. Add I/O anywhere, from local cabinets to remote enclosures miles away, by simply installing the hardware and connecting it to the DeltaV control network. Each I/O card can serve I/O signals to any four controllers with 50-ms updates for fast, reliable control.
- Single Channel Granularity: The CHARM I/O architecture allows each individual channel to be characterized for the field device's requirements. Any instrument signal can be wired to any terminal block and electronically marshalled by installing the appropriate CHARM and assigning the channel to a controller. Home run multi-core instrument cables can be landed in order on a series of CHARM terminal blocks without concern for signal types.
- Reduces Installed Cost of System: DeltaV Electronic Marshalling reduces overall system costs by eliminating internal cabinet cross-wiring, reducing footprint, simplifying I/O channel assignments, and minimizing Factory Authorized Testing activities. It provides separation between I&E hardware installation schedules and control strategy development, allowing wiring to begin earlier. Late scope changes can be accommodated without rewiring. Adding control capacity does not require re-wiring I/O; simply assign control modules and their I/O signals to the new controller.
- Fully Redundant Architecture: The CIOC architecture is fully redundant, starting with two I/O cards on a carrier. The carrier has redundant communication modules for primary and secondary network connections and two 24V DC input power connections. The carrier connects to the CHARMs baseplates, providing redundant power and communication buses to the CHARMs. Redundancy extends down to the individual channel.
- Field-Mounted Capable Hardware: All CIOC components are rated for installation in Class 1/Div 2 or Zone 2 hazardous locations. Extended operating temperature ranges and G3 environment rating allow installation in field-mounted junction boxes, reducing the footprint required in central equipment rooms and the overall wiring infrastructure.
- Plug and Play I/O: The DeltaV CIOC is designed for ease of use in physical installation and software tools. Components snap together with secure DIN-rail latches and interlocking carrier connectors. Up to 96 I/O channels can be attached to a DIN-rail in minutes. Inserting CHARMs auto-senses the node, creating the I/O definition in the DeltaV configuration database. CHARMs use a self-keying system to automatically set a channel for a specific CHARM type, preventing incorrect insertion. All, one, or any number of channels can be assigned to a controller with a simple click or drag and drop.
Product Description
Electronic Marshalling hardware includes:
- CHARM I/O Carrier: DIN rail-mounted, supports a redundant pair of CHARM I/O Cards, redundant 24V DC power connectivity, and redundant Ethernet communication modules.
- CHARM I/O Card (CIOC): Provides communication between CHARMs and the Ethernet I/O network to M-series, S-series, and PK controllers. The CIOC has Achilles Communications Certification Level 1, and the redesigned CIOC2 has Level 2 certification. The CIOC2 is a drop-in replacement for the CIOC (v14.3 or later required).
- CHARM Baseplate: DIN rail-mounted with interleaving power and bus connectors. Supports 12 CHARMs and their terminal blocks, plus connection for injected field power.
- CHARM Terminal Block: Removable terminal block providing terminal connections to field wiring and a physical latch for the CHARM.
- CHARMS: Characterization Module for each field signal, providing basic analog-to-digital conversion and signal isolation to the redundant communication bus.
- Cable Extenders: Provide flexibility in carrier mounting.
- I/O Bus Termination: Provides bus terminations for the redundant I/O bus.
- Labeling Features: Available for baseplate and channel identification to aid maintenance.
Field power is provided through a redundant 24V DC bus to each CHARM, with up to 100 mA per CHARM. Higher current channels can be powered through integrated power injection bus local to each CHARM Baseplate.
CHARM Types
A variety of analog and discrete CHARMs are available to meet specific requirements, including:
- AI 4-20 mA HART
- RTD
- Thermocouple / mV
- AI 0-10V DC Isolated
- AO 4-20 mA HART
- DI NAMUR
- DI 24V DC low-side sense (dry contact)
- DI 24V DC Isolated
- DO 24V DC High Side
- DO 100mA Energy Limited
- DO 24V DC Isolated
- 24V DC Power
- DI 120V AC Isolated
- DI 120V AC Isolated Plus
- DI 230V AC Isolated
- DO V AC Isolated
Hardware Specifications
Common Environmental Specifications (all components) | Value |
---|---|
Operating Temperature* | -40 to 70°C (-40 to 158°F) |
Storage Temperature | -40 to 85°C (-40 to 185°F) |
Relative Humidity | 5 to 95%, non-condensing |
Protection Rating | IP 20 |
Airborne Contaminants | ISA-S71.04-1985 Airborne Contaminants Class G3 Conformal coating |
Shock | 10 g 1/2-sine wave for 11 ms |
Vibration | 1 mm peak-to-peak from 2 to 13.2 Hz, 0.7 g from 13.2 to 150 Hz |
*Operating any electronics at the higher end of its temperature range for long periods will shorten its expected lifetime. Refer to the 'Effects of Heat and Airflow Inside an Enclosure' White Paper for more information.
**When used with copper Ethernet I/O Ports (Copper IOP), the operating temperature range is limited to -40 to 60°C (-40 to 140°F).
***When used with all CHARM Types except the DI 120 V AC Isolated Plus CHARM, the operating temperature range is limited to -40 to 60°C (-40 to 140°F).
CHARM Keying Posts
Terminal Blocks contain keying posts that are automatically set and locked to the unique position of the installed CHARM, preventing the insertion of an incorrect CHARM during maintenance. Keys are shipped in a neutral position and set upon CHARM insertion. They can be manually reset to re-task a channel for a different signal type. The keying mechanism consists of two keying posts that rotate and lock into the terminal block base. Each CHARM type has a unique key setting.
ASCO Numatics 580 CHARM Node
The 580 CHARM node enables easy solenoid valve integration into DeltaV with Electronic Marshalling. The new 580 CHARM node connects directly to the CIOC via redundant CHARM Baseplate extender cables. DeltaV can autosense the I/O as DO Solenoid Valve CHARMs, similar to other CHARMs.
Benefits of the new 580 CHARM Node:
- Redundant communications and power connections to pneumatic valve manifolds.
- Eliminates the need for additional dedicated networks like Profibus-DP, simplifying system I/O mapping.
- Expands Electronic Marshalling I/O to include ASCO Numatics pilot valve manifolds, enhancing the "I/O Anywhere" concept.
- Reduces programming and commissioning time.
System Compatibility
DeltaV Electronic Marshalling hardware requires DeltaV v11.3.1 or later software. Assigning CHARMs to MD Plus, MQ, MX, and PK controllers is supported in DeltaV v14.3 and later. CHARM I/O Card 2 (CIOC2) requires DeltaV v14.3 or later software.
Electronic Marshalling requires the use of DeltaV Smart Switches between controllers and CIOCs. Refer to the 'Network Considerations for M-series with Electronic Marshalling' White Paper for details.
Certifications
The following certifications are available for DeltaV Electronic Marshalling:
- CE
- EMC - EN 61326-1
- FM (USA)
- CSA
- ATEX
- IEC-Ex
- Marine Certifications: IACS E10, ABS Certificate of Design Assessment, DNV-GL Marine Certificate
- Achilles Communications Certification: CIOC Level 1 (v13.3.1, v14.FP1), CIOC2 Level 2 (v14.3, v14.FP1)
Hazardous Area/Location
DeltaV Electronic Marshalling solutions can be installed and used based on the following Standards:
- FM (USA): Class I, Division 2, Groups A, B, C, D, T4
- CFM (Canada): Class I, Division 2, Groups A, B, C, D, T4
- ATEX: II 3G Ex nA IIC T4 Gc, II 3G Ex nA [ic] IIC T4 Gc, II 3G Ex nA nC IIC T4 Gc
- IEC-Ex: II 3G Ex nA IIC T4 Gc, II 3G Ex nA ic IIC T4 Gc, II 3G Ex nA nC IIC T4 Gc
Additional Field Circuit Certification Information
This table details the certification status for various CHARM types and their assemblies across different hazardous area classifications.
CHARM Type Description | Class I Division II Non Incendive | Zone 2 Ex nL Certified | Zone 2 Ex ic Certified | Zone 2 Ex nA Certified |
---|---|---|---|---|
DI NAMUR | ✓ | ✓ | ✓ | ✓ |
DI 24V DC Low-Side Sense (Dry Contact) | ✓ | ✓ | ✓ | ✓ |
DI 24V DC Isolated | — | — | ✓ | ✓ |
DO 24V DC High-Side | ✓ | ✓ | ✓ | ✓ |
DO 24V DC 100mA Energy Limited | ✓ | ✓ | ✓ | ✓ |
DO 24V DC Isolated | — | — | ✓ | ✓ |
24V DC Power | — | — | ✓ | ✓ |
AI 4-20 mA HART | ✓ | ✓ | ✓ | ✓ |
Thermocouple/mV Input | ✓ | ✓ | ✓ | ✓ |
RTD Input | ✓ | ✓ | ✓ | ✓ |
AI 0-10V DC Isolated | ✓ | ✓ | ✓ | ✓ |
AO 4-20 mA HART | ✓ | ✓ | ✓ | ✓ |
DI 120V AC Isolated | — | — | — | — |
DI 120V AC Isolated Plus | — | — | — | — |
DI 230V AC Isolated | — | — | — | ✓ |
DO V AC Isolated | — | — | — | ✓ |
CHARMS and Terminal Block Assembly Description | Class I Division II Non Incendive | Zone 2 Ex nL Certified | Zone 2 Ex ic Certified | Zone 2 Ex nA Certified |
---|---|---|---|---|
DO 24V DC High-Side CHARM with Relay Output Terminal Block | ✓ | ✓ | ✓ | ✓ |
Thermocouple/mV Input CHARM with Thermocouple/mV Terminal Block | ✓ | ✓ | ✓ | ✓ |
24V DC Power CHARM with Fused-Injected-Power Terminal Block | — | — | ✓ | ✓ |
AI 4-20 mA HART with 3-wire AI Fused Injected Power Terminal Block | — | — | ✓ | ✓ |
(— Stands for: Not Applicable; ✓ Stands for: Certification is in place.)
Ordering Information
This section details the model numbers for various DeltaV Electronic Marshalling components.
CHARM I/O Cards and Carrier
Description | Model Number |
---|---|
Redundant CIOC2 with Copper Ethernet, includes redundant pair of CHARM I/O Card 2, CHARM I/O Carrier with Screw Terminals, Copper I/O Ports, a Baseplate Identifier and a Baseplate Separation Wall | SE6505T01 |
Redundant CIOC2 with fiber optics Ethernet, includes redundant pair of CHARM I/O Card 2, CHARM I/O Carrier with Screw Terminals, Fiberoptic I/O Ports, a Baseplate Identifier and a Baseplate Separation Wall | SE6505T02 |
Redundant CIOC Carrier Assembly with Copper Ethernet, includes CHARM I/O Carrier with Screw Terminals, Copper I/O Ports, a Baseplate Identifier and a Baseplate Separation Wall | SE6501T05 |
Redundant CIOC Carrier Assembly with fiber optics Ethernet, includes CHARM I/O Carrier with Screw Terminals, Fiberoptic I/O Ports, a Baseplate Identifier and a Baseplate Separation Wall | SE6501T06 |
Redundant CIOC2, includes 2 CHARMs I/O Card 2, (Order these with standard cabinets) | SE6504 |
CHARM Baseplates Assemblies
Description | Model Number |
---|---|
CHARMS Baseplate Assembly, includes CHARMs Baseplate, CHARM Address Terminal Block with Screw Terminals, 12 Standard CHARM Terminal Blocks and a Baseplate Identifier | SE4601T07 |
CHARMS Baseplate Assembly with 3-wire DI Fused Fused-Injected-Power, includes CHARMS Baseplate, CHARM Address Terminal Block with Screw Terminals, 12 3-wire DI Fused-Injected-Power CHARM Terminal Blocks and a Baseplate Identifier | SE4601T09 |
CHARMS Baseplate Assembly with Fused-Injected Field Power, includes CHARMS Baseplate, CHARM Address Terminal Block with Screw Terminals, 12 Fused-Injected-Power CHARM Terminal Blocks and a Baseplate Identifier | SE4601T08 |
CHARMS Baseplate Assembly with Relay Output, includes CHARMS Baseplate, CHARM Address Terminal Block with Screw Terminals, 12 Relay Output CHARM Terminal Blocks and a Baseplate Identifier | SE4601T05 |
CHARM I/O Baseplate Address Plugs
Description | Model Number |
---|---|
CHARMS Addressing Plugs, includes Address Plugs 1 through 8 | SE4602 |
CHARMS Addressing Plugs, includes Address Plugs 1 through 4 | SE4613 |
Each vertical DIN rail requires a DIN Rail stop to lock baseplates in position. Order VE4054DRS, which is a box of 5.
CHARM I/O Baseplate Extender and Terminator
Description | Model Number |
---|---|
CHARMS Baseplate Extender with Cable Connectors, Top (Male) includes a Baseplate Identifier and a Baseplate Separation Wall | SE4603T05 |
CHARMS Baseplate Extender with Cable Connectors, Bottom (Female) includes a Baseplate Identifier and a Baseplate Separation Wall | SE4603T06 |
CHARMS Baseplate Terminator, Top (Male) includes a Baseplate Identifier and a Baseplate Separation Wall | SE4604T03 |
CHARMS Baseplate Terminator, Bottom (Female) includes a Baseplate Identifier and a Baseplate Separation Wall | SE4604T04 |
CHARM I/O Baseplate Extender Cables
Description | Model Number |
---|---|
CHARMS Baseplate Cables, includes two 0.5 m cables | SE4605T02 |
CHARMS Baseplate Cables, includes two 1 m cables | SE4605T03 |
CHARMS Baseplate Cables, includes two 2 m cables | SE4605T04 |
Low Voltage Instrumentation CHARMs
Description | Model Number |
---|---|
DI NAMUR | SE4301T01 |
DI 24V DC Low-Side Sense (Dry Contact) | SE4301T02 |
DI 24V DC Isolated | SE4301T07 |
DO 24V DC High-Side | SE4302T01 |
DO 24V DC Isolated | SE4302T02 |
DO 24V DC 100mA Energy Limited | SE4302T04 |
24V DC Power | SE4302T05 |
AI 4-20 mA HART | SE4303T01 |
Thermocouple/mV Input | SE4303T02 |
RTD Input | SE4303T03 |
AI 0-10V DC Isolated | SE4303T04 |
AO 4-20 mA HART | SE4304T01 |
High Voltage Instrumentation CHARMs
Description | Model Number |
---|---|
DI 120V AC Isolated | SE4301T03 |
DI 120V AC Isolated Plus | SE4301T05** |
DI 230V AC Isolated | SE4301T04 |
DO V AC Isolated | SE4302T03 |
Low Voltage Instrumentation CHARMs and Terminal Block Assemblies
Description | Model Number |
---|---|
DO 24V DC High-Side CHARM with Relay Output Terminal Block | SE4302T51 |
Thermocouple/mV Input CHARM with Thermocouple/mV Terminal Block | SE4303T52 |
24V DC Power CHARM with Fused-Injected-Power Terminal Block | SE4302T55* |
* 24V DC Power CHARM requires DeltaV v12.3 or later software to be able to configure and use the diagnostic information.
** The DI 120V AC Isolated Plus CHARM requires a HotFix to be used with DeltaV v11.3.1 and v12.3.1.
Additional Ordering Information for Protection Cover and Terminal Blocks
Protection Cover (fits all terminal blocks)
Description | Model Number |
---|---|
CHARM Protection Cover; Package of 12 | SE6103 |
Terminal Blocks
Description | Model Number |
---|---|
Standard CHARM Terminal Block | SE4501 |
3-wire DI Fused-Injected-Power Terminal Block | SE4512 |
Fused-Injected-Power Terminal Block | SE4502 |
Relay Output Terminal Block | SE4503 |
Thermocouple/mV Terminal Block | SE4504 |
3-wire AI Fused Injected Power Terminal Block | SE4511 |
CHARM I/O Labeling and Spare part ordering Information
CHARM I/O Labeling and Spare Parts
Description | Model Number |
---|---|
Channel Identifier Labels for CHARM Baseplates; Package of 8 | SE4606T02 |
Charm Baseplate Identifier; Package of 9 | SE4606T03 |
Power Terminal Plug for CHARM I/O Carrier | KJ4005X1-BF1 |
250V 2A Fuse for Fused Terminal Block; Box of 20 | KJ4010X1-BC1 |
I/O Port Switch Module; Copper; for CIOC Carriers | KL1601X1-BA1 |
I/O Port Switch Module; Fiber; for CIOC Carriers | KL1602X1-BA1* |
* Fiberoptic Ethernet I/O Ports are not cascadeable.
ASCO Numatics Series 580 CHARM node
ASCO Numatics Series 580 CHARM node parts
Description | ASCO Part Number |
---|---|
580 CHARM node | Contact ASCO* |
580 CHARM Power and Communication Cable Set 2 Cables, 1.5 M Length, with M12 and sub-D connectors | Contact ASCO* |
* Requires hotfix for DeltaV v11.3.1, v12.3.1, and v13.3. Sold directly from ASCO, please see more detail at http://www.asco.com/580charm.
Related Products
DeltaV Electronic Marshalling with Distributed CHARMS
Prerequisites
DeltaV Electronic Marshalling hardware requires DeltaV v11.3.1 or later software. Assigning CHARMs to MD Plus, MQ, MX, and PK controllers is supported in DeltaV v14.3 and later, but is not supported on M-series Controller Interfaces to PROVOX and RS3. CHARM I/O Card 2 (CIOC2) requires DeltaV v14.3 or later software. Electronic Marshalling requires the use of DeltaV Smart Switches between controllers and CIOCs; refer to the Network Considerations for M-series with Electronic Marshalling White Paper when adding Electronic Marshalling to M-series systems.