Product Overview
The Mitsubishi Electric NAXMMX24A132AA is a Multi-Zone Inverter Heat-Pump System designed for efficient heating and cooling. It offers advanced features for performance and comfort.
Key Features:
- Variable speed INVERTER-driven compressor for precise temperature control and energy efficiency.
- Optional base pan heater for enhanced cold-weather performance.
- Quiet outdoor unit operation, with sound levels as low as 55 dB(A).
- Integrated protection systems: High pressure protection, compressor thermal protection, and compressor overcurrent detection.
- Fan motor overheating/voltage protection for durability.
- ENERGY STAR® certified (specifically for non-ducted applications), indicating high energy efficiency.
Image Description: The outdoor unit is depicted as a white, rectangular cabinet with a prominent fan grille on the side. It is mounted on a base with visible connection points and a control panel area.
Specifications: NAXMMX24A132AA
(For data on specific indoor units, refer to the MXZ-C Technical and Service Manual.)
Parameter | Unit | Cooling* (Non-ducted / Ducted) | Heating at 47°F* (Non-ducted / Ducted) | Heating at 17°F* (Non-ducted/Ducted) | Connectable Capacity |
---|---|---|---|---|---|
Rated Capacity | Btu/h | 22,000 / 23,600 | 25,000 / 24,600 | 14,000 / 14,000 | 12,000 - 27,000 |
Capacity Range | Btu/h | 9,500-22,000 / 9,500-25,500 | 15,500-30,600 / 15,500-29,400 | N/A | |
Rated Total Input | W | 1,620 / 2,100 | 1,750 / 1,900 | 2,120 / 2,230 |
Parameter | Details |
---|---|
Energy Star® | Yes (ENERGY STAR products are third-party certified by an EPA-recognized Certification Body.) |
Power Supply | 208/230V, 1-Phase, 60 Hz |
Electrical Requirements | Recommended Fuse/Breaker Size: 25 A MCA: 22.1 A |
Voltage | AC 208/230V DC ±24V (for control) |
Compressor | INVERTER-driven Scroll Hermetic |
Fan Motor (ECM) | 2.43 A |
Sound Pressure Level (Cooling) | 51 dB(A) |
Sound Pressure Level (Heating) | 55 dB(A) |
External Dimensions (H x W x D) | 31-11/32" x 37-13/32" x 13" (796 x 950 x 330 mm) |
Net Weight | 137 Lbs (62 kg) |
External Finish | Munsell No. 3Y 7.8/11 |
Refrigerant Pipe Size O.D. (Liquid / High Pressure) | 1/4" (6.35 mm) |
Refrigerant Pipe Size O.D. (Gas / Low Pressure) | A Port: 1/2" (12.7 mm); Other: 3/8" (9.52 mm) |
Max. Refrigerant Line Length | 230 ft (70 m) |
Max. Piping Length for Each Indoor Unit (If IDU is Above ODU) | 82 ft (25 m) |
Max. Piping Length for Each Indoor Unit (If IDU is Below ODU) | 49 ft (15 m) |
Max. Refrigerant Pipe Height Difference (If IDU is Above ODU) | 49 ft (15 m) |
Connection Method | Flared/Flared |
Refrigerant | R410A |
Operating Range and Energy Efficiencies
Parameter | Outdoor Condition | Energy Efficiencies | |||||
---|---|---|---|---|---|---|---|
Indoor Unit Type | SEER | EER | HSPF | COP @ 47°F | COP @ 17°F | ||
Cooling | 14 to 115° F (-10 to 46° C) DB | Non-ducted (e.g., 06+09+09) | 20.0 | 13.6 | 9.8 | 4.2 | 2.97 |
Ducted and Non-ducted | 18.0 | 12.4 | 9.5 | 4.0 | 2.79 | ||
Ducted (e.g., 09+09+09) | 16.0 | 11.2 | 9.2 | 3.8 | 2.61 | ||
Heating | 5 to 65° F (-15 to 18° C) WB | (Values listed above for Cooling also apply to Heating performance based on indoor unit configuration) |
Notes: For actual capacity performance based on indoor unit type and number of indoor units connected, please refer to MXZ Operational Performance. The maximum connectable capacity can exceed rated capacity, but the outdoor unit cannot provide more than 100% of its rated capacity. This over-capacity capability is useful for load shedding or applications where not all connected units operate simultaneously.
Outdoor Unit Accessories
Accessory | Description / Part Number |
---|---|
Air Outlet Guide | Air Outlet Guide (1 Piece) |
Ball Valve | Refrigeration Ball Valve - 1/2" (BV12FFS12) Refrigeration Ball Valve - 1/4" (BV14FFS12) Refrigeration Ball Valve - 3/8" (BV38FFS12) Refrigeration Ball Valve - 5/8" (BV58FFS12) |
Distribution pipe for Branch Box | M-NET Converter (PAC-IF01MNT-E) |
Drain Socket | Drain Socket (PAC-SG60DS-E) |
Hail Guards | Hail Guard (HG-A9) |
Mounting Pad | Condensing Unit Mounting Pad: 16" x 36" x 3" (ULTRILITE1) Outdoor Unit 3-1/4 inch Mounting Base (Pair) - Plastic (DSD-400P) |
Optional Defrost Heater | Base Heater (PAC-646BH-E) |
Port Adapter | Adaptor: 1/2" x 3/8" (MAC-A455JP-E) Adaptor: 1/2" x 5/8" (MAC-A456JP-E) Adaptor: 3/8" x 1/2" (MAC-A454JP-E) Adaptor: 3/8" x 5/8" (PAC-SG76RJ-E) |
Power Supplies and Auxiliary Components | M-Net Control Wire, 1,000' Roll (16-AWG, Standard, Twisted Pair, Shielded, Jacketed-Plenum rated) (CW162S-1000) M-Net Control Wire, 250' Roll (16-AWG, Standard, Twisted Pair, Shielded, Jacketed-Plenum rated) (CW162S-250) |
Stand | 18" Single Fan Stand (QSMS1801M) 24" Single Fan Stand (QSMS2401M) Condenser Wall Bracket (QSWB2000M-1) Condenser Wall Bracket -Stainless Steel Finish (QSWBSS) Outdoor Unit Stand 12" High (QSMS1201M) |
Outdoor Unit Dimensions and Installation Clearances
The following describes the physical dimensions and required installation clearances for the NAXMMX24A132AA outdoor unit.
Unit Dimensions
Diagram Description: The diagram shows the outdoor unit from multiple views (front, side, top). Key dimensions are indicated with lines and measurements in inches. The front view shows the main fan grille and control panel area. Side views highlight the depth and height, including mounting points and pipe connection ports. The top view shows the overall footprint. Specific measurements include: Height (approx. 37-13/32 inches), Width (approx. 31-11/32 inches), Depth (approx. 13 inches). It also indicates knockout holes for wiring and pipe connections, and U-shaped notches for foundation bolts (M10).
Installation Clearances (Free Space and Service Space)
Adequate space around the unit is crucial for proper airflow and maintenance.
- 1. FREE SPACE: Minimum clearances required for unobstructed airflow.
- Front: 19-11/16" or more
- Side (Left/Right): 3-15/16" or more
- Top: 3-15/16" or more
- Rear: 3-15/16" or more
- 2. SERVICE SPACE: Minimum clearances required for maintenance access.
- Front: 13-25/32" or more
- Side (Left/Right): 3-15/16" or more
- Top: 19-11/16" or more
- Rear: 3-15/16" or more
Note: Specific service access requirements may vary. Refer to the installation manual for detailed guidance.
Connection Details
The unit supports connections for multiple indoor units via refrigerant piping. The diagram shows pipe sizes for different connection ports (e.g., Unit A, Unit B, Unit C).
- LIQ (Liquid) Pipe: Typically 1/4" (Ø6.35) FLARE for smaller connections, and 1/2" (Ø12.7) FLARE for larger connections.
- GAS (Gas) Pipe: Typically 3/8" (Ø9.52) FLARE.
The system utilizes R410A refrigerant.