R. STAHL 8530/1-MCB-STA101-B32-500-2 Line Protection Circuit Breaker

Article Number: 293985

Product Description

The R. STAHL 8530 series line protection circuit breakers offer reliable current limitation for short circuits with high switching capacities of 10, 15, or 25 kA. These components are designed for minimal line load and high selectivity with upstream fuses. They are modular, available in 1 to 4 pole versions, with nominal currents from 0.5–63 A, and a maximum installation capacity of 4.5 partial units (UP).

Key Features

Technical Characteristics

Explosion Protection

Application Domain (Zones) 1, 2
Application Domain (Zones) Note Usable in Zone 21 / 22 with protection by Ex tb / tc enclosure
IECEx Gas Certificate IECEx FMG 19.0029U
IECEx Gas Explosion Protection Ex db eb IIC Gb
ATEX Gas Certificate FM19ATEX0191U
ATEX Gas Explosion Protection II 2G Ex db eb IIC Gb
Certificates ATEX (FM), Brazil (ULB), China (CQST), IECEx (FM)
Certificate of Conformity ATEX Conformity Certificate (ATEX)

Electrical Characteristics

Rated operational voltage AC 230 V
Rated service current 32 A
Frequency 50/60 Hz
Rated ultimate short-circuit breaking capacity 10 kA
Electrical service life 104
Mechanical service life 2 x 104
1st Auxiliary Function Auxiliary contact 1 changeover + signal contact 1 changeover
Voltage 1st Auxiliary Function AC 230 V
Max. Current 1st Auxiliary Function 2 A
2nd Auxiliary Function None
Max. Voltage 2nd Auxiliary Function DC -
Tripping Characteristic B
Number of poles 1 pole

Ambient Conditions

Ambient Temperature -40 °C ... 70 °C (-40°F ... +158°F)
Ambient Temperature Note Ambient temperatures different from the above based on current certificates, upon request.

Mechanical Characteristics

Degree of Protection (IP) (IEC 60529) IP2X
Housing Material Thermoplastic
Connection Terminal Minimum Cross-section 1.5 mm²
Connection Terminal Maximum Cross-section 25 mm²
Connection Terminal AWG min. 16 AWG
Connection Terminal AWG max. 4 AWG
Connection Terminal 2 Minimum Cross-section 1.5 mm²
Connection Terminal 2 Maximum Cross-section 10 mm²
Connection Terminal 2 AWG min. 16 AWG
Connection Terminal 2 AWG max. 8 AWG
Conn. terminal aux. contact min. 0.5 mm²
Conn. terminal aux. contact max. 4 mm²
Conn. terminal aux. contact min. AWG 18 (unece.unit.AWG)
Conn. terminal aux. contact max. AWG 14 (unece.unit.AWG)
Clamping torque min. 2 N·m
Clamping torque max. 3 N·m
Connection Terminal Note Connection of 2 conductors (upper and lower chamber simultaneously): Upper and lower chamber max. 16 / 10 mm² (Connection can be made with a maximum cross-section difference between the upper and lower chamber.) Permitted combination possibilities for connection cross-sections are indicated in the operating manual.

Dimensions

Width 65 mm (2.56 in)
Length 165 mm (6.5 in)
Mounting Depth 138.3 mm (5.44 in)
Weight 1 kg (2.205 lb)

Mounting / Installation

Clamping torque 2-3 N·m (17.7 ... 26.6 lbf-in)
Clamping torque auxiliary contact 0.4-0.6 Nm (3.5 ... 5.3 lbf-in)

Technical Drawings

Tripping Characteristic Curve

The graph shows the tripping characteristic for a cold state. The x-axis represents multiples of the rated current (I/In), and the y-axis represents the tripping time in seconds or minutes. Different curves are shown for AC and DC, with characteristic B indicated.

Overall Dimensions

Diagrams showing the overall dimensions of the circuit breaker unit (8530/1; 2 division units) are provided, with measurements in millimeters and inches. Key dimensions include width (65 mm / 2.56 in), length (165 mm / 6.50 in), mounting depth (138.3 mm / 5.44 in), and height (91.50 mm / 3.60 in).

Accessories

Quadruple Locking Device

A locking/unlocking system that allows individual locking of the component using up to 4 cylinder locks.

Description Article Number
Quadruple locking/unlocking device for individual locking of the component using up to 4 cylinder locks. 227232

Fixing Kit

Description Article Number
A fixing kit for mounting the component onto a mounting plate without a DIN rail. 276618

Cylinder Lock

Description Article Number
For locking (shackle Ø 3) 107115

PDF preview unavailable. Download the PDF instead.

ex-ficha-tecnica-individual-disyuntor-8530-1-mcb-sta101-b32-500-2-293985-fr-fr-rstahl Adobe PDF Library 17.0

Related Documents

Preview R. STAHL 8530/1-MCB-STA101-B6-500-2 Line Protection Circuit Breaker
Technical specifications and features of the R. STAHL 8530/1-MCB-STA101-B6-500-2 line protection circuit breaker, including explosion protection, electrical characteristics, mechanical specifications, and accessories.
Preview R. STAHL 8530/1-MCB-STA101-C10-500-2 Line Protection Circuit Breaker Technical Data
Detailed technical specifications, features, and dimensions for the R. STAHL 8530/1-MCB-STA101-C10-500-2 line protection circuit breaker, including explosion protection certifications and electrical characteristics.
Preview R. STAHL 8530/1-MCB-STA101-C20-500-2 Line Protection Circuit Breaker
Technical specifications and features of the R. STAHL 8530/1-MCB-STA101-C20-500-2 line protection circuit breaker, including explosion protection, electrical characteristics, mechanical specifications, and accessories.
Preview R. STAHL 8530/1-MCB-STA101-B16-500-2 Circuit Breaker for Line Protection
Technical specifications and features of the R. STAHL 8530/1-MCB-STA101-B16-500-2 circuit breaker for line protection, including explosion protection, electrical characteristics, mechanical specifications, and accessories.
Preview R. STAHL 8530/1-MCB-STA101-C16-500-2 Line Protection Circuit Breaker
Technical specifications and features of the R. STAHL 8530/1-MCB-STA101-C16-500-2 line protection circuit breaker, including electrical characteristics, mechanical specifications, and explosion protection details.
Preview R. STAHL 8530/1-MCB-STA101-C40-500-2 Circuit Breaker - Technical Specifications and Features
Detailed technical specifications, features, and accessories for the R. STAHL 8530/1-MCB-STA101-C40-500-2 line protection circuit breaker, including explosion protection data, electrical characteristics, mechanical specifications, and installation details.
Preview R. STAHL 8530/1-MCB-STA101-C6-500-2 Line Protection Circuit Breaker
Technical specifications and features of the R. STAHL 8530/1-MCB-STA101-C6-500-2 line protection circuit breaker, including explosion protection, electrical characteristics, mechanical specifications, and accessories.
Preview R. STAHL Miniature Circuit Breaker 8530/1-MCB-STA101-C6-500-2: Technical Specifications and Features
Detailed technical specifications, features, and accessories for the R. STAHL 8530 series miniature circuit breaker (MCB), model 8530/1-MCB-STA101-C6-500-2. Includes information on explosion protection, electrical data, ambient conditions, dimensions, and mounting.