Legrand DMX³ 2500 Open Circuit Breakers and DMX³-I 2500 Open Switches
This document provides comprehensive technical information for the Legrand DMX³ 2500 series of open circuit breakers and DMX³-I 2500 series of open switches. These devices are designed for optimal protection in electrical installations up to 6300 A, offering robust electrical and mechanical performance, high breaking capacity, and extensive accessory options.
1. Utilization
The DMX³ open circuit breakers offer optimal solutions for protection at the origin of low-voltage electrical installations (IEC/EN 60364-1) up to 6300 A. Their electrical and mechanical robustness, breaking capacity, and accessory possibilities make them well-suited for these requirements. The DMX³ range also includes the DMX³-I range of switches without trip units, offering high performance in terms of insulation, robustness, closing, and withstand capacity. Both ranges are designed to enhance service continuity, considering energy efficiency and environmental aspects.
2. Range
The DMX³ 2500 series includes fixed and withdrawable versions with UP MP2.10 and MP4.10 protection units, available in 50 kA, 65 kA, and 100 kA breaking capacities.
2.1 DMX³ 2500 Fixed Version with UP MP2.10/MP4.10
In (A) | 50 kA | 65 kA | 100 kA | |||
3P | 4P | 3P | 4P | 3P | 4P | |
630 | 0 283 60 | 0 283 70 | 0 283 80 | 0 283 90 | 0 284 00 | 0 284 10 |
800 | 0 283 61 | 0 283 71 | 0 283 81 | 0 283 91 | 0 284 01 | 0 284 11 |
1000 | 0 283 62 | 0 283 72 | 0 283 82 | 0 283 92 | 0 284 02 | 0 284 12 |
1250 | 0 283 63 | 0 283 73 | 0 283 83 | 0 283 93 | 0 284 03 | 0 284 13 |
1600 | 0 283 64 | 0 283 74 | 0 283 84 | 0 283 94 | 0 284 04 | 0 284 14 |
2000 | 0 283 65 | 0 283 75 | 0 283 85 | 0 283 95 | 0 284 05 | 0 284 15 |
2500 | 0 283 66 | 0 283 76 | 0 283 86 | 0 283 96 | 0 284 06 | 0 284 16 |
2.2 DMX³ 2500 Withdrawable Version with UP MP2.10/MP4.10
In (A) | 50 kA | 65 kA | 100 kA | |||
3P | 4P | 3P | 4P | 3P | 4P | |
630 | 0 284 20 | 0 284 30 | 0 284 40 | 0 284 50 | 0 284 60 | 0 284 70 |
800 | 0 284 21 | 0 284 31 | 0 284 41 | 0 284 51 | 0 284 61 | 0 284 71 |
1000 | 0 284 22 | 0 284 32 | 0 284 42 | 0 284 52 | 0 284 62 | 0 284 72 |
1250 | 0 284 23 | 0 284 33 | 0 284 43 | 0 284 53 | 0 284 63 | 0 284 73 |
1600 | 0 284 24 | 0 284 34 | 0 284 44 | 0 284 54 | 0 284 64 | 0 284 74 |
2000 | 0 284 25 | 0 284 35 | 0 284 45 | 0 284 55 | 0 284 65 | 0 284 75 |
2500 | 0 284 26 | 0 284 36 | 0 284 46 | 0 284 56 | 0 284 66 | 0 284 76 |
2.3 DMX³-I 2500 Fixed/Withdrawable Version with UP MP2.10/MP4.10
In (A) | Fixed Version | Withdrawable Version | ||
3P | 4P | 3P | 4P | |
1250 | 0 282 40 | 0 282 50 | 0 282 80 | 0 282 90 |
1600 | 0 282 41 | 0 282 51 | 0 282 81 | 0 282 91 |
2000 | 0 282 42 | 0 282 52 | 0 282 82 | 0 282 92 |
2500 | 0 282 43 | 0 282 53 | 0 282 83 | 0 282 93 |
3. Technical Characteristics
3.1 Electrical Characteristics
Circuit Breaker DMX³ 2500
50 kA | 65 kA | 100 kA | ||||||||
Rated current In | 2500 A | |||||||||
Number of poles | 3P - 4P | |||||||||
Insulation voltage Ui | 1000 V | |||||||||
Impulse withstand voltage Uimp | 12 kV | |||||||||
Rated voltage Ue (50/60Hz) | 690 V | |||||||||
Max breaking capacity Icu (kA) | 50 | 65 | 100 | |||||||
Rated service breaking capacity Ics (% Icu) | 100% | |||||||||
Rated short-circuit making capacity Icm (kA) | 220/240 V~ | 105 | 143 | 220 | 105 | 143 | 220 | 105 | 143 | 220 |
380/415 V | 105 | 143 | 220 | 105 | 143 | 220 | 105 | 143 | 220 | |
440/460 V~ | 105 | 143 | 220 | 105 | 143 | 220 | 105 | 143 | 220 | |
480/500 V~ | 105 | 143 | 220 | 105 | 143 | 220 | 105 | 143 | 220 | |
480/550 V~ | 105 | 132 | 165 | 105 | 132 | 165 | 105 | 132 | 165 | |
600 V~ | 105 | 132 | 165 | 105 | 132 | 165 | 105 | 132 | 165 | |
690 V~ | 105 | 121 | 143 | 105 | 121 | 143 | 105 | 121 | 143 | |
Rated short-time withstand capacity Icw (kA) for 1s | 220/240 V~ | 50 | 65 | 85 | 50 | 65 | 85 | 50 | 65 | 85 |
380/415 V | 50 | 65 | 85 | 50 | 65 | 85 | 50 | 65 | 85 | |
440/460 V~ | 50 | 65 | 85 | 50 | 65 | 85 | 50 | 65 | 85 | |
480/500 V~ | 50 | 65 | 85 | 50 | 65 | 85 | 50 | 65 | 85 | |
480/550 V~ | 50 | 65 | 75 | 50 | 65 | 75 | 50 | 65 | 75 | |
600 V~ | 50 | 60 | 75 | 50 | 60 | 75 | 50 | 60 | 75 | |
690 V~ | 50 | 55 | 65 | 50 | 55 | 65 | 50 | 55 | 65 | |
Rated short-time withstand capacity Icw (kA) for 3s | 220/240 V~ | 45 | 45 | 65 | 45 | 45 | 65 | 45 | 45 | 65 |
380/415 V~ | 45 | 45 | 65 | 45 | 45 | 65 | 45 | 45 | 65 | |
440/460 V~ | 45 | 45 | 65 | 45 | 45 | 65 | 45 | 45 | 65 | |
480/500 V~ | 45 | 45 | 65 | 45 | 45 | 65 | 45 | 45 | 65 | |
480/550 V~ | 45 | 45 | 65 | 45 | 45 | 65 | 45 | 45 | 65 | |
600 V~ | 45 | 40 | 65 | 45 | 40 | 65 | 45 | 40 | 65 | |
690 V~ | 45 | 45 | 65 | 45 | 45 | 65 | 45 | 45 | 65 |
Circuit Breaker DMX³-I 2500
Rated current In | 1250 A / 1600 A / 2000 A / 2500 A |
Number of poles | 3P - 4P |
Insulation voltage Ui | 1000 V |
Impulse withstand voltage Uimp | 12 kV |
Rated voltage Ue (50/60Hz) | 690 V |
Rated short-circuit breaking capacity Icm (kA) | 220/240 V~: 143; 380/415 V~: 143; 440/460 V~: 143; 480/500 V~: 143; 600 V~: 132; 690 V~: 121 |
Rated short-time withstand capacity Icw (kA) for 1s | 220/240 V~: 65; 380/415 V~: 65; 440/460 V~: 65; 480/500 V~: 65; 600 V~: 60; 690 V~: 55 |
Rated short-time withstand capacity Icw (kA) for 3s | 220/240 V~: 45; 380/415 V~: 45; 440/460 V~: 45; 480/550 V~: 45; 600 V~: 45; 690 V~: 45 |
3.2 Limit tripping current for phases
Thermal | Magnetic | |||||||
In (A) | 0.2 x In | 1 x In | 1.5 x Ir min | 10 x Ir max | ||||
630 | 126 | 630 | 378 | 6300 | ||||
800 | 160 | 800 | 480 | 8000 | ||||
1000 | 200 | 1000 | 600 | 10000 | ||||
1250 | 250 | 1250 | 750 | 12500 | ||||
1600 | 320 | 1600 | 960 | 16000 | ||||
2000 | 400 | 2000 | 1200 | 20000 | ||||
2500 | 500 | 2500 | 1500 | 25000 |
3.3 Mechanical Characteristics
Endurances:
- Mechanical: 20,000 cycles (with maintenance)
- Electrical: 10,000 cycles (without maintenance)
Auxiliary Contacts: Identical to the circuit breaker (10,000 cycles without maintenance).
Motorized Operation: 10,000 cycles.
Coils/Trip Units: 10,000 cycles.
3.4 Power Loss per Pole at In/Ie
The table below shows power loss values for DMX³ 2500 circuit breakers and DMX³-I 2500 switches.
Rated current In (A) | DMX³ 2500 | DMX³-I 2500 | |||
Fixed | Withdrawable | Fixed | Withdrawable | ||
50 kA | 65 kA | 100 kA | |||
630 | 5.7 | 9.9 | 3.2 | 6.4 | 41.4 |
800 | 9.2 | 16.0 | 5.2 | 10.2 | 41.5 |
1000 | 14.4 | 25.0 | 8.1 | 16.0 | 415 |
1250 | 22.4 | 39.1 | 12.7 | 25.0 | 423 |
1600 | 36.7 | 64.0 | 20.8 | 41.0 | 354 |
2000 | 57.4 | 100.0 | 32.5 | 64.0 | 433 |
2500 | 89.7 | 156.3 | 50.8 | 100.0 | 354 |
3.5 Electronic Protection Unit
All DMX³ 2500 circuit breakers can be equipped with an MP2.10 or MP4.10 electronic protection unit. These units offer advanced protection functions, adjustable settings, and diagnostic capabilities.
- MP2.10: LED display for electrical values and settings.
- MP4.10: LCD display for electrical values, settings, and logs.
Key protection functions include:
- Ir (Long Time Delay): Protection against overloads from 0.2 to 1 x In.
- tr (Long Time Delay Time): Adjustable delay time for overloads.
- Isd (Short Time Delay): Adjustable current for short-circuit protection from 1.5 to 10 x Ir.
- tsd (Short Time Delay Time): Adjustable delay time for short-circuit protection.
- li (Instantaneous Current): Instantaneous overcurrent protection from 2 to 15 x In.
- Ig (Earth Leakage Current): Earth leakage protection from 0.2 to 1 x In.
- tg (Earth Leakage Delay Time): Adjustable delay time for earth leakage protection.
- N (Neutral Protection): OFF, 50%, 100%, 200% settings.
The protection units can be fully configured to adapt to installation requirements, allowing for precise adjustment of tripping curves and parameters.
4. Installation Rules
4.1 Temperature Derating
The rated current and its adjustment must be considered based on ambient temperature and installation conditions. The following tables indicate the maximum long-time (LT) protection setting as a function of ambient temperature for DMX³ 2500 fixed and withdrawable versions.
4.2 Altitude Derating
Derating factors for current and voltage are provided for DMX³ and DMX³-I at different altitudes.
Altitude (m) | 2000 | 3000 | 4000 | 5000 |
Rated current (at 40°C/50°C) In (A) | 0.98 x In | 0.94 x In | 0.9 x In | |
Rated voltage Ue (V) | 690 | 600 | 500 | 440 |
Insulation voltage Ui (V) | 1000 | 900 | 750 | 600 |
Dielectric withstand (V) | 3500 | 3200 | 2500 | 2000 |
5. Dimensions and Weights
5.1 Dimensions
Detailed dimensions are provided for DMX³ 2500 and DMX³-I 2500 in fixed and withdrawable versions, for 3-pole and 4-pole configurations.
5.2 Weights
Weights for DMX³ 2500 and DMX³-I 2500 are listed for fixed and withdrawable versions.
6. Electrical Connections
This section provides guidance on minimum copper bar cross-sections required for electrical connections, for various DMX³ 2500 and DMX³-I versions and current ratings. It includes recommendations for vertical and horizontal bar arrangements.
7. Accessories and Equipment
7.1 Connection Terminals and Spreading Terminals
Various types of connection terminals and spreading terminals are available for fixed and withdrawable versions, including those for different breaking capacities (up to 65 kA and 100 kA) and pole configurations.
7.2 Control Auxiliaries
A range of control auxiliaries are available, including:
- Current Release Coils: For tripping the circuit breaker when energized.
- Delayed Trip Units: Used with voltage release units.
- Motorized Operations: Connect to release units and a closing coil for remote operation.
- Shunt Release Coils: For tripping the circuit breaker when the coil is de-energized.
- Under-voltage Release Coils: For tripping the circuit breaker when the coil is de-energized.
7.3 Signaling Auxiliaries
These include contacts for signaling the position of the circuit breaker (e.g., tripped, tested, withdrawn) and additional signaling contacts.
7.4 Interlocks
Key interlocks and supports are available to prevent unauthorized operation or to ensure correct installation.
7.5 Mechanical Counter
A mechanical counter tracks the number of operating cycles.
7.6 Calibration Key
A key to prevent the insertion of an incompatible withdrawable base.
7.7 Lifting Handles
A set of two lifting handles.
7.8 Fixing Devices
Specific instruction sheets are provided for integrating DMX³ 2500/DMX³-I 2500 into XL³ 4000 or XL³ HP 6300 cabinets.
7.9 Equipment for Converting Fixed to Withdrawable
Bases and conversion kits are available to transform fixed versions into withdrawable ones.
7.10 Interlocking Mechanism
Mechanical interlocking systems using cables are available for securing multiple devices.
7.11 Interlocking Cables
Interlocking cables of various lengths are offered.
7.12 Separation Partitions
Separation partitions are available for different versions and pole configurations.
8. Marking
Products are supplied with labeling that complies with relevant standards, including laser-etched and self-adhesive labels detailing manufacturer information, product specifications, and compliance marks.
9. Tripping Curves
9.1 Tripping Curve for DMX³ 2500 with MPx.10 Protection Unit: L-T Protection Detail
This section displays the tripping curves for the DMX³ 2500, illustrating the relationship between current (I/Ir) and tripping time (t) for long-time (L) and thermal (T) protection.
9.2 Tripping Curve for DMX³ 2500 with MPx.10 Protection Unit: Short-Circuit Protection Detail
This section shows the tripping curves for short-time (s) and instantaneous (i) protection against short circuits.
9.3 Tripping Curve for DMX³ 2500 with MPx.10 Protection Unit: Instantaneous Trip Protection Detail
This section details the tripping curves for instantaneous trip protection, including fixed instantaneous trip (Isf).
9.4 Earth Leakage Fault Curve for DMX³ 2500 with MPx.10 Protection Units
This graph illustrates the earth leakage fault protection curves, showing the relationship between current (I/Ig) and tripping time (t) for various settings.
9.5 Specific Constant Energy Curve (at 415 V)
This curve shows the constant energy characteristic for different breaking capacities (50 kA, 65 kA, 100 kA).
10. Standards and Regulations
Legrand DMX³ products comply with IEC/EN 60947-2 and 60947-3 standards, as well as various certifications like CB scheme, Lloyd's Shipping Register, RINA, and Bureau Veritas Marine. The products also adhere to RoHS, REACH, and WEEE directives, ensuring environmental compliance.
11. Other Information
- XLPro Calcul: Software for creating calculation notes for installers and design offices.
- XLPro³ Tool Selectivity and Coordination: Software for defining selectivity and coordination values for electrical associations.
- XLPro Switchboards: Software for designing distribution panels.
- Workshop Manuals: Provide assembly tips and information on equipment.
- Notices: Detailed assembly procedures.
- PEP (Environmental Product Declaration): Available online.
For further technical information, contact Legrand technical support.