Legrand DMX³ 4000 & DMX³-I 4000 Circuit Breakers and Trip Free Switches
Technical Data Sheet
Manufacturer: Legrand
Document Reference: F03885EN-01
Publication Dates: Created: 12/10/2022, Updated: 08/09/2025
1. Use
The DMX³ air circuit breakers are designed to meet protection requirements for low voltage electrical installations (IEC/EN 60364-1) up to 6300 A. They offer electric and mechanical robustness, high breaking capacity, and extensive accessorizing options. The DMX³-I series provides trip-free switches with enhanced insulation, robustness, closing, and withstand capabilities, contributing to plant energy efficiency and "green aspects".
2. Range
2.1 DMX³ 4000 Fixed Version (PU MP2.10/MP4.10)
In (A) | 50 kA | 65 kA | 100 kA | |||
---|---|---|---|---|---|---|
3P | 4P | 3P | 4P | 3P | 4P | |
3200 | 0 283 67 | 0 283 77 | 0 283 87 | 0 283 97 | 0 284 07 | 0 284 17 |
4000 | 0 283 68 | 0 283 78 | 0 283 88 | 0 283 98 | 0 284 08 | 0 284 18 |
2.2 DMX³ 4000 Draw-out Version (PU MP2.10/MP4.10)
In (A) | 50 kA | 65 kA | 100 kA | |||
---|---|---|---|---|---|---|
3P | 4P | 3P | 4P | 3P | 4P | |
3200 | 0 284 27 | 0 284 37 | 0 284 47 | 0 284 57 | 0 284 67 | 0 284 77 |
4000 | 0 284 28 | 0 284 38 | 0 284 48 | 0 284 58 | 0 284 68 | 0 284 78 |
2.3 DMX³-I 4000 Trip-Free Switches (Fixed/Draw-out Version)
In (A) | Fixed version | Draw-out version | ||
---|---|---|---|---|
3P | 4P | 3P | 4P | |
3200 | 0 282 44 | 0 282 54 | 0 282 84 | 0 282 94 |
4000 | 0 282 45 | 0 282 55 | 0 282 85 | 0 282 95 |
2.4 Composition
Main parts constituting the circuit breaker
Fixed version:
- 1. Protection Unit
- 2. Auxiliary contacts
- 3. Reset button
- 4. OFF button
- 5. ON button
- 6. ON-OFF Indication
- 7. Spring status indication
- 8. Charging handle
- 9. Dejon cell
- 10. Mini USB cover
- 11. Battery cover
Diagram showing a fixed version circuit breaker with numbered components.
Draw-out version:
- 12. Draw-out mechanism
- 13. Draw-out bar insertion
- 14. Racking shutter
- 15. Support to place the breaker in draw-out cassette
- 16. Draw-out main shaft
- 17. Insertion guide
Diagram showing a draw-out version circuit breaker with numbered components.
Draw-out base components:
- 1. Auxiliary terminal block
- 2. Safety shutter
- 3. Earth connection
- 4. Earth terminal
- 5. Removable cassette
Diagram of a draw-out base unit showing terminal blocks, shutters, and connection points.
DMX³ circuit breakers are equipped with auxiliary contacts (expandable up to 10) and a doorframe. The fixed version includes rear terminals for horizontal connections with bars. The draw-out version features flat rear terminals and comes with a base equipped with an extraction crank and isolating components. Door sealing is also included.
3. Technical Characteristics
3.1 Electrical Characteristics
Circuit breaker
Parameter | DMX³ 4000 (50 kA) | DMX³ 4000 (65 kA) | DMX³ 4000 (100 kA) |
---|---|---|---|
Frame current | 4000 A | ||
Rated current In | 3200 A / 4000 A | ||
Poles | 3P - 4P | ||
Rated insulation voltage Ui | 1000 V | ||
Rated impulse withstand voltage Uimp | 12 kV | ||
Rated operational voltage (50/60Hz) Ue | 690 V | ||
Rated ultimate short-circuit breaking capacity Icu (kA) | 220/240 V~: 50 | 380/415 V~: 65 | 440/460 V~: 100 |
480/500 V~: 50 | 600 V~: 65 | 690 V~: 75 | |
220/240 V~: 50 | 380/415 V~: 65 | 440/460 V~: 100 | |
480/500 V~: 50 | 600 V~: 65 | 690 V~: 75 | |
220/240 V~: 50 | 380/415 V~: 65 | 440/460 V~: 100 | |
480/500 V~: 50 | 600 V~: 65 | 690 V~: 75 | |
Rated service short-circuit breaking capacity Ics (% Icu) | 100% |
Trip-free switches
Parameter | DMX³-I 4000 (3P) | DMX³-I 4000 (4P) |
---|---|---|
Rated current In (A) | 3200 A / 4000 A | 3200 A / 4000 A |
Poles | 3P | 4P |
Rated insulation voltage Ui | 1000 V | |
Rated impulse withstand voltage Uimp | 12 kV | |
Rated operational voltage (50/60Hz) Ue | 690 V | |
Category of use | AC23A | |
Rated short circuit making capacity Icm (kA) | 220/240 V~: 187 | 380/415 V~: 187 |
440/460 V~: 187 | 480/500 V~: 187 | |
600 V~: 165 | 690 V~: 143 |
General Electrical Characteristics (Circuit Breaker & Trip-Free Switches)
Parameter | Value |
---|---|
Suitable for insulation | Yes |
Neutral protection (% Ith) | 0 - 50 - 100 |
Operation temperature | -25 °C to +70 °C |
Storage temperature | -25 °C to +85 °C |
Rated Short Time Withstand Current (Icw)
Rated short time withstand current Icw (kA) for t = 1s | DMX³ 4000 | |||||
---|---|---|---|---|---|---|
220/240 V~ | 380/415 V~ | 440/460 V~ | 480/500 V~ | 600 V~ | 690 V~ | |
50 kA | 105 | 105 | 105 | 105 | 105 | 105 |
65 kA | 143 | 143 | 143 | 143 | 132 | 121 |
100 kA | 220 | 220 | 220 | 220 | 165 | 143 |
Rated short time withstand current Icw (kA) for t = 3s | DMX³ 4000 | |||||
---|---|---|---|---|---|---|
220/240 V~ | 380/415 V~ | 440/460 V~ | 480/500 V~ | 600 V~ | 690 V~ | |
50 kA | 50 | 50 | 50 | 50 | 50 | 50 |
65 kA | 65 | 65 | 65 | 65 | 60 | 55 |
100 kA | 85 | 85 | 85 | 85 | 75 | 65 |
Parameter | DMX³-I 4000 |
---|---|
Rated short time withstand current Icw (kA) for t = 1s | 85 |
Rated short time withstand current Icw (kA) for t = 3s | 65 |
Individual Pole Short-Circuit Current (I∆)
Parameter | Value |
---|---|
220/240 V~ | 1.2 times the maximum setting of the defined time delay release tripping current (Isd) (1) |
380/415 V~ | |
440/460 V~ | |
480/500 V~ | |
600 V~ | |
690 V~ |
(1) For more details, please consult Legrand.
Phase Limit Trip Current
In (A) | Thermal (Ir) | Magnetic (Isd) | ||
---|---|---|---|---|
0.2 x In | 1 x In | 1.5 x Ir min | 10 x Ir max | |
3200 | 640 | 3200 | 1920 | 32000 |
4000 | 800 | 4000 | 2400 | 40000 |
Note: For neutral adjustment, consider the values ratios 0%, 50% and 100% on set currents.
3.3 Mechanical Characteristics
Endurances
Parameter | DMX³ 4000 / DMX³-I 4000 |
---|---|
Mechanical Endurance (cycles) | 10000 (w/o maintenance); 20000 (with maintenance) |
Electrical Endurance (cycles) | 10000 (w/o maintenance) |
Category of use | B |
Notes:
- With auxiliary contacts: same as breaker (10000 cycles w/o maintenance).
- With motor operator: 10000 cycles.
- With releases: 10000 cycles.
Electrodynamic Forces
The table below indicates suggested distances to maintain between the breaker and the first fixing point of the conductor and bars to reduce the effects of electrodynamic stresses during a short circuit. The anchorage system should use isolators suitable for the conductor type and operating voltage.
Icc (kA) max | 50 | 65 | 100 |
---|---|---|---|
"X" max. (mm) | 300 | 250 | 150 |
Diagram illustrating the "X" max distance for conductor/bar connections to mitigate electrodynamic stresses.
3.4 Power Losses per Pole at In/Ie
Rated current In (A) | Fixed | Draw-out | ||
---|---|---|---|---|
Circuit breaker | Trip-free switches | Circuit breaker | Trip-free switches | |
3200 | 83.3 | 163.8 | 130.1 | 256.0 |
4000 | 130.1 | 256.0 | 163.8 | 256.0 |
Note: Power loss values are measured as per IEC 60947-2 (Annex G) for circuit-breakers and IEC 60947-1 for switches. Values are for a single phase.
3.5 Electronic Protection Unit
DMX³ 4000 circuit breakers can be equipped with MP2.10 or MP4.10 electronic protection units. Key features include:
- Display: LED matrix screen (MP2.10) or LCD screen (MP4.10) for electrical values, settings, and logs.
- Adjustment: Rotating encoder for settings.
- Protection Settings: Configurable Ir, tr, Isd, tsd, Ii, Ig, tg. Protections can be enabled/disabled.
- Measurement: Displays instantaneous, maximum, and average electrical values and fault signaling (for measure versions).
- Backup Power: Equipped with batteries for mains fault or when the breaker is open/disconnected (MP4.10).
- Connectivity: Mini USB Type-B socket for maintenance or PC connection.
Protection Unit Types
Features | Display | With Measure | Power Consumption | Cat.Nos |
---|---|---|---|---|
MP2.10 | LED matrix | NO | 55 mA | 0 283 04 |
LED matrix | YES | 69 mA | 0 283 05* | |
MP4.10 | LCD screen | NO | 62.5 mA | 0 283 06 |
LCD screen | YES | 80 mA | 0 283 07* |
* Requires CX³ EMS power supply module (Cat.No 4 149 45) for metering function.
Protective Functions
- Ir: Long time delay protection against overloads (0.2 to 1 x In, 1A steps). Protection ON/OFF.
- tr: Long delay protection operation time (40 ms to 30 s, 40 ms steps). Thermal memory ON/OFF.
- Isd: Short time delay protection against short-circuits (1.5 to 10 x Ir, 1A steps). Protection ON/OFF.
- tsd: Short time delay protection operation time (40 ms to 1 s, 40 ms steps; independent or inverse).
- Ii: Instantaneous protection against very high short-circuits (2 to 15 x In or Icw, 1A steps). Protection ON/OFF.
- Ig: Earth fault current (0.2 to 1 x In, 1A steps). Protection ON/OFF.
- tg: Time delay on earth fault tripping (80 ms to 1 s, 40 ms steps; independent or inverse).
- N: Neutral protection (OFF, 50%, 100%, 200%).
The protection units are fully configurable to adapt settings to specific installation requirements. Integrated measurement units can display voltage, power, frequency, and energy. Alarms can be programmed for various parameters.
4. Installation Rules
Temperature Derating
Rated current and its adjustment must consider ambient temperature variations and installation conditions. The tables below show maximum long-time (LT) protection settings based on ambient temperature.
Temperature deratings for DMX³/DMX³-I 4000 Fixed Version (Horizontal Terminals)
Temperature | up to 40 °C | 50 °C | 60 °C | 65 °C | 70 °C | |||||
---|---|---|---|---|---|---|---|---|---|---|
Imax (A) | Ir/In | Imax (A) | Ir/In | Imax (A) | Ir/In | Imax (A) | Ir/In | Imax (A) | Ir/In | |
DMX³ 4000 | 3200 | 1 | 3200 | 1 | 3200 | 1 | 3136 | 0.98 | 3008 | 0.94 |
DMX³-I 4000 | 4000 | 1 | 3920 | 0.98 | 3680 | 0.92 | 3440 | 0.86 | 3120 | 0.78 |
Temperature deratings for DMX³/DMX³-I 4000 Draw-out Version (Horizontal Terminals)
Temperature | up to 40 °C | 50 °C | 60 °C | 65 °C | 70 °C | |||||
---|---|---|---|---|---|---|---|---|---|---|
Imax (A) | Ir/In | Imax (A) | Ir/In | Imax (A) | Ir/In | Imax (A) | Ir/In | Imax (A) | Ir/In | |
DMX³ 4000 | 3200 | 1 | 3200 | 1 | 3200 | 1 | 3072 | 0.96 | 2880 | 0.90 |
DMX³-I 4000 | 4000 | 1 | 3760 | 0.94 | 3440 | 0.86 | 3200 | 0.80 | 2960 | 0.74 |
Climatic Conditions & EMC
Climatic Conditions: According to IEC/EN 60947-1 Annex Q, Cat. F (temperature, humidity, vibration, shock, salt mist). Pollution degree: 3 (IEC/EN 60947-2). Electromagnetic Disturbances (EMC): According to IEC/EN 60947-2 - Annex F.
Altitude Derating
Altitude (m) | <2000 | 3000 | 4000 | 5000 |
---|---|---|---|---|
Rated current (at 40°C/50°C) In (A) | In | 0.98 x In | 0.94 x In | 0.9 x In |
Rated voltage Ue (V) | 690 | 600 | 500 | 440 |
Rated insulation voltage Ui (V) | 1000 | 900 | 750 | 600 |
Dielectric withstand (V) | 3500 | 3200 | 2500 | 2000 |
5. Dimensions and Weights
5.1 Dimensions
Dimension | Version | DMX³ 4000 / DMX³-I 4000 (mm) |
---|---|---|
Height | 3P-fixed | 419 |
3P-Draw-out | 473 | |
4P-Fixed | 419 | |
4P-Draw-out | 473 | |
Depth | 3P-fixed | 354 |
3P-Draw-out | 433 | |
4P-Fixed | 354 | |
4P-Draw-out | 433 | |
Width | 3P-fixed | 408 |
3P-Draw-out | 425 | |
4P-Fixed | 538 | |
4P-Draw-out | 555 |
5.2 Weights
Version | DMX³ 4000 (kg) | DMX³-I 4000 (kg) |
---|---|---|
3P-fixed | 55 | 54 |
3P-Draw-out(1) | 106 | 105 |
4P-Fixed | 68 | 67 |
4P-Draw-out(1) | 134 | 133 |
(1) Weights for draw-out releases are to be intended with base.
5.3 Fixed Version Diagrams
Diagrams showing frontal, rear, and lateral views of the DMX³ 4000 fixed version circuit breaker, indicating dimensions and fixing points (labeled 'A').
5.4 Draw-out Version Diagrams
Diagrams showing frontal, lateral, and rear views of the DMX³ 4000 draw-out version circuit breaker, including dimensions for flat, horizontal, and vertical terminal configurations, and fixing points (labeled 'A').
6. Electrical Connections
These guidelines are for general selection. Actual installation must be verified based on specific switchgear shapes and conditions. Phase insulators or insulated bars are recommended if inter-pole air distance is less than 20 mm.
Minimum Cross Section of Copper Busbars per Pole (DMX³ and DMX³-I Fixed & Draw-out Versions)
Rated Current (A) | Vertical Bars (mm) | Horizontal Bars (mm) |
---|---|---|
630 | 1 bar 40 x 10 or 2 bars 40 x 5 | 2 bars 40 x 5 |
800 | 1 bar 50 x 10 or 2 bars 50 x 5 | 2 bars 50 x 5 |
1000 | 1 bar 50 x 10 or 2 bars 50 x 5 | 2 bars 60 x 5 |
1250 | 2 bars 60 x 5 | 2 bars 80 x 5 |
1600 | 2 bars 80 x 5 | 2 bars 50 x 10 |
2000 | 2 bars 50 x 10 | 2 bars 60 x 10 |
2500 | 3 bars 50 x 10 | 3 bars 60 x 10 |
3200 | 3 bars 100 x 10 | 4 bars 80 x 10 |
4000 | 4 bars 100 x 10 | 5 bars 100 x 10 |
Minimum Cross Section of Aluminium Busbars per Pole (DMX³ and DMX³-I Fixed & Draw-out Versions)
Rated Current (A) | Vertical Bars (mm) | Horizontal Bars (mm) |
---|---|---|
630 | 2 bars 40 x 8 | 2 bars 40 x 8 |
800 | 2 bars 50 x 8 | 2 bars 50 x 8 |
1000 | 2 bars 50 x 8 | 2 bars 50 x 10 |
1250 | 2 bars 50 x 10 | 2 bars 60 x 10 |
1600 | 2 bars 60 x 10 | 4 bars 50 x 8 |
2000 | 4 bars 50 x 8 | 4 bars 50 x 10 |
2500 | 4 bars 60 x 10 | 4 bars 80 x 10 |
3200 | 4 bars 150 x 10 | 5 bars 150 x 10 |
4000 | 5 bars 150 x 10 | 6 bars 150 x 10 |
7. Equipments and Accessories
7.1 Terminals
Rear terminals for fixed version (Flat connection pitch 130 mm)
Must be fixed onto horizontal rear terminals of the circuit breaker. Available for 3P (Cat.No 0 288 92) and 4P (Cat.No 0 288 93).
Diagram showing mounting examples for rear terminals for fixed version (flat connection).
Rear terminals for fixed version (Vertical connection pitch 130 mm)
Used to convert flat connection to vertical. Must be fixed onto Cat.Nos 0 288 92/93 according to pole count. Available for 3P (Cat.No 0 288 94) and 4P (Cat.No 0 288 95).
Diagram showing mounting examples for rear terminals for fixed version (vertical connection).
Rear terminals for draw-out version (Flat/vertical connection)
Must be fixed directly onto plate rear terminals of the circuit breaker. Available for 3P (Cat.No 0 288 94) and 4P (Cat.No 0 288 95).
Diagram showing mounting examples for rear terminals for draw-out version (flat/vertical connection).
7.2 Control Auxiliaries
Shunt Trip
Energizing trips the circuit breaker.
Voltage (V) | Cat.No |
---|---|
24 ~/= | 0 288 48 |
48 ~/= | 0 288 49 |
110 to 130 ~/= | 0 288 50 |
220 to 250 ~/= | 0 288 51 |
415 to 480 ~/= | 0 288 52 |
Specifications: Rated operating voltage (Uc) ranges from 24-480V, voltage range (% Uc) 70-110, pick-up consumption 500/500 W/VA, pick-up time 180 ms, hold consumption 5/5 W/VA, min opening time 30 ms, insulation voltage 2.5 kV.
Undervoltage Releases
Trips the device when the coil is de-energised.
Voltage (V) | Cat.No |
---|---|
24 ~/= | 0 288 55 |
48 ~/= | 0 288 56 |
110 to 130 ~/= | 0 288 57 |
220 to 250 ~/= | 0 288 58 |
415 to 440 ~/= | 0 288 59 |
Specifications: Rated operating voltage (Uc) ranges from 24-480V, voltage range (% Uc) 85-110, pick-up consumption 500/500 W/VA, pick-up time 180 ms, hold consumption 5/5 W/VA, min opening time 60 ms, insulation voltage 2.5 kV.
Modules for Delayed Tripping
Used with undervoltage releases.
Voltage (V) | Cat.No |
---|---|
110 ~/= | 0 288 62 |
230 ~/= | 0 288 63 |
Specifications: Rated operating voltage (Uc) 110 or 230V, voltage range (% Uc) 85-110, pick-up consumption 16.5 (@110V)/34.5 (@230V) W/VA, time delay 1s (up to 3 modules), hold consumption 5 (@110V)/10 (@230V) W/VA, opening threshold 0.3-0.75xUn, closing threshold 0.85xUn, operating temperature -10 to +55 °C.
Closing Coils
Enable remote closing of the circuit breaker when the closing spring is charged.
Voltage (V) | Cat.No |
---|---|
24 ~/= | 0 288 41 |
48 ~/= | 0 288 42 |
110 to 130 ~/= | 0 288 43 |
220 to 250 ~/= | 0 288 44 |
415 to 480 ~/= | 0 288 45 |
Specifications: Rated operating voltage (Uc) ranges from 24-480V, voltage range (% Uc) 85-110, pick-up consumption 500/500 W/VA, pick-up time 180 ms, hold consumption 5/5 W/VA, max closing time 30 ms, insulation voltage 2.5 kV.
Motor Operators
Connect to a release coil (UVR or trip on energising) and a closing coil.
Voltage (V) | Cat.No |
---|---|
24 ~/= | 0 288 34 |
48 ~/= | 0 288 35 |
110 to 130 ~/= | 0 288 36 |
220 to 250 ~/= | 0 288 37 |
415 to 440 ~/= | 0 288 38 |
480 ~/= | 0 288 40 |
Specifications: Rated operating voltage (Uc) ranges from 24-480V, voltage range (% Uc) 85-110, max power consumption 180/180 W/VA (up to 65kA), 240/240 W/VA (100kA), max peak current 2-3xIn, charging time 5 (up to 65kA) / 7 (100kA) s, operating frequency 2 (up to 65kA) / 1 (100kA) n°/min.
7.3 Signalling Auxiliaries
Signalling contact for draw-out version (inserted/test/drawn-out)
Provides 3 changeover contacts per position.
Rated operating voltage (Uc) | Cat.No 0 288 13 |
---|---|
= | 250 V - 0.3 A |
= | 125 V - 0.6 A |
~ | 250 V - 16 A |
~ | 125 V - 16 A |
Contact "ready to close" with charged springs
Rated operating voltage (Uc) | Cat.No 0 288 14 |
---|---|
= | 250 V - 0.3 A |
= | 125 V - 0.6 A |
~ | 250 V - 16 A |
~ | 125 V - 16 A |
Additional Signalling Contact
Rated operating voltage (Uc) | Cat.No 0 288 15 |
---|---|
= | 250 V - 0.3 A |
= | 125 V - 0.6 A |
~ | 250 V - 16 A |
~ | 125 V - 16 A |
Signalling Contact for Auxiliaries (ST, CC and UVR)
Rated operating voltage (Uc) | Cat.No 0 288 16 |
---|---|
= | 250 V - 0.3 A |
= | 125 V - 0.6 A |
~ | 250 V - 16 A |
~ | 125 V - 16 A |
7.4 Locking
Universal Key Locks
Used with key locking support Cat.No 0 288 28 or 0 281 94.
- Key barrel and flat key with random mapping: Cat.No 4 238 80
- Key barrel and flat key with fixed mapping: Cat.No 4 238 81
- Key barrel and star key with random mapping: Cat.No 4 238 83
Keylocks Supports
- Support in "open" position (for universal keylocks): Cat.No 0 288 28
- Support in "draw-out" position (for universal keylocks): Cat.No 0 281 94
Door Locking
Prevents door opening when the circuit breaker is closed. Available for left-hand and right-hand side mounting (Cat.No 0 288 20).
Padlocks
- Padlocking system for ACB (padlock not supplied): Cat.No 0 288 21
- Padlock for buttons: Cat.No 0 288 24
- Padlocking system for shutters (padlock not supplied): Cat.No 0 288 26
7.5 Mechanical Operations Counter
Counts total operation cycles of the device (Cat.No 0 288 23).
7.6 Rating Mis-insertion Device
Prevents insertion of a draw-out circuit breaker into an incompatible base (Cat.No 0 288 25).
7.7 Lifting Plate
Available (Cat.No 0 288 79).
7.8 Fixing Devices
Specific instruction sheets are provided for integrating DMX³ / DMX³-I 4000 into XL³ enclosure ranges (fixing plates, metal faceplates, cable sleeves, etc.).
7.9 Equipment for Conversion of Fixed to Draw-out Device
Bases for Draw-out Device
- For DMX³/DMX³-I 4000 3P: Cat.No 0 289 04
- For DMX³/DMX³-I 4000 4P: Cat.No 0 289 05
Transformation Kit for Draw-out Version
- For DMX³/DMX³-I 4000 3P: Cat.No 0 289 11
- For DMX³/DMX³-I 4000 4P: Cat.No 0 289 12
7.10 Equipment for Interlocking
Mechanical interlock uses cables to interlock 2 or 3 devices (different types possible) in vertical or horizontal configuration. The interlock unit mounts on the right-hand side. Interlock cables must be ordered separately.
Interlock for DMX³ 4000: Cat.No 0 288 65.
7.11 Interlock Cables
Available in various lengths:
- Length: 1000 mm - Cat.No 0 289 17
- Length: 1500 mm - Cat.No 0 289 18
- Length: 2600 mm - Cat.No 0 289 20
- Length: 3000 mm - Cat.No 0 289 21
- Length: 3600 mm - Cat.No 0 289 22
- Length: 4000 mm - Cat.No 0 289 23
- Length: 4600 mm - Cat.No 0 289 24
- Length: 5600 mm - Cat.No 0 289 25
Diagram illustrating interlock cable connection choices and showing how to calculate cable length based on variables H and V.
7.12 Insulating Shields
- Fixed version 3P: Cat.No 0 288 98
- Fixed version 4P: Cat.No 0 288 99
- Draw-out version 3P: Cat.No 0 288 18
- Draw-out version 4P: Cat.No 0 288 19
8. Marking
Products are labeled in full conformity with standards and directives using laser or sticker labels. Labels include manufacturer, product denomination/type/code, standard conformity, declared characteristics, and Icu identification.
Example of a product laser label on the front, detailing manufacturer, product code, current ratings (In, Icw, Ics), voltages (Uimp, Ui), and standard compliance.
Example of a product laser label on the side, detailing manufacturer, product type, standard conformity, and directive requirements.
Example of a mark sticker label on the side, showing product code and country deviation.
Example of a packaging sticker label, detailing manufacturer, product type, and standard conformity.
9. Curves
9.1 Tripping Curve for DMX³ 4000 MPx.10 Protection Units: L-T Protection Detail
This graph illustrates the Long Time (L) and Thermal (T) protection curve, showing the relationship between tripping time (seconds) and current (I) relative to the rated current (Ir). It defines the time delay for overload conditions.
Value | Description |
---|---|
I | Current |
Ir | Long time setting current |
tr | Long time delay |
9.2 Tripping Curve for DMX³ 4000 MPx.10 Protection Units: Short Time Trip Protection Detail
This graph details the Short Time (ST) trip protection, showing tripping time versus current for both independent time delay (t=k) and inverse time delay (I²t=k) characteristics. It covers settings for Isd and tsd.
Value | Description |
---|---|
I | Current |
Isd | Short time setting current |
tsd | Short time delay |
9.3 Tripping Curve for DMX³ 4000 MPx.10 Protection Units: Instantaneous Trip Protection Detail
This graph illustrates the instantaneous trip protection (Ii) and its relationship with current (I). It shows the tripping time for very high short-circuit currents, with settings for Ii and Isf (fixed instantaneous override).
Icu | Values for Isf |
---|---|
50 kA | 50 kA |
65 kA | 65 kA |
100 kA | 85 kA |
Value | Description |
---|---|
I | Current |
In | Rated current |
tsd | Short time delay |
Ii | Instantaneous release |
Icw | Rated short time withstand current |
9.4 Ground Fault Curve for DMX³ 4000 MPx.10 Protection Units
This graph shows the ground fault (Ig) protection curve, illustrating tripping time versus current (I/Ig) for various settings of constant tripping time (tsd=k) and constant pass-through energy (I²tsd=k).
Value | Description |
---|---|
I | Current |
In | Rated current |
Ig | Ground fault current |
tsd | Short time delay |
tsd = k | Constant tripping time setting |
I²tsd = k | Constant pass-through energy setting |
9.5 Pass-through Specific Energy Curve (at 415 V)
This graph displays the specific energy (A²s) versus the short-circuit current (Icc) for different rated currents and protection settings (e.g., tsd=0.5, 0.2, 0.1).
10. Conformity
The DMX³ range complies with IEC/EN standards 60947-2 and 60947-3, with certifications available via IECEE CB-scheme or LOVAG Compliance scheme. Local certifications (CCC, EAC) are also available. The products conform to Lloyds Shipping Register, RINA, and Bureau Veritas Marine standards.
RoHS: Compliant with Directive 2011/65/EU (as amended by 2015/863/EU) on the restriction of hazardous substances.
REACH: Substances of Very High Concern (SVHC) are declared if present above 0.1% w/w, as per Regulation (1907/2006). No SVHCs listed in Annex XIV are currently found in this product.
WEEE: Sale includes contribution to environmental bodies for end-of-life product management.
PACKAGING: Compliant with European Directive 94/62/CE.
BATTERIES: Batteries and accumulators comply with European Regulation 2023/1542.
11. Other Information
Software Tools
- XLPro Calcul: Software for installers, design offices, and operators to define electrical characteristics of low voltage installations.
- XLPro³ Tool Selectivity and Backup: Software for installers and panelbuilders to define selectivity and backup values and obtain tripping curves.
- XLPro Panels: Software for panelbuilders and designers to design electrical distribution panels, generate diagrams, and estimate costs.
Documentation
- Workshop Book: Mounting information, equipment, accessories, and spare parts available on e-catalog.
- Instruction Sheet: Mounting information available on e-catalog.
- PEP (Product Environmental Profile): Available on e-catalog.
For further technical information, please contact Legrand technical support.