Immergas INAIL Safety Kit with Circulator and Separator (440-770 kW)

Product Code: COD.3.023648

Document Code: 1.034900 - rev. ST.009369/000 - 07/2025

General Warnings

All Immergas products are protected with suitable transport packaging. The material must be stored in a dry place protected from the weather.

This instruction manual provides technical information for installing the Immergas kit. For other issues related to kit installation (e.g., safety in the workplace, environmental protection, accident prevention), it is necessary to comply with regulations in force and principles of good practice.

Improper installation or assembly of Immergas appliances, components, accessories, kits, and devices can cause unexpected problems for people, animals, and objects. Read the product instructions carefully for proper installation.

Installation and maintenance must be performed in compliance with regulations, according to manufacturer's instructions, and by professionally qualified staff with specific technical skills in the plant sector, as envisioned by law.

Compatible Appliances

  • The entire Ares Tec range (150-900 kW)

Description

The primary ring mixing header fastens perfectly on condensing generators with low water content and very high modulation ratio.

The kit includes:

  • SAFETY kit
  • Hydraulic balancing circuit
  • Modulating pump
  • Mechanical impurity filtering system

Kit Components and Diagram Description

Figure 1 and Figure 2 illustrate the physical assembly of the safety kit. The main components include a large cylindrical separator vessel, a manifold assembly containing a modulating pump, a 'Y' filter, and various ports for safety devices, sensors, and connections. The assembly is supported by brackets and adjustable feet.

Main Kit Components:

Ref.Component NameDescription
3Modulation Pump
5Filter "Y" DN100 PN16
15Mixing Header DN100
CSupport bracket(2 positions)
DAdjustable foot
EManifold safety Kit (DN100 PN16)
FDN65/DN100 Adapter
6Expansion vessel/ more expansion vessels (optional, depends on power)
16Automatic air vent valve
17Dirt separator connection

Manifold Safety Kit Components:

Ref.Component NameNotes
2Minimum water pressure switchCertified
4Paddle flow switch(not supplied)
7Predisposition for expansion vessel connection
8Control well for thermometer
9Safety pressure switch (Max)
10Thermometer(scale 0°C ÷ 120°C)
11Safety thermostat
12VIC bulb well
13Safety valve(not supplied, max calibration pressure: 5.4 bar. Up to 580 kW = 1 valve; > 580 kW = 2 valves)
14Pressure gauge connection(3-way tap, shock absorber tube)
23Manometer(not supplied)

Mounting Dimensions and Position Components

Figure 2 provides critical mounting dimensions and component placement. Key dimensions include overall height, width, and depth. Specific clearance requirements are indicated, such as the 10 cm screed under the boiler or the assembly. The diagram also shows the adjustable positioning of the support bracket (C).

Key Dimensions (approximate):

  • Overall Height: 1230 mm
  • Overall Width: 1415 mm
  • Overall Depth: 770 mm (main unit)
  • Clearance for Position 1: 10 cm (screed under boiler)

Note on Support Bracket (C): The support bracket can be mounted in 2 positions, with a height range of 235-255 mm.

Height Requirements for Different kW Models:

  • Up to 440 kW: 1087 mm
  • 550 - 660 kW: 1355 mm
  • 770 - 900 kW: 1623 mm

Electrical Connections

Figure 4 and Figure 5 detail the electrical connections required for the safety kit. The diagrams show wiring from the main electrical panel (Q.E) to various terminals on the kit, including a Wieland power supply socket (D), flow switch (FL), external sensor (SE), and pump connector (C). It also illustrates connections to a Boiler Control Module (BCM) via terminal blocks.

Terminal Connections:

LabelDescription
Q.EMain electrical panel (not supplied)
BServices connection return terminal board
DWieland mobile power supply socket 230 V - 50Hz
FLTerminals for Flow switch
SETerminals for external Sensor
SMGGlobal flow sensor
CPump power connector

Safety Detail Items (INAIL Safety Connections):

These connections are typically made to a Boiler Control Module (BCM). If terminal block "B" is not present, connections should be made directly to the BCM as indicated.

  • INAIL Safety Inputs:
  • Terminal 9 (Max Pressure Switch)
  • Terminal 10 (Flow Switch)
  • Terminal 11 (Min Pressure Switch)
  • Terminal 12 (Safety Thermostat)

Note on BCM Connections: When connecting directly to the BCM without terminal block "B", remove any bridge connections and connect cables as indicated (e.g., Y2 10 to terminal block M2, Y2 11 to terminal block M2).

Analog and Digital Inputs:

The system supports analog inputs (AI 1/2) and digital inputs (DI 1/2).

  • Analog Inputs (AI 1/2): Typically configured for 0-10 V or 4-20 mA / PT 1000 signals. For 0-10V, AI 1 uses terminals 13 (+In) and 12 (-GND).
  • Digital Inputs (DI 1/2): Used for various sensor signals.
  • Safety Extra-Low Voltage (SELV): Connections are made to specific terminals for safe operation.

PDF preview unavailable. Download the PDF instead.

1.034900 Adobe InDesign 19.4 (Windows) Adobe PDF Library 17.0; modified using iText 5.3.0 ©2000-2012 1T3XT BVBA

Related Documents

Preview Immergas Safety Kit with Circulator and Separator (300-350 kW) - Technical Specification
This document provides technical specifications and installation details for the Immergas Safety Kit, featuring a circulator and separator for 300-350 kW applications. It is designed for use with Immergas Ares Tec condensing generators and includes components for hydraulic balancing, modulation, and impurity filtering, along with essential safety features.
Preview Immergas 150 kW Safety Kit with Circulator and Separator (Cod. 3.023645) - Technical Specifications
Detailed technical specifications and installation guidance for the Immergas 150 kW Safety Kit, including circulator, separator, and INAIL safety components. Learn about compatible appliances, electrical connections, and mounting dimensions.
Preview Immergas Safety Kit with Circulator and Separator (200-250 kW) - Technical Specification
Detailed technical specifications and component list for the Immergas Safety Kit, including circulator and separator, designed for Ares Tec condensing generators (200-250 kW). Includes wiring diagrams and installation details.
Preview Immergas 900 kW Safety Kit with Circulator and Separator - Technical Specification
Technical specification and installation guide for the Immergas 900 kW Safety Kit, featuring a circulator and separator. Details compatible Ares Tec generators, kit components, mounting dimensions, electrical connections, and INAIL safety features.
Preview Immergas AVIO-ZEUS KW 2L Supplementary Domestic Hot Water Vessel Kit Installation Guide
This document provides installation instructions for the Immergas AVIO-ZEUS KW 2L Additional Domestic Hot Water Vessel Kit. It includes general warnings, installation steps, and a diagram of the components.
Preview Immergas VICTRIX PRO V2: High-Efficiency Condensing Gas Boilers for Commercial & Residential Use
Explore the Immergas VICTRIX PRO V2 series of wall-hung light commercial condensing gas boilers. Featuring high efficiency, flexible installation, Hydrogen Ready technology, and advanced control options for optimal heating performance.
Preview Immergas Hydraulic Manifold Kit with Additional Boiler Kit Installation Guide
This document provides installation instructions and technical information for the Immergas Hydraulic Manifold Kit with Additional Boiler Kit (Cod. 3.033669). It details the components, assembly steps, and compatibility with Victrix Pro 35/55/80 V2 boilers.
Preview Immergas Hydraulic Manifold Kit Installation Guide
This document provides installation instructions and general warnings for the Immergas Hydraulic Manifold Kit with Additional Boiler (Cod. 3.033668). It details the components, assembly steps, and compatibility with Victrix Pro boilers.