Immergas 150 kW Safety Kit with Circulator and Separator
Product Code: 3.023645
Model: KIT SICUREZZA INAIL COMPLETO DI CIRCOLATORE E SEPARATORE (150 KW)
General Warnings
All Immergas products are protected with suitable transport packaging. The material must be stored in a dry place protected from the weather. This instruction manual provides technical information for installing the Immergas kit. As for the other issues related to kit installation (e.g., safety in the workplace, environmental protection, accident prevention), it is necessary to comply with the provisions specified in the regulations in force and with the principles of good practice. Improper installation or assembly of the Immergas appliance and/or components, accessories, kits and devices can cause unexpected problems for people, animals and objects. Read the instructions provided with the product carefully to ensure proper installation. Installation and maintenance must be performed in compliance with the regulations in force, according to the manufacturer's instructions and by professionally qualified staff, meaning staff with specific technical skills in the plant sector, as envisioned by the law.
Compatible Appliances
- The entire Ares Tec range (150-900 kW)
Description
The primary ring mixing header fastens perfectly on condensing generators with low water content and very high modulation ratio. The kit includes:
- SAFETY kit,
- hydraulic balancing circuit,
- modulating pump,
- mechanical impurity filtering system.
Diagrams and Components
Figure 1: Kit Components
This diagram illustrates the assembled safety kit with circulator and separator. Key components identified include:
- Adapters (DN50, DN40, DN80)
- "Y" Filter
- Modulating Pump
- Mixing Header (DN100)
- Support Brackets and Adjustable Foot
- INAIL Safety Kit Manifold: This includes a minimum water pressure switch, a maximum safety pressure switch, a thermometer (0°C to 120°C), a safety thermostat, a control well for the thermometer, a VIC bulb well, and connections for a pressure gauge (with a 3-way tap and shock absorber tube). It also notes the safety valve (not supplied) with a maximum calibration pressure of 5.4 bar, with one valve for up to 580 kW and two valves for over 580 kW.
- Expansion Vessel (optional, depending on power requirements)
- Automatic Air Vent Valve
- Dirt Separator Connection
Water content of the kit is 1.41 liters.
Figure 2: Mounting Dimensions and Component Positions
This diagram provides essential mounting dimensions and shows the spatial arrangement of the main components of the kit. It includes height and depth measurements for different model capacities (up to 150 kW, 200-250 kW, 300-350 kW) and indicates the placement of the pump, filter, expansion vessel, and mixing header.
Electrical Connections
This section details the electrical connections required for the kit. It shows a schematic linking the main electrical panel (Q.E., not supplied) to the kit components. Key connections include:
- Power supply (230 V - 50 Hz) via a Wieland mobile power supply socket.
- Terminals for a flow switch (FL).
- Terminals for an external sensor (SE).
- Connection for the modulating pump (C).
- Terminal board for services connection.
- Details for analog inputs (AI 1/2) for 0-10 V signals and digital inputs (DI 1/2).
- Safety Extra-Low Voltage (SELV) connections.
- Bus connections (Wilo Net).
The diagrams also show terminal configurations for analog and digital inputs, including specific pin assignments like '+In', '- GND', '+24V'.
Safety Detail Items (INAIL Safety Kit)
This diagram provides a close-up view of the INAIL safety kit components and their specific wiring connections, particularly when connecting to a BCM (Boiler Control Module) or a terminal block if the "B" terminal block is not present. It illustrates the connections for the minimum pressure switch (1.2), maximum pressure switch (1.1), safety thermostat (1.3), and flow switch (FL). It also details how to remove bridges and connect cables to the BCM or terminal block M2.