Siemens FC121-ZA / FC122-ZA / FC123-ZA / FC124-ZA Fire Control Panel
Series FC120
Cerberus™ FIT
- Compact, prefabricated microprocessor-controlled fire control panel
- Fire control panel can be used as a stand-alone version
- Available in 2, 4, 8, or 12 zones
- Compatible with Siemens detector ranges 110-series / DS11 and SynoLINE300 / SynoLINE600
- Integrated user-friendly operating unit
- Optional EVAC module, key switch, LED indicators
- Slots for output cards
- Emergency power supply for up to 72 hours of emergency power time
- Flexible programming capabilities
- Programmable alarm organization for manned/unmanned operation
- Event memory with stamped date and time
- Simple user controls via menu navigation
- Key code user access with optional key-switch alternative
- Easy on-site configuration
System Overview
The system overview illustrates the connectivity of various detector lines and components to the Siemens fire control panel. Detector lines include Cerberus 110-series, AlgoRex DS110x, Synova 600, Synova 300, and lines conforming to BS 5839 Pt1. It also shows connections for call points, mixed lines (detector/call point differentiation), and intrinsically safe detectors (via DC1192 and safety barrier SB3). The panel provides outputs for monitored control lines (for horns, sirens, beacons), fire controls (internal relays), and remote transmission (internal contact).
Type | Zones | Monitored outputs | Relay outputs | Output cards | Power supply | Battery |
---|---|---|---|---|---|---|
FC121-ZA | 2 | 2 | 1 | 1 | 25 W | Max. 7 Ah |
FC122-ZA | 4 | 2 | 1 | 1 | 25 W | Max. 7 Ah |
FC123-ZA | 8 | 2 | 1 | 2 | 70 W | Max. 17 Ah |
FC124-ZA | 12 | 2 | 1 | 3 | 70 W | Max. 17 Ah |
Functional Elements
The FC121-ZA, FC122-ZA, FC123-ZA, and FC124-ZA are compact fire control panels featuring an integrated operating unit suitable for 2, 4, 8, or 12 zones. They process signals from the 110-series / DS11 and SynoLINE300/600 series. The control unit is designed for ease of use while offering extensive flexibility through its feature list.
- All detector lines are monitored for ground faults.
- Customer-specific text can be adapted directly on the panel via menu navigation.
- Up to 1000 events can be stored according to various criteria.
- Automatic summer/winter time change is supported.
Detection
- Each line supports 110-series / DS11 and SynoLINE300/600 series devices.
- Detectors and call points can be on the same line with functional differentiation where allowed.
- Intrinsically safe detectors are supported via line coupler DC1192 and safety barrier SB3.
Maximum load of devices per line is 32. Refer to the List of compatibility (A6V10393192) for details.
Inputs / Outputs
FC121, FC122
- 2 monitored control lines (24 V / 500 mA) for horns, fire controls, external remote transmission.
- 1 dry output (30 V / 1 A).
- 2 programmable control inputs.
FC123, FC124
- 2 monitored control lines (24 V / 500 mA) for horns, fire controls, external remote transmission.
- 1 dry output (30 V / 1 A).
- 3 programmable control inputs.
Extensions
- Up to 6 monitored control lines (24 V / 1 A) for horns, fire controls, external remote transmission (depending on panel type).
- Up to 6 dry outputs (30 V / 1 A) (depending on panel type).
PMI (Personalized Message Interface)
- Individual customer text for each zone.
- User-friendly operation via menu navigation.
Commissioning
- Basic functions can be adapted on-site without a laptop.
- Simple start-up with preset default values.
- Service function to view the date and time of the last alarm.
Operating Unit
The operating unit includes:
- CPU module and electronics for the operating unit.
- Power supply.
- Additional connection terminals for accessories.
- 'Nordic SE' key switch.
- LED display (12 x 2 LED).
- EVAC Module.
- Output card.
Power Supply 25 W and 70 W, Emergency Power Supply
The power supply unit supplies the hardware and charges the batteries. Batteries provide emergency power in case of a power failure.
Configuration
Easy on-site configuration is possible via the integrated display, requiring no additional equipment.
Application Ranges
The FC120 series is ideally suited for small applications, such as schools, small shops, and hotels.
Overview of FC121-ZA, FC122-ZA, FC123-ZA, FC124-ZA
This section provides an overview of the different panel models and their expansion capabilities.
FC121-ZA & FC122-ZA
- FC121-ZA: 2 zones, with 25 W power supply, battery capacity 4 or 7 Ah.
- FC122-ZA: 4 zones, with 25 W power supply, battery capacity 4 or 7 Ah.
FC123-ZA & FC124-ZA
- FC123-ZA: 8 zones, with 70 W power supply, battery capacity 7, 12, or 17 Ah.
- FC124-ZA: 12 zones, with 70 W power supply, battery capacity 7, 12, or 17 Ah.
Expansion Modules
- FCA1203-Z1: Output card with 2 monitored outputs (24 V / 1 A) and 2 relay outputs (30 V / 1 A).
- FTO1201-H1: EVAC module for NL 2&4 Z, supporting 1 EVAC zone.
- FTO1203-H1: EVAC module for NL 8&12 Z, supporting 1 EVAC zone.
- FTO1202-Z1: Zone indicator field with 12x2 LEDs, featuring red + yellow LEDs.
Accessories FC12x-ZA
- FCA1206-Z1: Key switch set (Nordic SE) for access level II.
- FCA1209-Z1: Output module (230 V) with relay output (230 V / 5 A) for activating external equipment.
- FP120-Z1: Power supply kit A 70 W, providing additional power.
Configuration of FC121-ZA and FC122-ZA
The diagram shows the internal components and expansion slots for the FC121-ZA and FC122-ZA panels.
- Basic Equipment: Control panel with power supply and main board.
- Battery: Options include 12 V, 4 Ah (AX1213) or 12 V, 7 Ah (FA2003-A1) for emergency power supply.
- Expansion Slots: Space for expansions A, B, C.
Slot | Designation | Notes |
---|---|---|
A | FCA1203-Z1 (Output card 2M 2R) | 2 monitored outputs, 2 relay outputs |
B | FTO1201-H1 (EVAC module) | Expansion C is not possible |
C | FCA1206-Z1 (Key switch) | Expansion B is not possible |
Configuration of FC123-ZA and FC124-ZA
The diagram illustrates the internal components and expansion slots for the FC123-ZA and FC124-ZA panels.
- Basic Equipment: Control panel with power supply and main board.
- Battery: Options include 2 x 12 V, 7 Ah (FA2003-A1), 2 x 12 V, 12 Ah (FA2004-A1), or 2 x 12 V, 17 Ah (FA2005-A1) for emergency power supply.
- Power Supply: 70 W (FP2015-A1).
- Expansion Slots: Space for expansions A, B, C, D.
Slot | Designation | Notes |
---|---|---|
A | FCA1203-Z1 (Output card 2M 2R) | FC123: max. 2 additional cards; FC124: max. 3 additional cards |
B | FTO1202-Z1 (Zone ind. Field 12x2 LED) | Expansion C, D are not possible |
C | FTO1203-H1 (EVAC module) | Expansion B, D are not possible |
D | FCA1206-Z1 (Key switch) | Expansion B, C are not possible |
Disposal
The device is considered electrical and electronic equipment for disposal according to the applicable European Directive and must not be disposed of as domestic garbage. Dispose of the device through designated channels and comply with all local and currently applicable laws and regulations. Dispose of empty batteries in designated collection points.
Batteries
⚠️ WARNING: Switching batteries in parallel poses a risk of explosion and fire. Never connect batteries in parallel. If more power is needed, use batteries with a higher capacity.
Technical Data
FC121-ZA / FC122-ZA | FC123-ZA / FC124-ZA | |
---|---|---|
Mains voltage | AC 196...253 V | AC 97...127 V, AC 196...253 V |
Power consumption | 25 W | 70 W |
Operating voltage | DC 21...28.6 V | |
Max. nominal output current without battery charging (I max b) | Max. 0.9 A | Max. 2.5 A |
Battery capacity | 2x 12 V, up to 7 Ah | 2x 12 V, up to 17 Ah |
Battery monitoring | Yes | Yes |
Mains monitoring | Yes | Yes |
Connectable detector series | 110-series / DS11 / SynoLINE300/600 | |
Number of lines | 2 | 4, 8, 12 |
Number of detectors per line | Max. 32 | |
Integrated inputs/outputs | ||
Monitored outputs | 1x 24 V / 0.5 A | 1x 24 V / 1 A |
RT Alarm | 1x 24 V / 0.5 A | 1x 24 V / 1 A |
Horn | ||
Dry contact | 30 V / 1 A | |
RT fault | ||
Free programmable inputs/outputs | 2 | 3 |
Slots for relay cards | 1 | 2, 3 |
Emergency current | Up to 72 Ah | |
Operating temperature | -5...+40 °C | |
Storage temperature | -20...+60 °C | |
Humidity (no condensation permitted) | ≤95% rel. | |
Dimensions (W x H x D) | 360 x 310 x 85 mm | 430 x 399 x 124 mm |
Color (Housing and Cover) | Grey, ~RAL 000 50 00 | |
Protection category (IEC 60529) | IP30 |
Certifications:
- FC121-ZA / FC122-ZA: CE 14 2831. Compliant with EN 54-2 / EN 54-4, EN 50130-4 / EN 61000-6-3, EN 60950-1, EN 50581.
- FC123-ZA / FC124-ZA: CE 14 2831. Compliant with EN 54-2 / EN 54-4, EN 50130-4 / EN 61000-6-3, EN 60950-1, EN 50581.
Declaration of Performance (DoP) and EU Declaration of Conformity (DoC) are obtainable via the Customer Support Center or the Siemens website.
Details for Ordering
Type | Part no | Designation | Weight |
---|---|---|---|
Fire control panels | |||
FC121-ZA | S54400-C131-A1 | Fire control panel (2Z) | 1.840 kg |
FC122-ZA | S54400-C130-A1 | Fire control panel (4Z) | 1.845 kg |
FC123-ZA | S54400-C129-A1 | Fire control panel (8Z) | 4.113 kg |
FC124-ZA | S54400-C128-A1 | Fire control panel (12Z) | 4.128 kg |
Expansion | |||
FCA1203-Z1 | S54400-B142-A1 | Output card 2M 2R | 0.064 kg |
FTO1202-Z1 | S54400-B119-A1 | Zone ind. Field 12x2 LED | 0.125 kg |
FTO1203-H1 | S54400-B118-A1 | EVAC module (NL 8&12 Z) | 0.112 kg |
FTO1201-H1 | S54400-B120-A1 | EVAC module (NL 2&4 Z) | 0.074 kg |
FCA1209-Z1 | S54400-B124-A1 | Output module (230 V) | 0.068 kg |
FCA1206-Z1 | S54400-S125-A1 | Key switch set (Nordic SE) | 0.065 kg |
Power supply | |||
FP120-Z1 | S54400-S122-A1 | Power supply kit A 70 W | 3.920 kg |
Batteries | |||
AX1213 | Battery 4 Ah | 1.665 kg | |
FA2003-A1 | Battery (12 V, 7 Ah, VDS) | 2.450 kg | |
FA2004-A1 | Battery (12 V, 12 Ah, VDS) | 3.930 kg | |
FA2005-A1 | Battery (12 V, 17 Ah, VDS) | 5.640 kg | |
Spare part | |||
FP2015-A1 | S54400-B121-A1 | Power supply (70 W) | 0.575 kg |
Issued by: Siemens Switzerland Ltd, Smart Infrastructure, Global Headquarters, Theilerstrasse 1a, CH-6300 Zug. Website: www.siemens.com/buildingtechnologies. Document ID: A6V10371354_i_en_--. Edition: 2019-11-11. © Siemens Switzerland Ltd, 2012. Technical specifications and availability subject to change without notice.