Siemens XC1001-A Extinguishing Control Unit
Product Overview and Technical Details
Product Description
The Siemens XC1001-A is a self-contained extinguishing control unit designed for small and medium-sized extinguishing installations. It integrates fire detection and extinguishing control functions, offering a comprehensive solution for fire safety systems.
Key Features
- Controls small and medium-sized extinguishing installations.
- Designed for 1 extinguishing sector.
- Self-contained unit including fire detection and extinguishing control.
- Integrated control facility for remote transmission.
- Connectible to fire detection systems.
- Supports solenoids and pyrotechnical actuators.
- Compatible with Siemens conventional detector series.
- Features 2 selectable detector line standards for broad detector compatibility.
- Includes 4 detection lines, 4 monitored inputs, and 5 monitored control lines.
- Provides 5 voltage-free contacts and 8 driver outputs.
- Offers simple user controls with isolate/test buttons.
- Key code user access with an optional key-switch alternative.
- Allows for easy on-site configuration and various system test modes.
- Includes automatic calibration facility for actuator control lines.
- Integral capacity for emergency power of up to 30 hours.
- Supports a 4.5 Ah battery (2 x 12 V).
- Complies with EN12094 and EN54 standards.
Typical Installation and Peripheral Devices
Typical Extinguishing Installation with XC10
The system is designed for a typical extinguishing installation involving a flooding area and a cylinder bank. Key elements include:
- Flooding Area: Contains fire detectors (in cross-zoning, 2 zones), an alarm horn (with programmable sound), and a door close device.
- Cylinder Bank: Houses the actuator unit (solenoid or pyrotechnical actuators), a pressure switch (with "released" contact), a weight device (with "loss of agent" contact), and a mechanical blocking device (with "open" and "closed" contacts).
- Adjacent Area: Can include an additional detector zone.
- Control Connections: The XC1001-A unit connects to detectors, alarm horns, door locks, ventilation systems (for shut down), and remote transmission systems.
Typical Peripheral Devices with XC1001-A
- Flooding Area Devices: Fire detectors (2 zones), alarm horn (variable sound, programmable), door close device.
- Cylinder Bank Devices: Actuator unit (solenoid/pyrotechnical), pressure switch ("released" contact), weight device ("loss of agent" contact), mechanical blocking device ("open"/"closed" contacts).
- Outside Flooding Area Devices: Manual release button(s), warning panel (on door), emergency hold/abort button (near entrance/door lock), fire control contacts (for ventilation shutdown and door closing), optional repeater, detector in adjacent area (1 zone), and facility to trigger remote transmission.
Mechanical Assembly and System Components
The unit comprises several key components:
- Main board
- Power supply unit (3.5 A / 28 VDC)
- Battery (4.5 Ah, 2 x 12 V)
- Fire control relays (optional)
- Add-on module for extra input (optional)
- RT isolation card (optional)
- Key switch for access level 2 (optional)
- Accessory set for FDCIO
Operating Panel
The operating panel is divided into extinguishing and fire sections and is labelled with slide-in inscription stripes available in various languages. It features controls and indicators for system status, modes, and zone management.
Key Controls and Indicators (Legend):
- 1. Access code entry: Separate user and engineer code access.
- 2. Silence Re-sound Horn: Controls horn silencing and re-sounding.
- 3. Mode select button: For selecting operational modes.
- 4. Test buttons: For various system tests (e.g., Lamp test, Detector test).
- 5. Disable/enable buttons: For disabling/enabling functions or outputs.
- 6. Zone disable/enable button: For managing detector zones.
- 7. Zone test/cancel button: For zone testing and cancellation.
- 8. Silence buzzer & reset button: For silencing the buzzer and resetting the system.
Indicators include System ON, Mech. blocked, Silence, Re-sound, Disabled, Detector test, Fault, Emergency hold/abort, Loss of agent, Earth fault, Power fault, Peripheral fault, System fault, System test, etc., for different zones and functions.
Technical Data
Parameter | Value |
---|---|
Mains voltage | 230 VAC, +10%/-15%, 50/60 Hz |
Power consumption | 20... 150 VA |
Quiescent current | 132 mA |
Emergency power operating | max. 30 h |
Outputs |
|
Control inputs (4) | Positive potential via dry contact |
Operating temperature | 0... +40 °C (class A) |
Storage temperature | -20... +60 °C |
Humidity (no condensation) | ≤95% rel. |
Cabinet Dimension (W x H x D) | 370 x 286 x 90 mm |
Color cover | white RAL 9003 |
Protection category (IEC 60529) | IP 30 |
Standards | EN12094-1 / EN 54-2, EN54-4 |
Details for Ordering
Type | Part no | Designation | Weight |
---|---|---|---|
XC1001-A | A6E60500060 | Extinguishing control unit | 4.102 kg |
XC1001-B | A5Q00018177 | Extinguishing control unit France | 4.102 kg |
XCA1016 | A5Q00016213 | Add-on module | 0.004 kg |
FCA1005-D | A6E60500024 | RT-isolation card | 0.039 kg |
Z3B171 | 4843830001 | Relay module | 0.040 kg |
FCA1007 | A6E60500026 | Kit key switch standard | 0.175 kg |
XCA1020 | A5Q00025158 | Accessory set for FDCIO | 0.150 kg |
XCE1002 | A5Q00015659 | Trigger element | – |
FA2010-A1 | A5Q00019674 | Battery 4.5 Ah / 12 V | 1.700 kg |
Inscription Stripes
Inscription stripes are shipped with each control unit and are available in multiple languages, including English, French, German, Italian, Spanish, Dutch, Flemish, Portuguese, Polish, Czech, Swedish, Danish, Norwegian, and Finnish.
Reference Documents
- Doc. No. 008399: XC1001-A Technical manual
- Doc. No. 008400: XC1001-A Operating manual