Siemens Connect X300 Installation Instructions

Description

Connect X300 is a physical device that serves as the gateway connection between a Cloud service and a controlled/monitored system. This system in a building can include fire alarm control panels, devices, sensors, detectors, etc.

Figure 1: Connect X300 Gateway

[Diagram showing the Connect X300 gateway with labeled ports: X60, X61, X63, X70, X62, X80, X30, X1 P1, X2 P1, X31. Includes labels for Earth Screw, Power Supply, Fire Panel Connection, Internet Access, and several "NOT USED" ports.]

Connections and Indicators

  • X1P1: Connection to Desigo Fire Safety Modular/Cerberus PRO Modular via FCM2041-U2/-U3 Operator Interface.
  • Connection to Desigo FC2025/FC2050 and Cerberus PRO FC922/FC924 via FCM2018/2019/2035-U2/-U3 Operating Units.
  • Connection to Desigo FV2025/2050 and Cerberus PRO FV922/924 via VCA2002-A1 Card Cage.
  • X2P1: Connection to internet network.

Features

  • Two Ethernet ports for WAN and LAN.
  • Remote firmware and configuration data update over the IP Interface.
  • LED indication of activities and state.
  • Operating voltage: DC 24V.
  • Max current load: 515mA DC.
  • Plug-in screw terminal block for supply.
  • Mounting on wall using enclosures.

Depending on firmware, the following functions are supported (examples):

  • Multi-site management.
  • Remote monitoring.

Application

The device integrates Desigo Fire Safety Modular, Cerberus PRO Modular, Desigo FC2025/FC2050/FV2025/FV2050, and Cerberus PRO FC922/FC924/FV922/FV924 fire panels over IP. It transmits data to the cloud over IP networks or over mobile networks (3G/4G/LTE).

Functions

The Connect X300 provides two integration levels to connect fire alarm control panels to the cloud: System integration (between the Connect X300 and the fire panels) and cloud integration (between the Connect X300 and the cloud). The Connect X300 supports Ethernet and 3G/4G/LTE for cloud connectivity.

Mounting and Wiring

The Connect X300 can be mounted inside the ENCL-01, P/N S54465-C63-A1, or PAB-ENCL Siemens enclosures using adaptor plates. Adaptor plate CGAP, P/N S54811-B101-A1, is used with the ENCL-01 enclosure while adaptor plate CGAP2, P/N S54811-B102-A1, is used for the PAB-ENCL enclosure. Refer to Figures 2 through 6.

Wiring the Connect X300 Gateway inside PAB-ENCL Enclosures

To connect the ethernet cable, see Figure 3. Use knockouts from the right side; wires are considered Power Limited. To connect the power to the Connect X300 Gateway, see Figure 2. Option: The FP2011-U1 Power Supply can be used with the cable provided to connect the power from the FP2011-U1 Power Supply to the Connect X300 Gateway. Use knockout close to the location of the Power Supply to enter the box. Wires are considered Non-Power Limited.

Power Connection Diagrams

Figure 2: Desigo Fire Safety Modular/Cerberus PRO Modular System Power Connection to Connect X300

[Diagram showing the ENCL-01 Enclosure (S54465-C63-A1) with CGAP Adapter Plate (S54811-B101-A1) mounting the Connect X300 Gateway (S55842-Z121-A100). Wires (12-22 AWG Black) are inserted into a 2-POS Power Plug (Black Wire to POS "L+"). A PSC-12 Power Supply is shown, connected to Terminal Block TB3 (24VDC @ 4A) via a 12-22 AWG Red wire. Notes on Power Limited vs. Non-Power Limited wiring and separation requirements (1/4" separation) are included.]

Figure 4: Desigo and Cerberus PRO Power Connection to Connect X300 Gateway

[Diagram similar to Figure 2, showing power connection to the Connect X300 Gateway within an enclosure, referencing FCI2016-U1 OR FCI2017-U1. Wiring specifications are repeated.]

Ethernet Connection Diagrams

Figure 3: Desigo Fire Safety Modular/Cerberus PRO Modular System Ethernet Connection to Gateway

[Diagram showing the Rear View of FCM2041-U2/-U3 Operator Interface and the Connect X300 Gateway (S55842-Z121-A100). Connections are made via X1P1 Plug on the gateway and J11 Ethernet Plug on the interface. An Ethernet Cable (6 ft., User Provided) is used. Notes on Power Limited wiring and UL/ULC application restrictions (wiring limited to 20 ft. in conduit for UL, 18 m. for ULC) are included.]

Figure 5: Desigo and Cerberus PRO Fire Only Panel Ethernet Connection to Connect X300 Gateway

[Diagram showing a Desigo/Cerberus PRO Fire Only Panel (FCM2018-U2/-U3, FCM2019-U2/-U3, OR FCM2035-U2/-U3) with an X5 connection. The Connect X300 Gateway is connected via X1P1 Plug. X2P1 Plug goes to Internet Connection. Ethernet cable details and restrictions are repeated.]

Figure 6: Desigo and Cerberus PRO Fire Voice Panel Ethernet Connection to Connect X300 Gateway

[Diagram showing connections to a VCA2002-A1 Card Cage (X301 or X302) and various ports on a Desigo/Cerberus PRO Fire Voice Panel. The Connect X300 Gateway is connected via X1P1 Plug. X2P1 Plug goes to Internet Connection. Ethernet cable details and restrictions are repeated.]

Configuration

Configuring for the Cerberus PRO FC922/FC924/FV922/FV924 and Desigo FC2025/FC2050/FV2025/FV2050

Refer to FG2004 Commissioning Guide, Document ID A6V11382550.

Configuring for the Desigo Fire Safety Modular/Cerberus PRO Modular using Zeus

  1. Insert a Custom Enclosure.
  2. Under this, insert the X300 Gateway.
    • Connection Supervision: Check property to enable supervision. If checked, a "Not responding trouble" will be reported each time the connection between the Operator Interface and Connect X300 is lost. By default, this property is unchecked.
    • Cloud Battery Backup: Check option to add the gateway to the battery calculations. By default, the value is checked.

Cyber Security Disclaimer

Siemens provides a portfolio of products, solutions, systems, and services that include security functions supporting the secure operation of plants, systems, machines, and networks. In Building Technologies, this includes building automation and control, fire safety, security management, and physical security systems.

To protect against cyber threats, a holistic, state-of-the-art security concept is necessary and must be continuously maintained. Siemens' portfolio is one element of such a concept. Users are responsible for preventing unauthorized access to their systems, which should only be connected to an enterprise network or the internet when necessary and with appropriate security measures (e.g., firewalls and/or network segmentation) in place. Siemens' guidance on appropriate security measures should be taken into account. For additional information, contact your Siemens sales representative or visit https://www.siemens.com/global/en/home/company/topicareas/future-of-manufacturing/industrial-security.html.

Siemens' portfolio undergoes continuous development for enhanced security. Siemens strongly recommends applying updates as soon as they are available and using the latest versions. Using unsupported versions or failing to apply updates may increase exposure to cyber threats. Siemens strongly recommends complying with security advisories on the latest security threats, patches, and other related measures, available at https://www.siemens.com/cert/en/cert-security-advisories.htm.

Models: Connect X300, Connect, X300

File Info : application/pdf, 10 Pages, 1.50MB

PDF preview unavailable. Download the PDF instead.

?tmstv=1676639565

References

Microsoft Word for Office 365

Related Documents

Preview Siemens FCM2041-U3 Operator Interface Installation Instructions
Installation instructions for the Siemens FCM2041-U3 Operator Interface, part of the Cerberus PRO Modular system. Covers introduction, diagnostics, installation, and operation.
Preview Siemens ZIC-4A Zone Indicating Card Installation Instructions
Detailed installation instructions for the Siemens ZIC-4A Zone Indicating Card, covering its features, operation, wiring, and configurations for various notification appliance and releasing service applications.
Preview Siemens Cerberus PRO/FIT OOH740/OOHC740 Automatic Fire Detectors - Technical Overview
A comprehensive guide to Siemens Cerberus PRO and Cerberus FIT automatic fire detectors, including the OOH740 multi-sensor and OOHC740 fire and CO detectors. Details features, ASAtechnology, applications, detector bases, accessories, technical specifications, and installation notes.
Preview Siemens MLC MXL Line Card Installation Instructions
This document provides detailed installation instructions for the Siemens MLC MXL Line Card. It covers introduction, operation, controls, indicators, pre-installation, installation steps, firmware upgrades, wiring, compatibility, electrical ratings, and cybersecurity considerations for use with Siemens FireFinder-XLS, Desigo Fire Safety Modular, and Cerberus PRO Modular systems.
Preview Siemens SNC Serial Network Card Installation Instructions
Comprehensive installation guide for the Siemens SNC Serial Network Card for USB Application with Windows, covering operation, configuration, physical installation, electrical connections, and driver setup.
Preview Siemens Cerberus PRO Intelligent Voice Communication System
Detailed technical data sheet for the Siemens Cerberus PRO intelligent voice communication system, outlining its advanced fire protection and integrated voice evacuation capabilities. Covers system specifications, components, and ordering information.
Preview Siemens ILED-XC and ILED-XW Intelligent Remote Lamps Installation Instructions
Installation instructions for Siemens ILED-XC (round plate) and ILED-XW (rectangular plate) intelligent remote lamps with dual isolators. This document covers introduction, mode of operation, controls and indicators, programming, wiring, and electrical ratings.
Preview Manuel de Programmation Siemens FC2005/FC901 : Panneau de Contrôle d'Alarme Incendie
Guide complet pour la programmation et la configuration du panneau de contrôle d'alarme incendie Siemens FC2005/FC901. Ce manuel couvre l'interface, les opérations, les niveaux d'utilisateur, la gestion des événements, les paramètres système et le dépannage.