Siemens Cerberus® PRO Intelligent Voice Communication System
Advanced fire protection system with integrated voice evacuation
Specifications for Architects and Engineers
- Voice communication panel with fire protection: resistant, intelligent, and intuitive.
- Model FV922: 252-point intelligent and addressable voice communication system.
- Model FV924: 504-point intelligent and addressable voice communication system.
- Voice systems exceed intelligibility requirements.
- Three-channel message repeater supporting up to 300 messages.
- 150 watts of amplification per unit.
- Three (3) simultaneous audio signals per panel.
- Communication with Cerberus PRO detection devices.
- Full support for standard and advanced intelligent detectors.
- Models OOHC941, OOH941, OH921, OP921, and HI921.
- Gas alarm events for CO detection, per NFPA 72.
- Voice and fire protection systems networkable on CAT5 or fiber optic cables.
- Supports up to 32 voice and fire protection panels.
- Utilizes Voice over Internet Protocol (VoIP) technology.
- All voice and fire protection signals transmitted over the same conductors.
- Support for multiple command stations.
- Cerberus DMS hazard management station can monitor and control up to 64 FV922/FV924 systems.
- UL listed for Fire Protection [UL 864/ULC-S527] and Mass Notification [UL 2572/ULC-S527] on a single Fire Alarm Control Panel (FACP).
- Separate event queues for Mass Notification System (MNS) events.
- MNS events can have higher or lower priority than fire events.
- Compatibility with MNS devices on the addressable loop.
- Compatibility with pre-action, deluge, and Sinorix agent release systems.
- Supervision of release valve.
- Supervision of sprinklers.
- Supports multiple display annunciators.
- UL and ULC listed; FM, CSFM, and NYCFD approved.
- Per UL 464, FV922/FV924 systems comply with low-frequency (520 Hz) tone requirements for sound signaling devices when used with compatible Siemens high-fidelity amplifiers and speaker/speaker-strobe devices.
- Integrated TCP/IP connectivity.
Product Overview
Siemens Cerberus PRO intelligent voice communication is an advanced, addressable fire alarm system with voice evacuation technology. Utilizing its proprietary "networked" multiprocessor design and intelligent detection devices, Cerberus PRO offers a flexible fire protection system with integrated voice evacuation and a wide range of configuration options.
Cerberus PRO voice panels are ideal for small to mid-market applications, supporting up to 252 (FV922) or 504 (FV924) addressable points on a network, with a history log of up to 10,000 events.
Each Cerberus PRO system features user-friendly controls including programmable keys, a backlit LCD display, and a four-direction navigation button.
Cerberus PRO voice panels are UL 864 10th Edition, UL 1711, UL 2017, and UL 2572 listed; ULC-S527 and ULC-S559 listed.
The ABHW-4B is a unique sounder base that can be powered directly from the signaling line circuit (SLC) in a two-wire configuration when used with intelligent Cerberus PRO detectors.
The ABHW-4S sounder base generates a 520 Hz square wave audio signal compliant with NFPA 72 and Underwriters' Laboratories applications.
Cerberus PRO standard and advanced intelligent detector lines offer high sensitivity with very early warning fire detection (VEWFD), carbon monoxide (CO) gas detection, and seven field-adjustable heat detection temperature settings.
System Components
Main System Components
Voice Communication System
- System Enclosure: Three-rack-unit (3HU) enclosure for FV922/FV924 models.
- Components of a 3HU Enclosure:
- Operating Unit (standard or with LED).
- Peripheral board.
- 300W Power Supply.
Operating Interface Unit
- Model: FCM2018-U3 (standard), FCM2019-U3 (with LED).
- Functions as the operator interface and central microprocessor for fire terminals and Cerberus PRO FACPs.
- Features easy event "acknowledgment", control of notification appliance circuits (NACs), and manual system reset.
- 2" x 4-3/4" backlit LCD display for event information.
- Site-specific program configuration using "Cerberus Works" software.
- Supports connection to remote peripheral modules (FCA2018-U1) and remote terminal displays.
- For Canada, the FCM2035-U3 is required for LED operating units.
Peripheral Boards
- Models: FCI2016-U1, FCI2017-U1.
- Integral components for FV922/FV924 panel operation.
- Monitor and supervise input device identity.
- Control signaling line circuits for smoke detectors and field devices (C-NET).
- Each board features two (2) programmable Class B (Style Y) or one (1) Class A (Style Z) NAC, with 24VDC/5A output per circuit for audio/visual notification devices.
- Mount directly into the rear compartment of FV922/FV924 enclosures.
- Provide two (2) parallel auxiliary power connections (24VDC/1.5A max) for external modules and devices.
Power Supply Module
- Model: FP2012-U1.
- 300-watt power supply providing regulated 24VDC for Cerberus PRO systems.
- 11.5 Amps regulated 24VDC output.
- Includes two (2) 6.3A slow-blow fuses and an AC line filter.
- Installs in the rear box of FHB2005-U1/R1.
- For applications requiring over 300W, the FP2013-U1 can optionally power FV922/FV924 voice systems, providing up to 600W at 24VDC.
Voice System Components
Voice System Card Compartment
- Model: VCA2002-A1.
- Accommodates various cards for FV922/FV924 panels.
- Supports:
- Voice CPU card (VCC2001-A1).
- Voice I/O card (VCC2002-A1).
- 25V/70V Voice Amplifier card (VCI2001-U1) (up to four 50W amplifiers).
- Provides six (6) slots for card installation.
Voice System CPU Card
- Model: VCC2001-A1.
- Controls and monitors all modules and functions of Cerberus PRO intelligent voice FACPs.
- Installs in the VCA2002-A1 compartment.
- Works with the Voice I/O card (VCC2002-A1) to control the voice system.
Voice System I/O Card
- Model: VCC2002-A1.
- Provides input/output for the Cerberus PRO voice system.
- Installs in the VCA2002-A1 compartment.
- Features two (2) local audio inputs and one (1) low-level audio output.
Voice Amplifier Card (25/70V)
- Model: VCI2001-U1.
- Provides 50W AC power between the FV922/FV924 panel and the site speaker system.
- Installs in the VCA2002-A1 card compartment.
- Supports up to four (4) amplifiers for 3+1 or 1+1 redundancy.
MoNET Connection Module
- Model: FCA2031-A1.
- Facilitates communication between operating units and voice CPU cards.
- Can provide system integration with Ethernet switches.
- Installs in position 1 of an FCM series operating unit.
Remote Microphone Kit
- Models: VR2005-U3/R3.
- Includes components for a remote voice station.
- Supports up to four (4) remote voice stations per intelligent voice panel.
Microphone Option Module
- Model: VTO2004-U3.
- Provides live, unrecorded voice communication.
- Can be used as a primary or remote microphone.
- Supports up to two (2) VTO2004-U3 microphones per FV922/FV924 FACP.
Switch Option Module
- Model: VTO2001-U3.
- Features programmable, illuminated pushbuttons.
- Each module has 24 group switches and up to 96 multicolor LED status indicators.
- Can be used in conjunction with the VTO2004-U3 microphone option module.
Battery Mounting Bracket
- Model: FHA2044-U1.
- Secures 33 AH system battery packs.
- Seismically compliant.
DIN Rail Kit
- Model: FHA2031-U1.
- Optional kit for mounting components.
100W Booster Amplifier (and Enclosure)
- Model: EBA2004-A1 (amplifier), FH2016-U1/R1 (enclosure).
- Expands speaker zones for increased system amplification.
- Amplifier includes a 50W amplifier, battery charger, and removable terminal blocks.
Three-Rack-Unit (3HU) Enclosure/Cabinet
- Largest enclosure available for Cerberus PRO panels, used exclusively for voice systems.
- Available in red or black.
- Components include: rear box, inner doors, clear objectives, outer door, and blank plate.
Back Box for 3HU Enclosure
- Models: FHB2005-U1 (black), FHB2005-R1 (red).
- Part of the 3HU system hardware for mounting an outer door.
Series S License Keys
- Model: FCA2033-A1 (S1), FCA2034-A1 (S2), FCA2035-A1 (S3).
- Enable virtual monitoring and control, BACnet output, and combined functionality.
3HU Outer Door
- Accommodates the system operating unit, voice card compartment, and battery brackets.
Clear Objectives
- Model: FHD2006-U1.
- Robust Lexan® window for door openings.
3HU Blank Plate
- Model: FHD2009-U1.
- Covers unused spaces in a 3HU enclosure.
3HU Enclosure/Cabinet Trim Kit
- Models: FHA2043-U1 (black), FHA2043-R1 (red).
- Provides a finished look for recessed 3HU cabinets.
Interior Doors
- Model: FHD2004-U1.
- Stores the standard or LED operating unit.
- Accommodates one operating unit or up to four (4) LED option modules.
Modular Ethernet Switch
- Model: FN2012-A1.
- Network connector for Cerberus PRO fire-only FACPs and voice systems.
- Supports CAT5, multimode fiber, or single-mode fiber connections.
Electric Ethernet Module
- Model: VN2001-A1.
- Network connector for Siemens fire-only FACPs and voice systems.
Single-Mode Ethernet Module
- Model: VN2003-A1.
- Network connector for Siemens fire-only FACPs and voice systems using single-mode fiber optic cables.
Multimode Ethernet Module
- Model: VN2002-A1.
- Network connector for Siemens fire-only FACPs and voice systems using multimode fiber optic cables.
Voice over Internet Protocol (VoIP) Module
- Model: VCI2003-A1.
- Converts analog and digital voice signals for VoIP applications.
- Installs on the voice CPU card for network voice applications.
Remote Terminal Board ("Class B")
- Model: VTA2001-A1.
- Supports the 24-switch option module and microphone option module for remote enclosures.
- Serves as a central station for audio output, system communication, and 24VDC power.
LED and Tabular Annunciator Controller
- Model: FT2007-U1.
- Key component for custom graphic annunciators.
- Provides outputs for system and zone status.
- Monitored via RS-485 interface.
Tabular Annunciators
- Series: FT2008 (16 zones), FT2009 (32 zones).
- Display system events from Cerberus PRO panels in real-time.
Cerberus PRO Fire Components
- C-WEB Network Module: Model FN2001-U1. Enables network connection for up to 32 FACPs and fire terminals via the C-WEB system bus.
- City/Dedicated Line Link Module: Model FCI2020-U1. Provides local power output for municipal public telephone connections and reverse polarity output for dedicated line connections.
Release Module
- Model: XCI2001-U1.
- Optional module connecting to peripheral boards for two (2) optional release circuits.
- Supports activation of release valves in extinguishing/pre-action systems.
- Supports Class B or Class A release circuits.
Remote Terminal Display (with RS-485 Interface)
- Models: FT2014-U3/R3, FT2015-U3/R3.
- LED/LCD units displaying the status of a 252/504-point Cerberus PRO system.
- Display event details and allow for remote control capabilities.
- Connect remotely via RS-485 interface. Requires FCA2016-U1 RS-485 module.
NAC Expansion Module
- Model: FCI2011-U1.
- Optional module connecting to peripheral boards to provide additional NACs for 252 and 504-point systems.
- Each NAC has a 3-amp rating.
Remote Peripheral Module (with RS-485 Interface)
- Model: FCA2018-U1.
- Provides a connection medium for a Cerberus PRO panel to a parallel printer for configuration and system status reports.
- Connects remotely to the RS-485 bus.
LED Option Module(s)
- Models: FCM2023-U3, FCM2034-U3 (Canadian).
- Provide system activity notification via LEDs.
- Configurable for up to 24 zone indicators or 48 individual LEDs.
Blank Option Module
- Model: FCM2022-U3.
- Covers unused LED spaces in the interior door.
Related Documentation
Model | Data Sheet # | Product |
---|---|---|
OH921 | 9300 | Cerberus DMS management stations |
HI921 | 9900 | Thermal (heat) detector |
OP921 | 9901 | Photoelectric smoke detector |
OOHC941 | 9903 | Multi-criteria fire/CO detector [with ASA technology] |
OOH941 | 9904 | Multi-criteria fire detector [with ASA technology] |
FDCIO422 | 9905 | 4-input, 4-output interface module |
FDBZ492/-HR,-R-PR | 9906 | "FDBZ" series air duct housings |
DB2-HR, DB-11/DB-11E | 9907 | "DB" series detector bases |
ABHW-4B | 9909 | Intelligent sounder base (sensor) |
ABHW-4S | 9910 | Sounder base (sensor) for break areas |
Cerberus PRO Voice Electronic Parts Package
Model | Part Number | Product |
---|---|---|
FV920-EK | S54400-C167-A1 | Voice electronic parts package includes:
|
Cerberus PRO Voice Enclosure Package
Model | Part Number | Product |
---|---|---|
FHK2004-U3 | S54400-C168-A1 | Voice enclosure package (black) Includes:
|
FHK2004-R3 | S54400-C169-A1 | Voice enclosure package (red) Includes:
|
Cerberus PRO Booster Amplifier Package
Model | Part Number | Product |
---|---|---|
EBA2001-U1 | S54400-B140-A1 | 100W booster amplifier package (black) includes:
|
EBA2001-R1 | S54400-B141-A1 | 100W booster amplifier package (red) includes:
|
Cerberus PRO Remote Microphone Package
Model | Part Number | Product |
---|---|---|
VR2005-U3 | S54400-C90-A1 | Remote microphone kit (black) includes:
|
VR2005-R3 | S54400-C92-A1 | Remote microphone kit (red) includes:
|
Ordering Information (Parts)
Model | Part Number | Product |
---|---|---|
FHB2005-U1 | S54400-B110-A1 | 3HU enclosure rear box, black |
FHB2005-R1 | S54400-B110-A2 | 3HU enclosure rear box, red |
FHD2004-U1 | S54400-B52-A1 | Black inner door (center space open for module access) |
FHD2005-U1 | S54400-B53-A1 | Opaque black inner door (no open space/opening) |
FHD2006-U1 | S54400-C46-A1 | Clear Lexan objective window |
FHD2007-U3 | S54400-B113-A1 | 3HU outer door, black (contains three {3} openings with windows) |
FHD2007-R3 | S54400-B113-A2 | 3HU outer door, red (contains three {3} openings with windows) |
FHD2009-U1 | S54400-B114-A1 | 3HU blank plate, black |
FHD2009-R1 | S54400-B114-A2 | 3HU blank plate, red |
FHD2012-U1 | S54400-C135-A1 | Black inner door [used in Canadian RDT installations] |
FN2001-U1 | S54400-A60-A1 | C-WEB network module |
FN2012-A1 | S54400-B152-A1 | Modular Ethernet switch |
FP2012-U1 | S54400-Z60-A1 | 300-watt power supply |
FP2013-U1 | S54400-Z61-A1 | 600W expanded power supply |
FT2007-U1 | S54400-A142-A1 | LED annunciator controller |
FT2008-U1 | S54400-A143-A1 | 16-zone tabular annunciator, black |
FT2008-R1 | S54400-A144-A1 | 16-zone tabular annunciator, red |
FT2009-U1 | S54400-A145-A1 | 32-zone tabular annunciator, black |
FT2009-R1 | S54400-A146-A1 | 32-zone tabular annunciator, red |
FT2014-U3 | S54400-B80-A1 | Remote terminal display, black |
FT2014-R3 | S54400-B73-A1 | Remote terminal display, red |
FT2015-U3 | S54400-888-A1 | Remote terminal display, black (contains three {3} buttons) |
FT2015-R3 | S54400-B16-A1 | Remote terminal display, red (contains three {3} buttons) |
FTI2001-U1 | S54400-A58-A1 | Fire terminal panel |
VCA2002-A1 | S54400-A47-A1 | Voice system card compartment (4A) |
VCC2001-A1 | S54400-A40-A1 | Voice CPU card |
VCC2002-A1 | S54400-A41-A1 | Voice I/O card |
VCI2001-U1 | S54400-A45-A1 | Voice amplifier card (25V or 70V) |
VCI2003-A1 | S54400-A141-A1 | VoIP Module |
VN2001-A1 | S54400-A42-A1 | Electric Ethernet Module |
VN2002-A1 | S54400-A43-A1 | Multimode Ethernet Module |
VN2003-A1 | S54400-A44-A1 | Single-mode Ethernet Module |
VR2005-U3 | S54400-C90-A1 | Remote microphone kit, black |
VR2005-R3 | S54400-C92-A1 | Remote microphone kit, red |
VTA2001-A1 | S54400-F163-A1 | "Class B" remote terminal board |
VTO2001-U3 | S54400-C60-A2 | Optional module, 24 switches |
VTO2004-U3 | S54400-C61-A2 | Optional module, microphone |
XCI2001-U1 | S54400-A69-A1 | Release Module |
Environmental Specifications
The Siemens Cerberus PRO intelligent voice communication system is UL 864 10th Edition listed for dry indoor environments within a temperature range of 32°F to 120°F (0°C to 49°C) and 0°F to 120°F (-2°C to 49°C), and with a relative humidity of 93% ±2% at 90°F ±3°C (32°F ±2°C).
Related Documents
![]() |
Siemens Cerberus PRO Intelligent Voice Communication System Detailed specifications and overview of the Siemens Cerberus PRO Intelligent Voice Communication system, an advanced fire-protection system with integrated voice evacuation. Covers system components, capabilities, and ordering information. |
![]() |
Siemens Desigo Fire Safety: Comprehensive Fire Protection Solutions Explore the Siemens Desigo Fire Safety system, a comprehensive portfolio of innovative fire detection, alarm signaling, voice communication, and operator control technologies designed for diverse environments. Learn about its scalability, advanced ASAtechnology™ detectors, and integrated solutions for total building safety. |
![]() |
Siemens FS920 Fire Alarm Control Panel Installation Instructions Comprehensive installation guide for Siemens FS920 Fire Alarm Control Panel series, including FC922, FC924, FT924, FV922, FV924, and VR2005. Covers system overview, installation, wiring, electrical characteristics, limitations, and battery calculations. |
![]() |
Siemens ILED-XC and ILED-XW Intelligent Remote Lamps Installation Instructions Installation instructions for Siemens ILED-XC (round plate) and ILED-XW (rectangular plate) intelligent remote lamps with dual isolators. This document covers introduction, mode of operation, controls and indicators, programming, wiring, and electrical ratings. |
![]() |
Siemens VCA2002-A1 Card Cage Installation Instructions Detailed installation instructions for the Siemens VCA2002-A1 Card Cage, a component of the FS20 Fire Voice Control System, covering its features, pre-installation, operation, mounting, card installation, wiring, and electrical ratings. |
![]() |
Siemens Cerberus PRO/FIT OOH740/OOHC740 Automatic Fire Detectors - Technical Overview A comprehensive guide to Siemens Cerberus PRO and Cerberus FIT automatic fire detectors, including the OOH740 multi-sensor and OOHC740 fire and CO detectors. Details features, ASAtechnology, applications, detector bases, accessories, technical specifications, and installation notes. |
![]() |
Siemens Smart Infrastructure Solutions Overview An overview of Siemens' comprehensive Smart Infrastructure solutions, covering fire safety, voice alarm systems, gas detection, access control, intrusion detection, building automation, electrical products, and digital services for enhanced efficiency, sustainability, and security. |
![]() |
Siemens XTRI-M Addressable Interface Module Installation Instructions Installation instructions and technical details for the Siemens XTRI-M Addressable Interface Module with Dual Isolators, covering wiring, programming, mounting, and electrical ratings for fire alarm systems. |