Vertiv™ Liebert® ITA2 UPS
5-40 kVA: Flexible power protection for Rack or Tower installation
Introduction
In today's dynamic world, basic power protection is not enough for enterprises. Business continuity is vital with digital trends constantly emerging. In your critical system, you cannot afford downtime or waste time recovering systems after a disruption. The Vertiv™ Liebert® ITA2 is a robust, highly-efficient, reliable UPS system which offers perennial, round-the-clock protection for diverse applications.
Our Solution
The Vertiv™ Liebert® ITA2 is a fully-digital, highly reliable, double-conversion UPS solution that provides clean and consistent power. This highly efficient solution is ideal for various deployments, including IT racks, network closets, automation control systems, and precision instruments to small sized control rooms among other edge applications.
- Cutting-edge design enables seamless integration into various ecosystems.
- Tailored for global deployment in a low carbon, compact footprint.
- The ultimate level of engineering and dynamics facilitate top-notch availability and excellent performance at low ownership costs, giving you ultimate peace of mind.
Application Areas
- Edge Networks
- Data Centers
- Automation industries
- Server Farms
- Workstations
- Telecom
Robust power protection solution in a compact package
Dust Resistant Moisture Resistant High Temp Proof High Durability Compatible w/ Vehicle
High Altitude Certified Seismic Certified Shipment Certified RoHS Certified Energy Star Certified
Key Features
- Robust structure with cutting edge channelized airflow design.
- Wide input voltage range, making it immune to grid interference.
- Rack-tower design for installation flexibility.
- Able to deliver both three-phase and single-phase output.
- 0.99 input power factor for better grid or generator compatibility.
- Powerful charging capability for minimum battery recharging time.
- Programmable output outlets/terminals with cascade protection to protect key devices during heavy load.
- Integrated communication port for remote monitoring.
- Easy to install, repair, and maintain.
- Compliance with seismic conduction and vehicle carrying test.
- Gravity sense LCD display.
- Turnkey dust-resistant design with ability to operate under high ambient temperature of up to 50 °C.
The Most Efficient UPS
Vertiv™ Liebert® ITA2 offers best-in-class efficiency of up to 96.5% in double conversion mode over a wide range of load conditions, resulting in significant OPEX cost savings. Liebert ITA2's integrated ECO mode of operation further enhances efficiency of up to 99%.
A line graph shows efficiency versus load. The 'Double Conversion Mode' line starts at approximately 94% efficiency at 25% load and rises to approximately 96.5% at 100% load. The 'ECO Mode' line starts at approximately 97% efficiency at 25% load and rises to approximately 99% at 100% load.
The Most Flexible UPS
Optimized modules minimize the amount of used space in the rack.
Support base makes it convenient and stable to place on a floor.
Adjustable display panel ensures readability and ease of use.
Fast, flexible and easy to deploy power output distribution options.
The flexible battery configurations such as VRLA and Lithium-ion external battery cabinets are designed to meet individual installation availability and back up time requirements.
Two images show battery cabinets: one labeled 'VRLA Battery Cabinet' and another labeled '2U Li-ion Battery Cabinet'.
Reliability in a compact footprint
- Fully-digital control with high output voltage precision.
- Manages all the nine power problems including sagging, spikes, and fluctuations.
- Built-in intelligent communication card for remote monitoring and management.
- Built-in power charger for fast charging reduces the battery charging time.
- Prolonged backup time through cascaded connection.
- Quality-tested for 1000 hours for extreme durability and tolerance even in stringent conditions.
High Availability
- Early Warning of UPS System Status: Multiple audible and visual alarms instantly alert for critical issues.
- Periodic Battery Testing: Provides automatic and manual self-diagnostic battery testing for peace of mind.
- Power-Factor Correction: Prevents noise, harmonics, and distortion from being transferred to connected loads or fed back to the utility.
- Lightning and Surge Protection: The transient voltage surge suppression circuitry inside the Liebert® ITA2 provides additional protection for the connected equipment.
- Wide Input Voltage Window: Prolongs battery life by allowing the UPS to maximize the use of utility power before being transferred to the battery when the input voltage exceeds the specified limits.
An image depicts a dust-resistant design with airflow.
More of What You Need: High Power Density
The Vertiv™ Liebert® ITA2 is designed with a high power factor in a small footprint. This increased power density maximizes the usable power to meet the needs of advanced IT operations.
A bar chart compares 'Liebert® ITA2' with 'Brand A' and 'Brand B' for 'Saves space'. Liebert® ITA2 shows a saving of 'Up to 35%' compared to Brand A and Brand B.
POD - Optional Accessories
The Liebert POD maintenance bypass and output distribution unit ensures continuous uptime when your critical system cannot afford any power loss without power, even for scheduled UPS maintenance.
It allows you to manually transfer connected equipment to utility power via a maintenance bypass switch, permitting scheduled service or UPS replacement without shutting down connected equipment.
A diagram shows a UPS, POD, and battery module configuration.
Lithium-ion Battery Compatibility
The Liebert® ITA2 is powered with the most powerful & intelligent battery charger that enables to integrate seamlessly with Safest Lithium Iron Phosphate (LFP) chemistry batteries.
Considering the benefits lithium-ion batteries provide over traditional battery deployments, users enjoy longer life, more cycles, and fewer replacements. They also benefit from the compact, smaller size, and lower weight. The higher operating temperature and lower maintenance add to the savings.
All these advantages directly impact IT facilities to drive an impressive total cost of ownership experience. Vertiv leverages its DNA in critical systems to deliver a lithium-ion battery system that is integrated seamlessly into the power chain.
Our capabilities and processes come together to ensure the UPS, batteries, monitoring, management service, and support offerings are orchestrated for delivering on customer expectations.
An image shows multiple Vertiv™ MPL Lithium ion Battery Cabinets with Liebert® ITA2 units.
Benefits of Lithium-ion Batteries
- Longer life: VRLA (2-3) vs LIB (60%).
- Weighs less: VRLA (10 LB) vs LIB (4 LB).
- More cycles: LEAD ACID (100%) vs LIB (500%).
- Saves space: VRLA (70%) vs LIB (30%).
- Saves cooling cost: VRLA (70%) vs LIB (30%).
Battery Management System
- Intelligent Batteries
- External Lead Acid
- Built-in LiB
Intelligent Communications
The Vertiv™ Liebert® ITA2 offers an intuitive control panel, network connectivity communications card, and optional software monitoring, all designed to ensure visibility, control, and peace of mind for manned or unmanned locations. You can even monitor key environmental and room conditions.
Vertiv™ Power Insight
Vertiv™ Power Insight is a web-based solution for managing and monitoring up to 100 Vertiv™ UPSs and rPDUs that provides a quick way to safely shutdown IT devices based on user-configured parameters. It helps improve availability and simplifies the monitoring and management of mission-critical IT equipment.
Additionally, if VMware™ is your virtualization platform of choice, you can benefit from the seamless integration offered by the Vertiv Power Insight vCenter Plugin. The vCenter Plugin provides single-pane-of-glass monitoring and management of UPS and rPDU infrastructure directly within the vCenter Management Platform.
It can also be configured to trigger automatic Virtual Machine (VM) shutdown or migration (using vMotion) based on alarms or events communicated by Vertiv Power Insight.
An image shows the Vertiv Power Insight dashboard interface.
Remote Diagnostic Services for Rapid Response
Data-Driven Insight: With Life Services, Vertiv experts continuously monitor and analyze all relevant control and operating parameters from your equipment to maintain optimum performance.
Real-time Response: Real-time data enables response to potential anomalies. Vertiv Life Services “sees” operating issues as soon as they occur, triggering immediate service action to prevent problems or cut hours or days off the time-to-repair, preventing or reducing downtime.
Connected Service: Vertiv service engineers can resolve many anomalies remotely and are connected to the Vertiv field service organization for on-site resolution. They can dispatch a field service engineer as soon as a critical condition is identified, often arming the engineer with a diagnosis so they arrive knowing the issue and with any required replacement parts.
A circular diagram illustrates 'LIFE™ SERVICES' with sections for 'Monitoring', 'Analysis & Diagnostics', and 'Response'.
Battery Backup Table (With VRLA)
The following tables provide battery backup times in minutes for various UPS models and battery module configurations using VRLA batteries.
UPS Model | Battery Modules | 5kVA | 4.5kVA | 4kVA | 3.5kVA | 3kVA | 2.5kVA | 2kVA | 1.5kVA | 1kVA | 0.5kVA |
---|---|---|---|---|---|---|---|---|---|---|---|
5kVA (Single phase UPS Models) | 1 | 6.8 | 7.8 | 9.2 | 11.2 | 13.9 | 17.9 | 24.3 | 35.6 | 58 | 122.4 |
2 | 18 | 20.9 | 24.6 | 29.7 | 36.5 | 46 | 59.7 | 81.7 | 126.4 | 278.8 | |
3 | 31.9 | 36.6 | 42.6 | 50.2 | 60.2 | 74.1 | 94.5 | 128.3 | 207 | 435.7 | |
4 | 46.3 | 52.6 | 60.3 | 70.2 | 83.5 | 102.2 | 130.3 | 182.7 | 287.6 | 592.5 | |
5 | 60.4 | 68.1 | 77.8 | 90.3 | 107 | 131.4 | 171.6 | 237.1 | 368.2 | 749.3 | |
6 | 74.4 | 83.7 | 95.4 | 110.4 | 131.5 | 164.6 | 212.9 | 291.5 | 448.8 | 906.1 | |
6kVA (Single phase UPS Models) | 1 | 5.1 | 6.1 | 7.1 | 8.6 | 10.8 | 13.9 | 19 | 28 | 46.9 | 101 |
2 | 14 | 16.1 | 19.1 | 23 | 28.6 | 36.5 | 48.4 | 67 | 103.9 | 228.2 | |
3 | 24.7 | 28.7 | 33.6 | 40 | 48.5 | 60.2 | 77.6 | 105.6 | 167.6 | 359.7 | |
4 | 36.7 | 42 | 48.7 | 57 | 68 | 83.5 | 106.9 | 147.8 | 235.1 | 491.2 | |
5 | 48.8 | 55.3 | 63.3 | 73.6 | 87.5 | 107 | 138.3 | 193.5 | 302.6 | 622.8 | |
6 | 60.5 | 68.2 | 77.9 | 90.4 | 107.1 | 131.5 | 172.9 | 239.1 | 370.1 | 754.3 | |
10kVA (Single phase UPS Models) | 2 | 4.8 | 5.5 | 7.4 | 10.2 | 14 | 18 | 24.6 | 36.5 | 59.7 | 126.4 |
3 | 8.8 | 10.2 | 13.6 | 18.5 | 24.7 | 31.9 | 42.6 | 60.2 | 94.5 | 207 | |
4 | 13.7 | 15.9 | 21.1 | 28.4 | 36.7 | 46.3 | 60.3 | 83.5 | 130.3 | 287.6 | |
5 | 19.4 | 22.4 | 29.7 | 39.3 | 48.8 | 60.4 | 77.8 | 107 | 171.6 | 368.2 | |
6 | 25.8 | 29.6 | 38.6 | 50.6 | 60.5 | 74.4 | 95.4 | 131.5 | 212.9 | 448.8 | |
16kVA (Three phase UPS Models) | 4 | 9.5 | 11 | 13 | 15.6 | 19.4 | 24.8 | 33.8 | 48.7 | 77.7 | 169.6 |
6 | 16.8 | 19.6 | 23.1 | 27.8 | 34 | 42.9 | 56.2 | 77.9 | 121.7 | 271.9 | |
8 | 25.3 | 29.3 | 34.4 | 40.8 | 49.2 | 60.7 | 78.1 | 107.3 | 173.2 | 374.1 | |
10 | 34.4 | 39.5 | 45.9 | 53.8 | 63.9 | 78.4 | 100.3 | 138.9 | 225.2 | 476.3 | |
12 | 43.6 | 49.7 | 57.2 | 66.5 | 78.7 | 96.1 | 122.4 | 173.7 | 277.2 | 578.6 | |
20kVA (Three phase UPS Models) | 4 | 6.9 | 8 | 9.5 | 11.5 | 14.3 | 18.3 | 24.8 | 36.7 | 60.3 | 130.3 |
6 | 12.3 | 14.3 | 16.8 | 20.4 | 25.3 | 32.3 | 42.9 | 60.5 | 95.4 | 212.9 | |
8 | 18.5 | 21.5 | 25.3 | 30.5 | 37.5 | 46.8 | 60.7 | 84 | 131.8 | 295.5 | |
10 | 25.3 | 29.3 | 34.4 | 41 | 49.7 | 61.1 | 78.4 | 107.6 | 173.4 | 378.1 | |
12 | 32.6 | 37.5 | 43.6 | 51.4 | 61.6 | 75.2 | 96.1 | 132.3 | 215.1 | 460.7 |
Note: Battery autonomy times and 5-year design life are based on operation at 25°C. Approximate autonomy times are based on fully charged batteries and can vary +/-5% due to battery manufacturing variances.
Battery Backup Table (With 192 V, 12 Ah Lithium-ion)
The following tables provide battery backup times in minutes for various UPS models and battery module configurations using 192 V, 12 Ah Lithium-ion batteries.
UPS Model | Battery Modules* | 5kVA | 4.5kVA | 4kVA | 3.5kVA | 3kVA | 2.5kVA | 2kVA | 1.5kVA | 1kVA | 0.5kVA |
---|---|---|---|---|---|---|---|---|---|---|---|
5 KVA (Single phase UPS Models) | 1 | 20 | 22 | 28 | 32 | 36 | 46 | 56 | 76 | 118 | 222 |
2 | 44 | 50 | 56 | 64 | 78 | 92 | 116 | 156 | 242 | 448 | |
3 | 68 | 76 | 88 | 100 | 118 | 144 | 178 | 240 | 364 | 674 | |
4 | 94 | 104 | 116 | 134 | 158 | 194 | 240 | 322 | 484 | 894 | |
5 | 118 | 132 | 144 | 168 | 198 | 244 | 302 | 404 | 604 | 1114 | |
6 | 142 | 160 | 172 | 202 | 238 | 294 | 364 | 486 | 724 | 1334 | |
6 KVA (Single phase UPS Models) | 1 | 16.0 | 18.0 | 20.6 | 26.0 | 30.0 | 36.0 | 47.9 | 63.0 | 98.3 | 185.0 |
2 | 36.0 | 41.0 | 46.9 | 53.0 | 60.0 | 78.0 | 95.8 | 129.0 | 201.7 | 373.3 | |
3 | 56.0 | 63.0 | 71.3 | 83.0 | 96.0 | 118.0 | 147.8 | 199.0 | 303.3 | 561.7 | |
4 | 78.0 | 86.0 | 97.5 | 111.0 | 130.0 | 158.0 | 197.8 | 267.0 | 403.3 | 745.0 | |
5 | 97.0 | 109.0 | 123.8 | 139.0 | 164.0 | 198.0 | 247.8 | 335.0 | 503.3 | 928.3 | |
6 | 117.0 | 132.0 | 150.0 | 167.0 | 198.0 | 238.0 | 297.8 | 403.0 | 603.3 | 1111.7 | |
10 KVA (Single phase UPS Models) | 1 | 10 | 11 | 14 | 16 | 18 | 23 | 28 | 38 | 59 | 111 |
2 | 22 | 25 | 28 | 32 | 39 | 46 | 58 | 78 | 121 | 224 | |
3 | 34 | 38 | 44 | 50 | 59 | 72 | 89 | 120 | 182 | 337 | |
4 | 47 | 52 | 58 | 67 | 79 | 97 | 120 | 161 | 242 | 447 | |
5 | 59 | 66 | 72 | 84 | 99 | 122 | 151 | 202 | 302 | 557 | |
6 | 71 | 80 | 86 | 101 | 119 | 147 | 182 | 243 | 362 | 667 | |
20 KVA (Three phase UPS Models) | 1 string | 10 | 11 | 14 | 16 | 18 | 23 | 28 | 38 | 59 | 111 |
2 string | 22 | 25 | 28 | 32 | 39 | 46 | 58 | 78 | 121 | 224 | |
3 string | 34 | 38 | 44 | 50 | 59 | 72 | 89 | 120 | 182 | 337 | |
4 string | 47 | 52 | 58 | 67 | 79 | 97 | 120 | 161 | 242 | 447 | |
5 string | 59 | 66 | 72 | 84 | 99 | 122 | 151 | 202 | 302 | 557 | |
6 string | 71 | 80 | 86 | 101 | 119 | 147 | 182 | 243 | 362 | 667 | |
30 KVA (Three phase UPS Models) | 2 string | 15 | 16 | 18 | 21 | 25 | 30 | 39 | 52 | 78 | 173 |
3 string | 22 | 25 | 28 | 32 | 38 | 47 | 59 | 81 | 120 | 260 | |
4 string | 30 | 34 | 38 | 43 | 52 | 63 | 79 | 109 | 161 | 345 | |
5 string | 38 | 43 | 48 | 55 | 66 | 78 | 99 | 137 | 202 | 430 | |
6 string | 47 | 52 | 59 | 67 | 80 | 93 | 119 | 165 | 243 | 515 | |
7 string | 56 | 62 | 70 | 79 | 94 | 109 | 139 | 193 | 284 | 600 |
Note: * 1 string equals to 2 battery cabinets.
Note: Backup times in the above tables have approximate values. They are based on new, fully charged batteries at a temperature of 77°F (25°C) with 100% resistive UPS loading. Different loading will change the actual backup times. Backup times listed may vary by ±5% due to manufacturing variances of the batteries.
Build Your Total Infrastructure Solution with Vertiv
Discover expert designed IT infrastructure solutions with proven success in diverse environments.
- Vertiv™ VE Rack: Self-contained 42U server rack designed to simplify equipment installation and provides an additional 6cm of useable depth.
- Software and IT Management: Monitor the entire system either locally or remotely to ensure you are alerted of out-of-range conditions that could result in costly downtime.
- Vertiv™ Liebert ITA2 UPS: Protect mission critical equipment in the event of power loss or extreme power fluctuations.
- Vertiv™ Geist™ rPDU: Reliable power distribution with outlet level remote monitoring and management providing the highest level of power visibility and control.
- Vertiv™ MPL: First and Only Lithium-Ion battery option for rack-mount 1-phase & 3-phase UPS that provides safe, reliable, and scalable backup power.
- Cable and Air Flow Management: Included accessories ensure proper cable management and airflow to keep your equipment cool.
- POD: Ensures safe and reliable power distribution function.
Vertiv™ Liebert® ITA2 UPS Specifications
5 | 6 | 8 | 10 | 16 | 20 | 30 | 40 | ||
---|---|---|---|---|---|---|---|---|---|
Nominal Ratings (kVA) | 5 | 6 | 8 | 10 | 16 | 20 | 30 | 40 | |
Long Backup Model | ITA-05k00AL1102P00 | ITA-06k00AL1102P00 | ITA-10k00ALA102P00 | ITA-16k00ALA102P00 | ITA-20k00AL3A02P00 | ITA-30k00AL3302P00 | ITA-40k00AL3302P00 | ||
Part Number | 01202670 | 01202671 | 01202672 | 01202682 | 01202683 | 01202660 | 01202897 | ||
Input Parameters | |||||||||
Nominal Input Voltage (V) | 220/230/240 VAC 1-Phase, 2 Wire | 220/230/240 VAC 1-Phase, 2 Wire; | 380/400/415 VAC 3-Phase, 4 Wire | ||||||
Input Voltage Range (V) | 176-288 VAC at full load; 100-176 VAC at linear derating; 100 VAC at half load | ||||||||
Nominal Input Frequency (Hz) | 50/60 | ||||||||
Input Power Factor (kW/KVA) | 0.99 | ||||||||
Current THD at Full Linear Load | <3% | ||||||||
Battery | |||||||||
Battery Blocks Per String | 5 | 8 | 13 | 24*, 30, 32, 34, 36, 38, 40 | |||||
Battery Charger Max. Power (A) | 5 | 8 | 13 | 24*, 30, 32, 34, 36, 38, 40 | |||||
External Battery Cabinet Option (VRLA) | P/C: ITA-BCI0020K01 (built-in battery module of 16 block X 12 V X 9 AH) Battery cabinet Dimensions in rack arrangement - 430 (W) x 750 (D) x 85 (H) | ||||||||
External Battery Cabinet Option (Li-ion) | P/C: ITA-BL10020KL2 (2U lithium ion battery module assembly - 192V/12Ah/1 cabinet ) Battery cabinet Dimensions in rack arrangement- 430 (W) x 680 (D) x 86 (H); Weight - 35 kg / cabinet | ||||||||
Output | |||||||||
Nominal Output Voltage (V) | 220/230/240 VAC (1-phase) | 220/230/240 VAC (1-Phase), 380/400/415 VAC (3-Phase) | |||||||
Nominal Output Frequency (Hz) | 50/60 | ||||||||
Rated Power Factor (kW/kVA) | Unity | ||||||||
Voltage Harmonic Distortion (%) | <2% for Linear loads & <5% for Non-linear loads | ||||||||
Overload Capacity @ at 25 °C | 105~125%, 10 min; 125~150%, 1 min; >150%, 200 ms | 105~125%, 10 min; 125~150%, 1 min; 150~200%, 5 s | |||||||
Efficiency | |||||||||
Online Mode Efficiency | Up to 95.5% | Up to 95.8% | Up to 96.2% | Up to 96.5% | |||||
ECO Mode Efficiency | Up to 99% | ||||||||
Dimensions and Weight | |||||||||
UPS Dimensions (W x D x H) in mm-Rack Mounted Arrangement | 430 x 480 x 85 | 430 x 590 x 85 | 430 x 600 x 130 | 430 x 730 x 130 | |||||
Weight (kg) | 11 | 15 | 23 | 23.5 | 30 | ||||
General | |||||||||
Noise at 1 m (dBA) | <55 | <58 | <60 | <63 | |||||
Operating Temperature (°C) | 0~50* | ||||||||
Relative Humidity (%RH) | 5~95, non-condensing | ||||||||
Altitude (m) | 3000 without derating | ||||||||
General and Safety Requirements for UPS | IEC 62040-1 | ||||||||
EMC Requirements for UPS | IEC 62040-2 | ||||||||
UPS Classification According to IEC 62040-3 | VFI-SS-111 | ||||||||
Environmental Aspects- Requirements and Reporting | IEC 62040-4 |
Note: *De-rating conditions apply ** 24-26-28-30 with de-rating (1) with ABS certification (2) Not Available in 30 & 40 kVA (3) Conditions apply (4) For 5-10 kVA, requires min 1 battery cabinet; For 16-20 KVA, requires min one group (2 battery cabinets); For 30 kVA, requires min two groups (4 battery cabinets); For 40 kVA, not available