Vertiv™ Liebert® APM2: High-Density, Efficient, and Scalable Power Solution

Technology-driven power solution for mission-critical facilities.

Highlights

The Vertiv Liebert APM2 UPS is an online, three-phase (in/out), 208/220V; 480V and 415V UPS, optimized with a flexible high-density design.

Key Benefits

Consider the Vertiv™ Liebert® APM2

The next-generation mid-size UPS for mission critical applications. Introducing the innovative Vertiv™ Liebert® APM2 Modular UPS, a flexible high-density solution designed for mission-critical applications in small, medium, and large data centers, including high performance compute (HPC), or commercial, light industrial, retail, telecommunications, and healthcare applications. Derived from the reliable Vertiv™ Liebert® EXM, the next-gen Vertiv Liebert APM2 builds on its proven track record and widespread usage in thousands of critical power sites.

The Vertiv Liebert APM2 UPS uses advanced three-level IGBT technology and Silicon Carbide converters to achieve a remarkable 97.5% peak efficiency, driving operational cost savings and reducing environmental impact. The modular and scalable construction provides optimized flexibility for capacity growth and is built with system redundancies to mitigate single points of failures.

Key Features:

Optimized for a Variety of Critical Power Applications

Vertiv™ Liebert® APM2 provides exceptional performance and reliability for critical power in data centers along with critical infrastructure in commercial and industrial settings.

Banking

Retail

Healthcare

Manufacturing and Light Industrial

Flexible and Optimized Design

Seamlessly Integrate Aesthetic Design into Your Infrastructure

Designed for Easy Service and Maintenance

Vertiv™ Liebert® APM2 is designed with front-access serviceability, which allows easy accessibility and a plug-and-play replacement experience thanks to the enhanced modular features, including power modules, bypass, controls, internal battery, and HMI, that provide an efficient and user-friendly process to minimize downtime and service labor.

Modular and Hot-swappable Design - Optimized Mean Time to Repair < 0.5h

Hot-swappable and modular architecture building blocks enable easy and fast on-site replacement, thus reducing MTTR. It is quick and easy to add, replace, or remove modular components and minimize downtime.

Internal modular battery modules in Vertiv Liebert APM2 (10-120kVA) are also hot-swappable, and easy to expand or replace, offered in both VRLA and Lithium-Ion.

Easy detection of power modules

Vertiv Liebert APM2 effortlessly detects newly added power modules, updates its configuration settings, and notifies the status at-a-glance through the LED light bar of the monitoring system.

Flexible Architectures

The innovative and flexible architecture of the Vertiv™ Liebert® APM2 reduces cost, improves management, and speeds up deployment. The modular architecture allows a single unit capacity to be scaled up to a maximum of 600 kW in one single unit and up to 2.4MW solution in parallel. There are three different product architectures available, each with a specific maximum cabinet capacity and feature set.

Vertiv™ Liebert® APM2 10-120 kW

Compatible with Lithium-Ion/VRLA internal modular batteries, External Modular VRLA, Standard VRLA, and Lithium-Ion Battery Cabinets.

Modular Lithium-Ion Internal Batteries

Modular VRLA Internal Batteries

Modular VRLA External Battery Cabinet

Vertiv™ Liebert® APM2 60-300 kW

Compatible with External standard VRLA and Lithium-Ion battery cabinets.

Vertiv™ Liebert® APM2 300-600 kW

Compatible with External standard VRLA and Lithium-Ion battery cabinets.

*IO Section includes Backfeed contactor (standard)

Flexible Configurations - Vertiv™ Liebert® APM2 at-a-glance

Vertiv™ Liebert® APM2 10-120kVA Vertiv™ Liebert® APM2 60-300kVA Vertiv™ Liebert® APM2 300-600kVA
Unit Capacity Range 10-120kVA 60-300kVA 300-600kVA
Ratings 208V/220V
480V/415V
208V/220V
480V/415V
N/A
300-600kVA
Hot Swappable Power Modules Size 15kVA (2U)
30kVA (2U)
30kVA (3U)
60kVA (3U)
60kVA (3U)
Wiring Configurations 208/220V 4W: 10-60kVA
480/415 3W/4W: 20-120kVA
30-150kVA
60-300kVA
N/A
60-600kVA
Internal Modular Batteries VRLA: Yes
Lithium-Ion: Yes
VRLA: No
Lithium-Ion: No
VRLA: No
Lithium-Ion: No
Power Module Redundancy N+1 Yes Yes Yes
Paralleling Yes Yes Yes
BMS Yes (1U) No-External Battery Cabinet No-External Battery Cabinet
Internal Maintenance Bypass Breakers Optional Optional No
DC Ground Fault Optional Optional Optional
Backfeed protection Yes Yes Yes
Dimensions (WxDxH) mm 600x1030x2000 600x1030x2000 1200x1030x2000
Ancillaries Maintenance Bypass Cabinet (MBC): Yes
MBC +UPS Width Dimensions (mm): 800mm-1600mm
Bypass Distribution Cabinet (BDC): Optional - distribution (≥250kVA), input (≥100kVA), output transformer (≥150kVA): 1200mm
Dual Input Transformer Cabinet: Yes (208V UPS)
Distribution Cabinet: Yes
Maintenance Bypass Cabinet (MBC): Yes
MBC +UPS Width Dimensions (mm): 900mm-1600mm
Bypass Distribution Cabinet (BDC): BDC (up to 150kVA 480V/208V out): No
Dual Input Transformer Cabinet: Yes- (≥100kVA 208V UPS)
Distribution Cabinet: Yes
Maintenance Bypass Cabinet (MBC): Yes
MBC +UPS Width Dimensions (mm): N/A
Bypass Distribution Cabinet (BDC): No
Dual Input Transformer Cabinet: Yes (≥250kVA 480V UPS)
Distribution Cabinet: No
External Battery Cabinet Standard VRLA: Yes
Modular VRLA: Yes
Lithium-Ion: Yes
Standard VRLA: Yes
Modular VRLA: No
Lithium-Ion: Yes
Standard VRLA: No
Modular VRLA: No
Lithium-Ion: Yes

Flexible Configurations and Deployment Options

Adapt and Scale with Ease

The flexible, scalable, redundant design of the Vertiv™ Liebert® APM2 UPS is available in many system configurations to provide optimal power protection.

GROW

FROM TO
10kW 208V Internal Batteries 60kW 208V Internal Batteries
60kW 208V Internal Batteries 150kW 208V Internal Batteries
30kW 480V Internal Batteries 120kW 480V Internal Batteries
120kW 480V Internal Batteries 300kW 480V Internal Batteries
300kW 480V Internal Batteries 600kW 480V Internal Batteries

Flexible Scalability Paths Meet Your Capacity/Redundancy Plans

Highly Available Fault Tolerant and Reliable Design

Scalability and Redundancy

The Vertiv™ Liebert® APM2 modular UPS design allows for quick and easy slide-in or out connection for capacity expansion or redundancy for both power and battery, thus reducing downtime and costs incurred. The advantage of this feature lies in its ability to enhance cost savings by leveraging existing equipment instead of investing in a new UPS system. Simply purchase a base factory-installed capacity to the current required capacity and install more capacity on-site within the limits of the product purchased.

The Vertiv Liebert APM2 10-120kW N+1 packs an entire UPS system, including power, maintenance bypass, and battery, into a single 600mm wide footprint, which provides at least 20% more power within its feature set compared to alternative products on the market. This new generation power module is our highest density solution, achieving 15kW/2U (208/220V) or 30kW/3U (480/415V). Modular battery runtimes can be achieved with 9Ah VRLA internal modular batteries with BMS and can be extended using an external matching modular battery cabinet. The product also includes an optional ultra-high density lithium battery module designed specifically for Vertiv Liebert APM2.

Similarly, Vertiv Liebert APM2 is offered at larger configurations, including 60-150kW 208/220V with 30kW/3U power modules and up to 120-600kW 480/415V with 60kW/3U power modules, with a variety of runtimes and energy storage technologies, including matching external VRLA or Lithium-Ion cabinet solutions.

Intelligent Paralleling

Increases in capacity and redundancy can be made within the unit through power module expansion and within a parallel system configuration up to 4 units, up to 2.4MW total system capacity. Integrated and redundant parallel and LBS communication ports provide a user-friendly and robust single-touch to initiate inverter ON/OFF for all parallel-connected UPS systems. The intelligent paralleling controls on Vertiv Liebert APM2 provide real-time controls and operation of the system that manages unit performance to provide peak efficiency operation by actively balancing power module and system capacities based on load variation to achieve greatest operating efficiencies.

Vertiv™ Liebert® APM2 Intelligent Paralleling 10-120kVA up to 4 units.

2 units at 30% load each = 97.2% efficiency.

Compact and Resilient Footprint

High Power Density

Thanks to the innovative design of the Vertiv™ Liebert® APM2 new generation power module, its three-level IGBT topology coupled with Silicon carbide (SiC) converters provides the highest power density (kVA/kW per U space), up to 100% from prior generation products. Vertiv Liebert APM2 is designed with the latest technology components to offer high-density 30kW(2U) and 60kW(3U) power module building blocks to achieve the most optimized power capacity footprint within the power ratings offered. Coupled with advancements in the battery solutions and technologies offered with Vertiv Liebert APM2, and the internal maintenance bypass feature option, this product provides superior density and space utilization which can be alternatively deployed for other revenue-generating equipment.

Saves footprint of up to 30-72%

Vertiv™ Liebert® APM2 10-120kW with modular internal Lithium-Ion Batteries – Saves Up to 72% space.

Saves footprint of up to 55%

Vertiv™ Liebert® APM2 is Compatible with Vertiv™ EnergyCore Li-Ion Battery Cabinet

Vertiv Liebert APM2 is designed to work efficiently with a variety of battery solutions, including the Vertiv™ EnergyCore battery system. Optimize efficiency and free up space by pairing it with the Vertiv EnergyCore Lithium-Ion battery system that fits your requirements. The Vertiv EnergyCore features a high-power density energy storage solution optimized at 250kW+ and arrives fully equipped to streamline deployment. Vertiv EnergyCore is the ultimate 5-minute EOL solution that removes the need for extra cabinets compared to other Lithium solutions in the market.

Lithium-ion Battery Compatibility

Considering the benefits lithium-ion batteries provide over traditional battery deployments, users enjoy longer life, more cycles, and fewer replacements. They also benefit from the compact, smaller size, and lower weight. Plus, the higher operating temperature and lower maintenance add to the savings.

All these advantages directly impact IT facilities to drive an impressive total cost of ownership experience.

Vertiv leverages its DNA in critical systems to deliver a lithium-ion battery system that is integrated seamlessly into the power chain.

Our capabilities and processes come together to provide the UPS, batteries, monitoring, management, service, and support offerings, orchestrated for delivering on our customer expectations.

Internal Modular Lithium-ion Battery Compatibility

High Energy Density

Simple and Easy

Smart and Flexible

Safety and Availability

[Note: This quick charging time does not include the battery cooling time after high power discharging]

Internal Lithium-Ion Battery Modules offer Superior Energy Density Compared to VRLA

Vertiv™ Liebert® APM2 10-120kW with modular internal Lithium-Ion batteries

Vertiv™ Liebert® APM2 10-120kW with modular internal VRLA batteries and Modular Battery Cabinet

Voltage Ratings Capacity (kVA/kW) Lithium-Ion Peak Runtime VRLA Batteries and Battery Cabinet
208V 60kW 20 mins 19.7 mins
480V 120kW 10 mins 7.8 mins

NOTE: Runtimes are given at power factor 1 with 100% load, beginning of life (BoL)

Vertiv™ Liebert® APM2 208V Internal Modular Battery Runtimes (Minutes)

VRLA

208V VRLA

Output Load (kW) / Battery Module Quantity 10 15 20 25 30 40 45 50 60 Installed Location
4 8.0 4.0 2.2 UPS
6 14.7 8.0 5.0 3.4 2.2
8 21.8 12.7 8.0 5.6 4.0 2.2 1.2
10 29.1 17.1 11.5 8.0 6.0 3.7 2.9 2.2
12 37.7 21.8 14.7 10.7 8.0 5.0 4.0 3.0 2.2
14 44.5 27.0 18.2 13.5 10.1 6.6 5.4 4.5 3.2
16 53.5 31.7 21.8 16.1 12.7 8.0 6.7 5.6 4.0
18 61.3 37.7 25.8 18.8 14.7 9.6 8.0 6.9 5.0
20 72.3 42.5 29.1 21.3 17.1 11.5 9.5 8.0 6.0
22 81.3 47.5 33.4 25.1 19.2 13.2 11.1 9.3 7.1
24 88.6 53.4 37.7 27.9 21.8 14.7 12.7 10.7 8.0
26 90.0 58.5 41.4 30.4 24.6 16.5 14.1 12.2 9.1
28 65.2 44.5 34.3 27.0 18.2 15.4 13.5 10.1
30 72.3 49.1 37.7 29.1 19.7 17.1 14.7 11.5 UPS & Modular Cabinet 600mm
32 78.4 53.4 40.7 31.7 21.8 18.5 16.1 12.7
34 83.9 57.3 43.3 34.9 23.9 19.8 17.5 13.7
36 88.7 61.3 46.2 37.7 25.8 21.8 18.8 14.7
38 90.0 67.1 50.0 40.2 27.5 23.7 19.9 15.8
40 72.3 53.4 42.5 29.1 25.4 21.8 17.1
42 77.0 56.6 44.5 30.9 27.0 23.5 18.2
44 81.2 59.4 47.5 33.4 28.4 25.1 19.2
46 85.1 63.7 50.6 35.6 29.7 26.5 20.2
48 88.7 68.2 53.4 37.7 31.7 27.9 21.8

NOTE: Runtimes are given at power factor 1 with 100% load, beginning of life (BoL)

Lithium-Ion

208V Lithium-Ion

Output Load (kW) / Battery Module Quantity 10 15 20 25 30 40 45 50 60 Installed Location
1 15.0 10.0 7.2 5.2 3.8 UPS
2 30.0 20.0 15.0 12.0 10.0 7.2 6.0 6.0 3.8
3 45.0 30.0 22.0 18.0 15.0 11.0 10.0 10.0 7.2
4 60.0 40.0 30.0 24.0 20.0 15.0 13.0 13.0 10.0
5 75.0 50.0 36.0 30.0 25.0 18.0 16.0 16.0 12.0
6 90.0 60.0 45.0 36.0 30.0 22.0 20.0 20.0 15.0
7 105.0 70.0 51.0 42.0 35.0 26.0 24.0 24.0 17.0
8 120.0 80.0 60.0 48.0 40.0 30.0 26.0 26.0 20.0

Vertiv™ Liebert® APM2 480V Internal Modular Battery Runtimes (Minutes)

VRLA

480V VRLA

Output Load (kW) / Battery Module Quantity 20 30 40 50 60 80 90 100 120 Installed Location
4 2.4 UPS
8 8.5 4.3 2.4
12 15.3 8.5 5.3 3.6 2.4
16 22.9 13.3 8.5 5.9 4.3 2.4 1.5
20 30.0 17.8 12.1 8.5 6.4 3.8 3.1 2.4
24 39.2 22.9 15.3 11.3 8.5 5.3 4.3 3.6 2.4
28 46.4 28.0 18.9 14.1 10.8 6.9 5.7 4.7 3.4 UPS & Modular Cabinet 600mm
32 55.5 33.4 22.9 16.9 13.3 8.5 7.1 5.9 4.3
36 64.8 39.2 26.9 19.5 15.3 10.0 8.5 7.2 5.3
40 75.4 43.8 30.0 22.9 17.8 12.1 9.9 8.5 6.4
44 84.0 49.7 35.0 26.1 19.9 13.8 11.7 9.7 7.4
48 90.0 55.5 39.2 28.8 22.9 15.3 13.3 11.3 8.5

NOTE: Runtimes are given at power factor 1 with 100% load, beginning of life (BoL)

Lithium-Ion

480V Lithium-Ion

Output Load (kW) / Battery Module Quantity 20 30 40 50 60 80 90 100 120 Installed Location
2 15.0 10.0 7.2 5.2 3.8 UPS
4 30.0 20.0 15.0 12.0 10.0 7.2 6.0 5.2 3.8
6 45.0 30.0 22.0 18.0 15.0 11.0 10.0 9.0 7.2
8 60.0 40.0 30.0 24.0 20.0 15.0 13.0 12.0 10.0

NOTE: Runtimes are given at power factor 1 with 100% load, beginning of life (BoL)

Provides Optimum Performance with Maximum Efficiency

Vertiv™ Liebert® APM2 delivers an exceptional Double conversion efficiency of up to 97.5%, which further increases up to 98.8% with the Dynamic online mode, consequently reducing operating costs and energy dissipation (kW) to a minimum. Dynamic online mode also supports in parallel operation, this significantly minimizes the consumption of the cooling system, providing an overall TCO reduction and rapid payback time.

Furthermore, the Vertiv Liebert APM2 can optimize efficiency at partial load, thereby attaining additional cost savings through the intelligent paralleling feature. The efficiency and electricity cost savings of Vertiv Liebert APM2 can be attributed to:

The seamless activation of Vertiv Liebert APM2's functioning modes provides the highest level of efficiency without compromising power quality and availability. The Dynamic online mode provides Class 1* output performance under most stringent conditions:

The unit discriminates between various interferences and responds rapidly, meanwhile also provides compatibility with downstream equipment (such as Transformers, STS, mechanical loads, etc.).

Matching System Ancillary Suite Provides an Optimized UPS Solution

The Vertiv™ Liebert® APM2 UPS includes optional OEM matching ancillary cabinet products to provide the ultimate line-in-match solutions to optimize the overall UPS system, integration, and performance.

External Battery Cabinets (EBC)

The flexible battery configurations of the Vertiv Liebert APM2 provide a superior range of optimized energy solutions to meet various applications and user requirements.

Vertiv Liebert APM2 is compatible with numerous battery configurations, including internal modular solutions (VRLA/Lithium-Ion), modular VRLA cabinet (10-120kVA), traditional VRLA external battery cabinets, and premium Lithium-Ion cabinet technologies.

Standard VRLA EBC (600,880,1200mm)

Modular VRLA Battery Cabinet 10-120kVA

Vertiv™ Liebert® EnergyCore Lithium-Ion

Bypass Distribution Cabinet (BDC)

The Vertiv Liebert APM2 BDC is one of the most flexible and optimized maintenance bypass solutions on the market. The Vertiv Liebert APM2 BDC has been further enhanced to include optional input or output transformers, subfeed or panelboard distribution, and a three-breaker bypass with optional solenoid key released unit (SKRU). Configurations include up to 100kVA input or 150kVA output transformers and distribution or up to 250kVA.

Bypass Distribution Cabinet (600mm W)

SKRU

Bypass Breakers

Panelboard or Subfeeds

Vertiv™ VR Racks

BDC

Vertiv™ Liebert® APM2

Vertiv™ Liebert® Energy Core

Maintenance Bypass Cabinet (MBC) - Various sizes available

The Maintenance Bypass Cabinet ancillary provides a factory line-in-match wrap-around bypass OEM solution that can be attached to the UPS for close-coupling. The MBC is designed with varying sizes ranging from 200-800mm for Vertiv™ Liebert® APM2 to provide solutions for ratings up to 300kVA and can be configured in Three (3) or Four (4) breaker configurations. The MBC allows for transfer of connected loads to an alternate power path, allowing full isolation of the UPS. The UPS can then be turned “OFF” and removed from service with no interruption of power to connected loads.

300mm

600mm

Vertiv™ VR Racks

MBC

Vertiv™ Liebert® APM2

Vertiv™ Liebert® Energy Core

Maintenance Bypass Cabinet

Powering Critical Cooling Equipment

The Vertiv Liebert APM2 provides robust performance features and technologies that enable compatibility to supply power backup for critical liquid cooling equipment, including the Vertiv™ Liebert® XDU and Vertiv™ Liebert® XDM liquid cooling products used for liquid cooling of high-performance compute (HPC) applications. Vertiv Liebert APM2, with its modular and compact high-density architecture, wide range of capacities and operating voltages, and battery technologies, makes this a leading product on the market in this application. Please consult with Vertiv technical support for sizing and equipment verification.

Illustration of liquid cooling high-density compute row

User Interface and Advanced Diagnostic

Intuitive to use

Consistent with other Vertiv touchscreens

Customer Configurable data & views

Status-At-A Glance LED light bar

Multiple screen colors available

Vertiv™ Liebert® APM2 makes your mission critical space a peaceful place through its advanced diagnostic capability, measuring and logging, enhanced event analysis, as well as an intelligent colored multi-language touch screen display.

Vertiv Liebert APM2 advanced DSP control platform, together with the Vector Control technology, enables increased performance of the three-level power converters and real-time control of output power quality, guaranteeing continuous operation and premium protection for your business.

65kA Short-circuit Withstand Capacity

The Vertiv Liebert APM2 product architecture features a robust withstand short circuit protection of 65kA.

Vertiv Liebert APM2 includes a standard 65kA withstand rating to clear short circuit capacity and provide protection of the SCRs against short circuits or overloads, which protects the equipment and the safety of operation during a fault interruption.

KAIC fuses

Flexible Monitoring and Management Options

Hardware Connectivity

Vertiv™ Liebert® APM2 allows for the monitoring and control of networked UPS through different protocol options. The integration of UPS with network management systems, via SNMP protocol, and building management systems, via MODBUS TCP/RTU and BACnet MSTP/IP. As an option, environmental sensors can also be attached to the UPS via a monitoring card. The integration with synoptic panels via a dry contact board.

Software

Vertiv connects and protects your network with core-to-edge solutions and unmatched expertise. For maximum visibility and effective monitoring in one view, pair your Vertiv™ UPS with a software solution.

Vertiv™ Environet™ Alert

Vertiv™ Environet™ Alert provides industrial companies with critical facility monitoring software that is affordable and easy to use. This solution delivers superior monitoring, alerting, trending, and data organization. Get monitoring, alerting, and trending at a price that's right for your business.

Vertiv™ Life™ Services Remote Diagnostic and Preventive Monitoring

Vertiv's service program is designed to provide that your critical power protection system is maintained in an optimum state of readiness at all times.

Vertiv™ Life™ Services provides continuous insight into critical equipment operation to improve performance, streamline service processes for faster issue resolution, and add deep equipment and service expertise to any organization without overhead.

With Vertiv Life Services you will benefit from:

Technical Specifications 208/220V

Vertiv™ Liebert® APM2 10-60 kW

Vertiv™ Liebert® APM2 60-150 kW

10, 15, 20,25,30,40,45,50,60 60,75,80,90,100,120,140,150
Ratings
Input
Power Module Capacity 15kW/kVA 30kW/kVA
Nominal input voltage 208/220V (3-phase 3-wire + N + PE) 208/220V (3-phase 3-wire + N + PE)
Input voltage range without battery discharge* 125-249V 125-249V
Nominal input frequency 50/60 Hz 50/60 Hz
Input frequency range 40 to 70 Hz 40 to 70 Hz
Input power factor at full load 0.99 0.99
Current THD at full linear load* < 3% < 3%
Bypass voltage tolerance Upper limit: +10%,15%,or+20% Vac Default: +15% Vac
Lower limit: -10%,-15%, -20%,-30%, or -40% Vac Default: -20% Vac
Upper limit: +10%,15%,or+20% Vac Default: +15% Vac
Lower limit: -10%,-15%, -20%,-30%, or -40% Vac Default: -20% Vac
Bypass frequency tolerance ±10% ±10%
Battery
Internal Battery Modular VRLA or Lithium Ion Modular VRLA or Lithium Ion
External Battery VRLA, Lithium VRLA, Lithium
Battery Bus voltage 192-288v (16~24 jars) 192-288v (16~24 jars)
Voltage temperature compensation -3.0 mV/°C/Cell (selectable 0 to 5.0 at 25°C) -3.0 mV/°C/Cell (selectable 0 to 5.0 at 25°C)
Battery charger max. current* 140 A 600 A
Output
Nominal output voltage 208/220V (3-phase 3-wire + N + PE) 208/220V (3-phase 3-wire + N + PE)
Nominal output frequency 50/60 Hz 50/60 Hz
Output power factor Unity Unity
THDv at full linear load ≤ 1% ≤ 1%
Inverter overload capacity* ≤ 105% Continuous; 105% to 125% for 10 min; 125% to 150% for 1 min; >150% for 200 ms ≤ 105% Continuous; 105% to 125% for 10 min; 125% to 150% for 1 min; >150% for 200 ms
Double conversion efficiency Up to 98.4% Up to 98%
ECO mode efficiency Up to 98% Up to 95.7%
Dynamic Online Up to 98.8% Up to 97%
Dimensions and Weight
Frame Dimensions (W x D x H) mm 600 x 1030 x 2000 mm 600 x 1030 x 2000 mm
UPS Weight (kg) (no power modules) 328 kg 332k
Power Module (W x D x H) mm 440 x 510 x 87 mm 440 x 630 x 130 mm
Power Module Weight (kg) 26..4 kg 35.5 kg
Battery Module VRLA (W x D x H) mm 230 x 730 x 87 mm 230 x 730 x 87 mm
Battery Module Weight (Kg) 35.5kg 36 Kg
Battery Module Li-Ion (W x D x H) mm 796 x 440 x 87 796 x 440 x 87
Battery Module Li-Ion Weight (Kg) 36 Kg 36 Kg
General
Noise within 1 m (no fan) ≤ 65 dB ≤ 65 dB
Maximum altitude <1500 m without derating (compliant with IEC/EN 62040-3 at altitudes exceeding 1500m) <1500 m without derating (compliant with IEC/EN 62040-3 at altitudes exceeding 1500m)
Operating Temperature 32°F to 122°F (0°C to 50°C)*C with automatic derating >40°C 32°F to 122°F (0°C to 50°C)*C with automatic derating >40°C
Relative Humidity 0% to 95%, non-condensing 0% to 95%, non-condensing
Protection level IEC (60529) IP20 IP20
General and safety requirements for UPS UL 1778 5th Edition; CSA 22.2 NO 107.3 UL 1778 5th Edition; CSA 22.2 NO 107.3
EMC requirements for UPS IEC 62040-2; FCC Part 15, Class A IEC 62040-2; FCC Part 15, Class A
Transportation ISTA Procedure 3B ISTA Procedure 3B

Specifications are subject to change without any further notification.

Technical Specifications 480/415/400V

Models (kVA/kW) Vertiv™ Liebert® APM2 20-120 kW Vertiv™ Liebert® APM2 120-300 kW Vertiv™ Liebert® APM2 300-600 kW
20,30,40,50,60,80,90,100,120 120,150,180,200,225,250,300 300,360,400,420,480,500,540,600
Ratings
Input
Power Module Capacity 30kW/kVA 60kW/kVA 60kW/kVA
Nominal input voltage 380/400/415/480 V (3-phase 3-wire + N + PE); 480V (3-phase 3-wire+PE)
Input voltage range without battery discharge* 380/400/415V: 228~478V; 480V: 288~528V 380/400/415V: 228~478V; 480V: 288~528V 380/400/415V: 228~478V; 480V: 288~528V
Nominal input frequency 50/60 Hz 50/60 Hz 50/60 Hz
Input frequency range 40 to 70 Hz 40 to 70 Hz 40 to 70 Hz
Input power factor at full load 0.99 0.99 0.99
Current THD at full linear load* ≤ 3% ≤ 3% ≤ 3%
Bypass voltage tolerance For 380V/400V/415V models,
Upper limit selections: +10%, +15%, +20%; default +15%.
Lower limit selections: -10%, -15%, -20%, -30%, -40%; default -20%.
For 480V models,
Upper limit selections: +10%.
Lower limit selections: -10%, -15%; default -10%.
For 380V/400V/415V models,
Upper limit selections: +10%, +15%, +20%; default +15%.
Lower limit selections: -10%, -15%, -20%, -30%, -40%; default -20%.
For 480V models,
Upper limit selections: +10%.
Lower limit selections: -10%, -15%; default -10%.
For 380V/400V/415V models,
Upper limit selections: +10%, +15%, +20%; default +15%.
Lower limit selections: -10%, -15%, -20%, -30%, -40%; default -20%.
For 480V models,
Upper limit selections: +10%.
Lower limit selections: -10%, -15%; default -10%.
Bypass frequency tolerance ±10% ±10% ±10%
Battery
Internal Battery Modular VRLA or Lithium-Ion Modular VRLA or Lithium-Ion External Battery Only
External Battery VRLA, Lithium Ion, Nickel Zinc VRLA, Lithium Ion, Nickel Zinc VRLA, Lithium Ion, Nickel Zinc
Battery Bus voltage 384-528V (32~44 jars) 384-528V (32~44 jars) 360-600V (30~50 jars)
Voltage temperature compensation -3.0 mV/°C/Cell -3.0 mV/°C/Cell -3.0 mV/°C/Cell
Battery charger max. current* 140 A 600 A 1200 A
Output
Nominal output voltage 380/400/415/480 V (3-phase 3-wire + N + PE); 480V (3-phase 3-wire+PE)
Nominal output frequency 50/60 Hz 50/60 Hz 50/60 Hz
Output power factor Unity Unity Unity
THDv at full linear load ≤ 1% ≤ 1% ≤ 1%
Inverter overload capacity* ≤ 105% Continuous; 105% to 125% for 10 min; 125% to 150% for 1 min; 150% to 200% for 200 ms ≤ 105% Continuous; 105% to 125% for 10 min; 125% to 150% for 1 min; 150% to 200% for 200 ms ≤ 105% Continuous; 105% to 125% for 10 min; 125% to 150% for 1 min; 150% to 200% for 200 ms
Double conversion efficiency Up to 97% Up to 98% Up to 97.5%
ECO mode efficiency Up to 98% Up to 97% Up to 99.5%
Dynamic Online Up to 98.8% Up to 97.5% Up to 99.2%
Dimensions and Weight
UPS Dimensions (W x D x H), mm 600 x 1030 x 2000 mm 600 x 1030 x 2000 mm 1200 x 1030 x 2000 mm
UPS Weight (kg) (no power modules) 328 kg 332kg 638.5kg
Power Module Dimensions (W x D x H), mm 440 x 518 x 87 mm 440 x 630 x 130 mm 440 x 630 x 130 mm
Power Module Weight (kg) 26.4 kg 35.5 kg 35.5 kg
Battery Module VRLA (W x D x H) mm 230 x 730 x 87 mm 230 x 730 x 87 mm 230 x 730 x 87 mm
Battery Module Weight (Kg) 30kg 30kg 30kg
Battery Module Li-Ion (W x D x H) mm 796 x 440 x 87 796 x 440 x 87 796 x 440 x 87
Battery Module Li-Ion Weight (Kg) 36 Kg 36 Kg 36 Kg
General
Noise within 1 m (no fan) ≤ 65 dB ≤ 70dB ≤ 70dB
Maximum altitude <1500 m without derating (compliant with IEC/EN 62040-3 at altitudes exceeding 1500m) <1500 m without derating (compliant with IEC/EN 62040-3 at altitudes exceeding 1500m) <1500 m without derating (compliant with IEC/EN 62040-3 at altitudes exceeding 1500m)
Operating Temperature 32°F to 122°F (0°C to 50°C)*C with automatic derating >40°C 32°F to 122°F (0°C to 50°C)*C with automatic derating >40°C 32°F to 122°F (0°C to 50°C)*C with automatic derating >40°C
Relative Humidity 0% to 95%, non-condensing 0% to 95%, non-condensing 0% to 95%, non-condensing
Protection level IEC (60529) IP20 IP20 IP20
General and safety requirements for UPS UL 1778 5th Edition; CSA 22.2 NO 107.3 UL 1778 5th Edition; CSA 22.2 NO 107.3 UL 1778 5th Edition; CSA 22.2 NO 107.3
EMC requirements for UPS IEC 62040-2; FCC Part 15, Class A IEC 62040-2; FCC Part 15, Class A IEC 62040-2; FCC Part 15, Class A
Transportation ISTA Procedure 3B ISTA Procedure 3B ISTA Procedure 3B

Specifications are subject to change without any further notification.

PDF preview unavailable. Download the PDF instead.

vertiv-liebert-apm2-10-600kw-brochure-sl-71311 Adobe PDF Library 17.0 Adobe InDesign 20.5 (Windows)

Related Documents

Preview Vertiv™ PowerUPS 9000: High-Performance UPS for Critical Infrastructure
Discover the Vertiv™ PowerUPS 9000, a high-performance, modular, and efficient Uninterruptible Power Supply (UPS) designed for data centers and critical infrastructure. Learn about its AI readiness, reduced TCO, and global support.
Preview Vertiv Liebert ITA2 UPS: 5-40 kVA Flexible Power Protection
Explore the Vertiv Liebert ITA2 UPS, a robust, highly-efficient, and reliable double-conversion UPS system designed for flexible power protection in rack or tower installations. Ideal for edge networks, data centers, and critical IT environments, it ensures business continuity with advanced features and high availability.
Preview Vertiv Liebert GXT5 UPS: 5-20 kVA Intelligent & Efficient Power Protection
Explore the Vertiv Liebert GXT5 UPS series (5-20 kVA, 230V), offering advanced online double-conversion power protection. Learn about its high efficiency, compact design, parallel operation, extensive features, and comprehensive service options for data centers and critical IT infrastructure.
Preview Vertiv Trinergy UPS: High-Performance, Reliable Power Solutions for Data Centers
Explore the Vertiv Trinergy UPS, a cutting-edge system offering exceptional reliability, efficiency, and modularity for critical data center infrastructure. Learn about its advanced features, including AI load management, dynamic grid support, and comprehensive global support.
Preview Vertiv PowerUPS 9000: High-Performance UPS for Critical Infrastructure
Discover the Vertiv PowerUPS 9000, a high-performance, modular, resilient, and efficient Uninterruptible Power Supply (UPS) system designed for modern data centers and mission-critical applications. Learn about its advanced features, reliability, efficiency, and global support.
Preview Vertiv Liebert ITA2 UPS: Flexible Power Protection for Rack or Tower Installation
Discover the Vertiv Liebert ITA2 UPS, a reliable, double-conversion UPS system offering clean and consistent power for diverse applications. Learn about its features, benefits, and specifications for flexible power protection.
Preview Vertiv Liebert GXT5 UPS: Intelligent and Efficient Power Protection
Explore the Vertiv Liebert GXT5 UPS, a high-efficiency online double conversion solution providing robust power protection for mission-critical applications. Learn about its advanced features, scalability, and comprehensive service options.
Preview Vertiv Liebert GXT5 UPS: 15-20kVA Power Protection for Mission-Critical Applications
Explore the Vertiv Liebert GXT5 UPS series, offering 15-20kVA of intelligent, efficient, and reliable power protection for mission-critical applications. Features include online double conversion, unity power factor, high efficiency, and advanced management capabilities.