Zone 2 Control & Monitoring Panels

Zone 2 Control, Monitoring and Power Distribution Panels

Product Overview

The Raychem Zone 2 Control, Monitoring and Power Distribution panels are configurable Electric Heat-Tracing (EHT) panels that are ATEX and IECEx approved. The enclosure and all components are Zone 2 approved, including the Circuit Breakers, Raychem controllers and Solid-State Relays used for switching the heat-tracing circuits. The panels meet the IEC/EN 61439 and 60079 series standards and are designed, manufactured, tested & Zone 2 certified.

The Control, Monitoring and Power Distribution solution can consist out of a combination of various panels mounted on a skid. The enclosures on the skid can be configured in different ways:

  • Control & Monitoring
  • Power Distribution
  • Combination of Control, Monitoring and Power Distribution in the same enclosure

Each panel on the skid has its own approval and will be configured separately via the configuration string as described in the datasheet.

A photograph shows several industrial control panels mounted on a skid, representing a combination of control, monitoring, and power distribution units. Certifications include [ATEX certification] and [IECEx certification], with a [Patented] mark.

Panel type (cm)Controllers / Maximum circuits (NGC-40)Controllers / Maximum circuits (NGC-30)Controllers / Maximum circuits (Elexant 4020i)
Control (60 x 60 x 30)6 circuits5 circuits-
Control (107 x 93 x 32)18 circuits20 circuits-
Control & Power Distribution combined (75 x 50 x 21)--2 circuits
Control and Power Distribution combined (107 x 93 x 32)6 circuits, 6 RCBO 32A, 30mA--
Power Distribution (107 x 93 x 32)18 RCBO's 32A, 30mA--

Product Specifications (Zone 2 panel)

  • Ingress Protection: IP66
  • Minimum ambient operating temperature (Control panel): -55°C
  • Ambient storage temperature (Control panel): -55°C to +70°C
  • Minimum ambient operating temperature (Power Distribution Panel): -20°C
  • Ambient storage temperature: -20°C to +70°C
  • Max. altitude: 2000 m
  • Humidity: 5-90% non-condensing
  • Controller types: NGC-40 (mix of NGC-40-HTC / HTC3 / IO / SLIM modules), NGC-30 (mix of NGC-30-CRMS, NGC-30-CTM / NGC-30-CVM boards), Elexant 4020i (all versions of available Elexant 4020i controllers), Other electronics upon request and validation.
  • Gland entries: The Zone 2 panels can be delivered with predrilled holes and glands when specified during the ordering process. If holes need to be drilled onsite, special instructions of safe use shall be applied.

Panel Configuration String

The configuration for the Zone 2 panel is represented by a configuration string, and the parameters in the string define the content of the panel. Any comments can be added to the string or discussed with the sales representative.

Config string parameterValues
Type of panelNGC30: NGC-30, NGC40: NGC-40, E4020i: Elexant 4020i
Electrical standardE: IEC
Area classSAFE: Safe Area, ZONE2: Zone 2
Panel size (# of circuits)0-40
EnclosureSS: Stainless Steel (IP66), SW: Stainless Steel with Window (IP66), AL: Aluminium
Control voltage (L-N)230: 230 Vac, 400: 400 Vac
Power distributionPDY: Power distribution included, PDN: No power distribution included
MCB/Load switchLS180: Load Switch 180 Amp, MCB160: MCCB 160A, 10kA
HeatedHTN: Panel not heated, HTY: Panel heated via patented heating system
CNTRLCNTRL: Control, PD: Power Distribution, PD/CNTRL: Power Distribution and Control
Number of circuits0-40
Circuit breaker typeRCBO/2P20C: circuit breaker with earth leakage protection, 2 Pole, 20 Amps, type C, RCBO/2P25C: circuit breaker with earth leakage protection, 2 Pole, 25 Amps, type C, RCBO/2P32C: circuit breaker with earth leakage protection, 2 Pole, 32 Amps, type C
Module type4020iMOD: 4020i-Mod, 4020iModIS: 4020i-Mod-IS, 4020iModISLIM: 4020i-Mod-IS-LIM, 4020iMod3P: 4020i-Mod-3P, 4020iMod3PIS: 4020i-Mod-3P-IS, 4020iModISPROF: 4020i-Mod-IS-PRF, 4020iModISLIMPRF: 4020i-Mod-IS-LIM-PRF, 4020iMod3PISPRF: 4020i-Mod-3P-IS-PRF, NGC40HTC: NGC-40-HTC, NGC40-HTC3: NGC-40-HTC3, NGC40-IO: NGC-40-IO (*1), NGC30CRM: NGC-30-CRM, NGC30-CRMS: NGC-30-CRMS, NGC20CE: NGC-20-C-E, NGC-20CLE: NGC-20-CL-E, NGC-40SLIM: NGC-40-SLIM, NGC30CTM: NGC-30-CTM, NGC30CVM: NGC-30-CVM
Additional module(List of NGC modules)
Poles1, 2, 3
Phase selectionLN: L-N, LL: L-L, L1L2L3: L1-L2-L3, L1L2L3N: L1-L2-L3-N
Type of relay and ratingSS3EX: 32A 277 Vac, 6 mm² cable, SS3ZEX: 32A 277 Vac, 6 mm² cable, Low Smoke Zero Halogen, SS3LEX: 32A 277 Vac, 10 mm² cable, SS3LZEX: 32A 277 Vac, 10 mm² cable, Low Smoke Zero Halogen, SS3REX: 32A 277 Vac, high in-rush, 6 mm² cable, SS3RZEX: 32A 277 Vac, high in-rush, 6 mm² cable, Low Smoke Zero Halogen, SS3RLEX: 32A 277 Vac, high in-rush, 10 mm² cable, SS3RLZEX: 32A 277 Vac, high in-rush, 10 mm² cable, Low Smoke Zero Halogen, SSH3EX: 32A 690 Vac, 6 mm² cable, SSH3ZEX: 32A 690 Vac, 6 mm² cable Low Smoke Zero Halogen, SSH3LEX: 32A 690 Vac, 10 mm² cable, SSH3LZEX: 32A 690 Vac, 10 mm² cable Low Smoke Zero Halogen, SSH6LEX: 63A 690 Vac, 10 mm², SSH6LZEX: 63A 690 Vac, 10 mm² cable Low Smoke Zero Halogen, 3SSR-SS3: Heated, 32A 277 Vac, 3SSR-SS3R: Heated, 32A 277 Vac, High inrush, 3SSR-SSH3: Heated, 32A 690 Vac
SkidYes, No
TransformerTransYes: Transformer included, TransNo: No Transformer
General optionsT1500: TOUCH 1500-EX, UIT: NGC-UIT3-EX, W800: Wireless 868 MHz, W2400: Wireless 2.4 GHz, Ant: Omni Antenna for wireless, AL: Alarm Lights (power / control alarm), AR: Alarm Relay (power / control alarm), RMM3, RMM2-DI.
Comment boxFree format text

Examples:

NGC40-E-ZONE2-18-SS-230- PDN-HTN-CNTRL-18-NGC40HTC-1-LN-SS3REX-T1500-AR-AL

  • NGC-40 panel, Zone 2, 18 circuits: Stainless steel, Phase-Neutral = 230 Vac, No power distribution, Non heated.
  • Circuit Configuration: 18 circuits NGC-40-HTC, 1 pole switching Line-Neutral, Solid state relay 32 Amp switching high inrush.
  • TOUCH 1500 user interface, Alarm relays, Alarm lights.

NGC40-E-ZONE2-15-SS-230- PDN-HTN-CNTRL-12-NGC40HTC-1-LN-SS3REX-3-NGC40HTC3-2-LL-SS3REX-AR-AL

  • NGC-40 panel, Zone 2, 15 circuits: Stainless steel, Phase-Neutral = 230 Vac, No power distribution, Non heated.
  • Circuit Configuration: 12 circuits NGC-40-HTC, 1 pole switching Line-Neutral, Solid state relay 32 Amp switching high inrush. 3 circuits NGC-40-HTC3, 2 pole switching Line-Line, Solid state relay 32 Amp switching high inrush.
  • Alarm relays, Alarm lights.

NGC40-E-ZONE2-13-SS-230-PDN-HTY-CNTRL-10-NGC40HTC-1-LN-HSS3EX-3-NGC40HTC3-3-LLL-HSS3EX-W24-ANT-AL-AR

  • NGC-40 panel, Zone 2, 13 circuits: Stainless steel, Phase-Neutral = 230 Vac, No power distribution, Heated.
  • Circuit Configuration: 10 circuits NGC-40-HTC, 1 pole switching Line-Neutral, Solid State relay 32 Amp switching. 3 circuits NGC-40-HTC3, 3 poles switching, L1-L2-L3, Solid State relay 32 Amp, Wireless radio 2.4 GHz, Alarm lights, Alarm relays, TOUCH 1500.
  • Wireless radio 2.4 GHz, Antenna, Alarm Lights, Alarm Relays.

Panel Configuration Summary

#1 Type of Panel#2 Electrical Standard#3 Area Class#4 Panel size (# of circuits)#5 Enclosure#6 Control Voltage (L-N)#7 Power Distribution#8 MCB/Load Switch#9 Heated
NGC-20IECSafe Area0..40SS = Stainless Steel230YesLS180Yes
NGC-30ZONE2SW = Stainless Steel with Window400NoMCB200No
NGC-40FG = Fiber Glass
Elexant-4020i

To be repeated for each controller configuration

#10 CNTRL#11 Number of Circuits#12 Circuit Breaker Type#13 Module Type#14 Additional Module#15 Poles#16 Phase Selection#17 Type of Relay and Rating#18 Skid#19 Transformer#20 General Options#21 Comment
CNTRL: Control, PD: Power Distribution, PD/CNTRL: Power Distribution and Control0..40RCBO/ 2P20CElexant-4020i XXXNGC30- XXX1L-NSS3Yes: Transformer includedYesT1500
RCBO/ 2P25CNGC40- XXXNGC40- XXX2L-LSS3ZNo: No TransformerNoUIT
RCBO/ 2P32CNGC30- XXXNGC20- XXX3...W800
W2400
ANT
AL
AR
RMM3 RMM2-DI

Controller Details

Raychem NGC-40

A diagram illustrates the Raychem NGC-40 system, showing local monitoring via a TOUCH 1500 touch screen display and remote configuration/monitoring via Supervisor software.

The Raychem NGC-40 is a multipoint electronic control system with a unique single point controller architecture for heat-tracing used in process temperature maintenance and freeze protection applications. By taking advantage of innovative modular packaging techniques, the NGC-40 control system provides configuration and component flexibility so that it may be optimized for a customer's specific needs. The NGC-40 uses a single controller module per heat-tracing circuit for maximum reliability. The NGC-40 control system in combination with the solid-state relays can be used for 1-phase and 3-phase heat-tracing circuits up to 63 Amp at 690 Vac. The NGC-40 control modules include ground-fault measurements and as well single-phase and three-phase line current measurements. The Safety Temperature limiter can be used in combination with hazardous area approved contactors for control limited designs in Zone 1 applications (with controller panel in Zone 2).

Temperature inputs: Each IO module accepts up to four additional RTD inputs. Each RMM3 module installed in the field can accept up to 8 RTDs. 16 RMM3 Modules can be daisy chained together via RS-485 for a total of 128 (8x16) RTDs. Since multiple RMM3's can be networked over a single cable to the NGC-40, the cost of RTD field wiring will be significantly reduced.

Digital inputs: The NGC-40 control system can be extended with the Digital Input module RMM2-DI. This enables the capability monitoring of equipment in the field like circuit breakers, switches etc.

Communication: The NGC-40 support Industry 4.0 and the Internet of Things (IoT) by offering a flexible Modbus map creating a very easy way of integrating the TOUCH 1500 user interface with external control systems. The NGC-40 system supports multiple communications ports, allowing serial interfaces (RS-485 and RS-232) and Ethernet connections to be used with external devices. All communications with the NGC-40 panel are accomplished through the NGC-40-BRIDGE module which acts as the central router for the system, connecting the panel's control modules, IO modules, TOUCH 1500 touch screen and Remote Monitoring Modules (RMM3), as well as upstream devices such as Raychem Supervisor and the TOUCH 1500 user interface.

Raychem NGC-30

A diagram depicts the Raychem NGC-30 system, with local monitoring via a TOUCH 1500 touch screen display and remote configuration/monitoring via Supervisor software.

The Raychem NGC-30 is a multi-circuit electronic control system for heat-tracing used in process-temperature maintenance and freeze-protection applications. The NGC-30 Controller can accommodate temperature inputs from a variety of sources: hard-wired to the panel mounted CRM(S) modules or from Remote Monitoring Modules (RMM3). The NGC-30 for Zone 2 applications is equipped with the card rack module for solid-state-relays (CRMS), rated up to 63 Amp at 690 Vac. Up to four Pt100 sensor inputs for each heat-tracing circuit allow for a variety of combinations of temperature control, monitoring, and alarming. The ability to monitor and configure the controller is available both locally and remotely with the User Interface Unit (NGC-UIT3-EX) and the Supervisor software.

Raychem Elexant 4020i

A photograph shows the compact, touch-screen-based Raychem Elexant 4020i controller.

The Raychem Elexant 4020i is a compact, full-featured, touch screen based, single-point heat-tracing controller. It provides control and monitoring of Electric Heat-Tracing (EHT) circuits for both freeze protection and process temperature maintenance. This controller can monitor and alarm on high and low temperature, high and low current, ground-fault levels, voltage, and supports a host of additional features to offer the utmost in control and monitoring of EHT. The Elexant 4020i controller provides three output types: a line powered relay for driving contactors, a DC output for driving solid-state relays (SSRs) and a 0-10 V analog output for driving variable output power modules. Multiple communication ports allow flexible connectivity for remote monitoring, configuration, and ease of integration with Supervisor software, TOUCH 1500-EX or a Process Control System.

Solid state relay modules

The Zone 2 approved solid state relay (SSRs) modules are available in various versions and may be used with any of the controller products outlined above. They are mounted on the side of the panel enabling good heat transfer to keep heat away from the inside of the panel. The heated SSR module always contains groups of three SSR modules mounted on one heat sink. The Type of SSR, including voltage, amperage, inrush current as well as the cable size and type of cable are specified at the panel configuration procedure. The minimum ambient operating temperature of the heated SSRs is –55°C.

Elexant 9200i wireless radio

Each panel can be optionally equipped with the Elexant 9200i wireless radio modules. The radios enable wireless communications between the Zone 2 panels and the network User Interfaces such as the TOUCH 1500-EX, UIT3-EX, and/or Supervisor. The radios using 868 MHz and 2.4 GHz are available, and they support point-to-point, star, line, and Mesh network topologies. Security is ensured through use of the 128-bit Advanced Encryption Standard (EAES). Reliability is enhanced by network self-healing capabilities and auto-negotiation of alternate pathways in the event of lost communications. Antennas can be installed on the panel or when needed, antenna packages are available to allow remote installation for improved range. For more details see the specifications of the Elexant 9200i.

Approvals

Panel: For use in ordinary and hazardous area Zone 2 (Gas). Temperature classification depends on panel configuration. Product certification includes [CE certification] and [IECEx certification] marks.

NGC-30/NGC-40/Elexant 4020i: For use in ordinary and hazardous area Zone 2 (Gas). Temperature classification: NGC-40: T4, NGC-30: T5, Elexant 4020i: T4. Product certification includes [CE certification] and [IECEx certification] marks.

More details about product certification, approvals and conditions of safe use are available at chemelex.com.

Ordering Information

The Zone 2 panels provide flexible configurations - the following items are optionally available:

ItemCan be used with
TOUCH 1500-EXNGC-40, Elexant 4010i / 4020i, (field mounted) NGC-20
NGC-UIT3-EXNGC-30, (field mounted) NGC-20
Alarm LightsAll controllers and Power Distribution
Alarm RelayAll controllers and Power Distribution
RMM3Remote monitoring module for Temperature Inputs
RMM2-DIRemote monitoring module for Digital Inputs

Contact Information

  • North America: Tel +1 800 545 6258, info@chemelex.com
  • Latin America: Tel +1 713 868 4800, info@chemelex.com
  • Europe, Middle East, Africa, India: Tel +32 16 213 511, Fax +32 16 213 604, info@chemelex.com
  • Asia Pacific: Tel +86 21 2412 1688, infoAPAC@chemelex.com

©2025 Chemelex. All Chemelex marks and logos are owned or licensed by Chemelex Europe GmbH or its affiliates. All other trademarks are the property of their respective owners. Chemelex reserves the right to change specifications without notice.

PDF preview unavailable. Download the PDF instead.

RAYCHEM-DS-EU1856-Zone2Panels-EN Adobe PDF Library 17.0 Adobe InDesign 20.1 (Windows)

Related Documents

Preview Raychem Zone 2 Control, Monitoring, and Switching Systems
Comprehensive technical specifications and configuration details for Raychem's ATEX and IECEx certified Zone 2 control, monitoring, and switching systems, designed for electric heat tracing applications in hazardous environments.
Preview Raychem Flex Series NGC-30/NGC-40 System Panels and Skids for Heat Tracing Control
Comprehensive technical specifications and configuration details for Raychem's Flex Series NGC-30 and NGC-40 heat tracing control and monitoring systems, designed for reliable operation in hazardous and non-hazardous industrial environments.
Preview Raychem Touch 1500 Configuration Guide
This guide provides detailed instructions for configuring and monitoring Raychem NGC-40 systems, including various modules like NGC-40-BRIDGE, HTC, HTC3, and SLIM, as well as compatible thermostats such as Elexant 3500i, NGC20/Elexant 5010i, and Elexant 4010i/4020i, using the Touch 1500 interface for heat tracing applications.
Preview Raychem Touch 1500 Configuration Guide
This guide provides detailed instructions for configuring and operating the Raychem NGC-40 system using the Touch 1500 user interface. It covers system overview, basic and advanced settings, and communication protocols for various Raychem modules.
Preview Raychem Supervisor Heat-Tracing Controller Configuration and Monitoring Software Operations Manual
Comprehensive operations manual for Raychem Supervisor software, detailing configuration, monitoring, system requirements, setup, and advanced features for heat-tracing controllers and systems. Covers NGC-40, Elexant, and other Raychem products.
Preview Raychem Elexant 4020i Installation Guide: Heat Tracing Control Module
Comprehensive installation guide for the Raychem Elexant 4020i, a touch-screen heat-tracing control module. Covers specifications, approvals, wiring diagrams, mounting, and safety conditions for electric heat tracing (EHT) applications.
Preview Industrial Electrical Heat Tracing Systems Engineering Specification
This engineering specification details requirements for Raychem's advanced industrial electrical heat-management and heat tracing systems, covering design, materials, installation, and testing.
Preview Raychem NGC-40-HTC and NGC-40-HTC3 Installation Instructions
This document provides installation instructions for the Raychem NGC-40-HTC and NGC-40-HTC3 control and monitoring modules, designed for use with the Raychem NGC 40 system. It covers product description, required tools, certifications, technical specifications, wiring diagrams, and maintenance.