Raychem Touch 1500 Configuration Guide

This document serves as a comprehensive guide for the setup and operation of the Raychem NGC-40 Control & Monitoring system, utilizing the intuitive Touch 1500 user interface.

Introduction to the Raychem NGC-40 System

The Raychem NGC-40 is a sophisticated multipoint electronic control, monitoring, and power distribution system designed for heat tracing applications. It is particularly effective for process temperature, maintenance, and freeze protection. Leveraging innovative modular packaging, the NGC-40 system offers exceptional configuration and component flexibility, allowing for optimization to meet specific customer needs.

This manual details the configuration and maintenance aspects of all Raychem NGC-40 components. For installation, operation, testing, and adjustment information, please refer to the NGC-40 Installation Manual.

Key Features and Capabilities

  • Temperature Measurement: Utilizes 3-wire, 100-ohm platinum or 2-wire Nickel/Nickel iron RTDs for accurate temperature readings.
  • Control Modes: Supports various control modes including On/Off (Deadband), Proportional, and PASC (Proportional Ambient Sensing Control) for both Electro-Mechanical Relays (EMRs) and Solid State Relays (SSRs).
  • Monitoring: Tracks parameters like ground fault, temperature, and load currents to ensure system integrity. Alarms can be individually enabled/disabled and set as latching or non-latching.
  • Ground-Fault Protection: Incorporates ground-fault monitoring and trip features, potentially eliminating the need for specialized circuit breakers and reducing overall system cost.
  • Communications: Networks with host PCs running Raychem Supervisor client-server software (DTS) and Touch 1500 units. Supports Modbus protocol and provides RS-232/RS-485 and Ethernet communication interfaces via the NGC-40-BRIDGE module.

User Interface

The Raychem NGC-40 system features a touch screen User Interface Terminal (Touch 1500 or TOUCH1500R) with an LCD color display. This interface provides an intuitive and user-friendly experience for programming and monitoring, eliminating the need for complex keyboards or cryptic codes.

Installation Considerations

The Touch 1500 can be installed locally on the Raychem NGC-40 panel door for indoor, nonhazardous locations. For outdoor or hazardous locations, specific protective measures such as a Z Purge system, a protective cover, and a space heater/thermostat may be required. Remote mounting options are also available for difficult-to-access or hazardous panel locations.

License Agreement

This document outlines the license agreement for the Raychem Touch 1500 Software. It details the terms of use, restrictions, warranty disclaimers, and limitations of liability provided by Chemelex LLC.

Models: TOUCH 1500, TOUCH 1500 Interface Terminal, Interface Terminal, Terminal

File Info : application/pdf, 176 Pages, 38.31MB

PDF preview unavailable. Download the PDF instead.

RAYCHEM-IM-H58682-NGC40TOUCH1500-EN ?srsltid=AfmBOopJkdOgirbPUf5pORBY5rCdxCnpn iSYBOCn6VU-WcrGpU6trww

References

Adobe PDF Library 17.0 Adobe InDesign 20.1 (Windows)

Related Documents

Preview Raychem Touch 1500 Configuration Guide
This guide provides detailed instructions for configuring and monitoring Raychem NGC-40 systems, including various modules like NGC-40-BRIDGE, HTC, HTC3, and SLIM, as well as compatible thermostats such as Elexant 3500i, NGC20/Elexant 5010i, and Elexant 4010i/4020i, using the Touch 1500 interface for heat tracing applications.
Preview Raychem Supervisor Heat-Tracing Controller Configuration and Monitoring Software Operations Manual
Comprehensive operations manual for Raychem Supervisor software, detailing configuration, monitoring, system requirements, setup, and advanced features for heat-tracing controllers and systems. Covers NGC-40, Elexant, and other Raychem products.
Preview Raychem NGC-40-HTC and NGC-40-HTC3 Installation Instructions
This document provides installation instructions for the Raychem NGC-40-HTC and NGC-40-HTC3 control and monitoring modules, designed for use with the Raychem NGC 40 system. It covers product description, required tools, certifications, technical specifications, wiring diagrams, and maintenance.
Preview Raychem NGC-40-HTC & NGC-40-HTC3 Installation Instructions
Installation instructions for Raychem NGC-40-HTC and NGC-40-HTC3 control and monitoring modules, used with the Raychem NGC-40 System. Covers features, approvals, specifications, wiring, and mounting.
Preview Raychem Zone 2 Control, Monitoring, and Switching Systems
Comprehensive technical specifications and configuration details for Raychem's ATEX and IECEx certified Zone 2 control, monitoring, and switching systems, designed for electric heat tracing applications in hazardous environments.
Preview Raychem Zone 2 Control, Monitoring, and Power Distribution Panels
Comprehensive guide to Raychem Zone 2 Control, Monitoring, and Power Distribution panels, detailing their ATEX and IECEx approved features, specifications, configuration options, controller capabilities (NGC-40, NGC-30, Elexant 4020i), and ordering information for industrial heat-tracing applications.
Preview Industrial Electrical Heat Tracing Systems Engineering Specification
This engineering specification details requirements for Raychem's advanced industrial electrical heat-management and heat tracing systems, covering design, materials, installation, and testing.
Preview Raychem NGC-40-BRIDGE Installation Instructions
Installation instructions for the Raychem NGC-40-BRIDGE module, a control and monitoring module for the Raychem NGC-40 System. Includes technical specifications, wiring diagrams, and safety information.