SECOP Compressor Technical Data

Model: KLE8.6GFTX

Sales Code: 106G5903

Compressor Design Specifications

Oil typePolyolester
Oil viscosity19,2 cSt
Oil quantity240 cm³ / 8,1 fl.oz
Refrigerant charge - technical limit250 g / 8,8 oz
Free gas volume (compressor)1495 cm³ / 50,6 fl.oz
Weight9,7 kg / 21,4 lbs
Motor protectionExternal
Winding resistance main8,4 Ω (at 25°C)
Winding resistance aux11,9 Ω (at 25°C)
Max. winding temperature125°C / 257°F
Max. discharge temperature130°C / 266°F
Additional noteGood robustness against liquid intake. Ice-cube maker optimization - indirect suction intake.
Refrigerant(s)R134a, R513A
Displacement8,6 cm³ / 0,52 cu.in
Compressors on pallet100

General Configurations

Configuration Summary

Parameter Conf. 1 Conf. 2 Conf. 3 Conf. 4
Motor configuration CSIR CSIR CSIR CSIR
Power supply (nominal) 220-240V/50Hz 208-230V/60Hz 220-240V/50Hz 208-230V/60Hz
Number of phases 1 1 1 1
Voltage range 187-254V 198-253V 187-254V 198-253V
Approvals VDE, CB, UL VDE, CB, UL VDE, CB, UL VDE, CB, UL
Starting torque HST HST HST HST
Note -/- -/- -/- -/-

Applications

Parameter Conf. 1 Conf. 2 Conf. 3 Conf. 4
Refrigerant R134a R134a R513A R513A
Application LBP+MBP+HBP LBP+MBP LBP+MBP+HBP LBP+MBP
System cooling fan 3m/s fan 3m/s fan 3m/s fan 3m/s
Hot gas defrost OK OK OK OK
Long interval pull down OK OK OK OK

Electrical Data

Parameter Conf. 1 Conf. 2 Conf. 3 Conf. 4
Starting device type relay relay relay relay
Run capacitor -/- -/- -/- -/-
Start capacitor 80 µF 80 µF 80 µF 80 µF
LRA (locked rotor amps / 4s/ U(N)) 13,4 A 13,2 A 13,4 A 13,2 A
RLA (rated load amps / 1s/ U(N)) 1,8 A 2 A 1,8 A 2 A
Cut in current (U(N)) 12,3 A 12,3 A 12,3 A 12,3 A

Compressor Dimensions and Features

Housing Dimensions

The compressor housing dimensions are provided in millimeters and inches:

  • A Height: 182mm / 7,17in
  • B Height: 175mm / 6,89in
  • C Length shell: 198mm / 7,8in
  • D Length w. cover: 238mm / 9,37in
  • E Width: 160mm / 6,3in

A diagram illustrates these dimensions, showing the overall height, length with cover, and width.

Connectors

Details for the Suction (X), Discharge (Y), and Process (Z) connectors:

Parameter Suction (X) Discharge (Y) Process (Z)
Diameter (i:inside, o:outside) [mm] øi 8,11-8,29 øi 6,11-6,29 øi 6,11-6,29
Diameter (i:inside, o:outside) [in] øi 0,32-0,33 øi 0,24-0,25 øi 0,24-0,25
Material Copper Copper Copper
Horizontal angle +2° 35°
Vertical angle +2° 30° 145°
Position l/h/w [mm] 119/73/59 117/107/66 -88/101/71
Position l/h/w [in] 4,7/2,9/2,3 4,6/4,2/2,6 -3,5/4/2,8
Straight tube length [mm] 14 14 14
Straight tube length [in] 0,5 0,5 0,5

A diagram shows the connector positions relative to the compressor body, including horizontal and vertical angles.

Compressor Fixation

The compressor is designed for mounting via bolt joints or snap-on connections. Baseplate dimensions and hole sizes are specified:

  • Baseplate dimensions: 204mm x 132mm (8.03in x 5.2in)
  • Baseplate diameter (ØE): 9.7mm (0.38in)
  • Large holes (Ll, Lw, ØL, ØS): 165mm x 101.6mm (6.5in x 4in), with hole diameters Ø19mm (0.75in) and Ø16mm (0.63in).
  • Small holes (Sl, Sw, ØS): 170mm x 70mm (6.7in x 2.76in), with hole diameter Ø16mm (0.63in).

A diagram illustrates the baseplate with these dimensions and hole placements.

Mounting Accessories

Available mounting accessories include various bolt joints and snap-on components with specific part numbers:

  • Bolt joint | M6 | Ø16mm: 118-1917
  • Bolt joint | Ø1/4" | Ø16mm: 118-1946
  • Bolt joint | Ø1/4" | Ø19mm: 118-1949
  • Snap-on | Ø7,3 | Ø16mm: 118-1947
  • Multi pack (for bolt joints): 118-1918, 118-1919

Diagrams show the bolt joint and snap-on mounting methods.

Application Notes

  • Provision for PE Grounding is located at the PE Stamp on the compressor.
  • Suction gas connector and Process connector can be switched, which may result in a minor loss of cooling capacity.

Performance Data and Operating Conditions

Ambient and Machine Room Temperatures

  • Ambient temperature range: 10 - 43°C (50 - 110°F)
  • Machine room temperature range: 10 - 48°C (50 - 119°F)
  • Compressor cooling: fan 3m/s

Operation Pressure Range

The document includes graphs illustrating the operation pressure range. These graphs plot condensing pressure (in bars and saturation temperature) against evaporation pressure (in bars and saturation temperature). Two sets of curves are shown for continuous operation and transitory operation.

Optimization + Standard Conditions

Performance data under various standard conditions for R134a and R513A refrigerants are provided:

Configuration 1 (R134a, 220-240V/50Hz)

Conditions Cooling Capacity Efficiency Power Consumption
[W] [Btu/h] [kcal/h] COP [W/W] EER [Btu/Wh] [kcal/Wh] P1 [W] I [A] Ref. mass flow [kg/h]
pe/pc
[°C] -23/54
[°F] -10/130
248,1847213,51,334,531,14186,91,414,82
[°C] -7/54
[°F] 20/130
517,31767445,21,786,081,53290,41,8211,29
[°C] 7,2/54
[°F] 45/130
901,63079775,92,317,901,99389,62,2720,00
[°C] -35/40
[°F] -31/104
131,2448112,91,043,560,90125,91,232,88
[°C] -10/45
[°F] 14/113
450,81540388,01,816,171,56249,41,6510,55
[°C] 5/50
[°F] 41/122
773,52642665,72,197,471,88353,92,1019,49

Configuration 2 (R134a, 208-230V/60Hz)

Conditions Cooling Capacity Efficiency Power Consumption
[W] [Btu/h] [kcal/h] COP [W/W] EER [Btu/Wh] [kcal/Wh] P1 [W] I [A] Ref. mass flow [kg/h]
pe/pc
[°C] -23/54
[°F] -10/130
299,21022257,51,354,601,16222,11,415,81
[°C] -7/54
[°F] 20/130
617,42109531,41,786,071,53347,41,8613,47
[°C] 7,2/54
[°F] 45/130
1076,93678926,82,317,901,99465,42,3523,89
[°C] -35/40
[°F] -31/104
156,3534134,61,123,840,97139,11,173,43
[°C] -10/45
[°F] 14/113
537,41835462,51,806,161,55298,11,6712,58
[°C] 5/50
[°F] 41/122
923,13153794,52,197,461,88422,42,1723,26

Configuration 3 (R513A, 220-240V/50Hz)

Conditions Cooling Capacity Efficiency Power Consumption
[W] [Btu/h] [kcal/h] COP [W/W] EER [Btu/Wh] [kcal/Wh] P1 [W] I [A] Ref. mass flow [kg/h]
pe/pc
[°C] -23/54
[°F] -10/130
273,8935235,71,344,581,15204,11,475,89
[°C] -7/54
[°F] 20/130
541,91851466,41,755,981,51309,41,9013,27
[°C] 7,2/54
[°F] 45/130
924,83158795,92,267,701,94410,02,3722,97
[°C] -35/40
[°F] -31/104
145,9498125,51,053,580,90139,31,263,61
[°C] -10/45
[°F] 14/113
470,41607404,91,776,041,52266,01,7212,47
[°C] 5/50
[°F] 41/122
783,52676674,22,107,181,81372,62,1922,46

Configuration 4 (R513A, 208-230V/60Hz)

Conditions Cooling Capacity Efficiency Power Consumption
[W] [Btu/h] [kcal/h] COP [W/W] EER [Btu/Wh] [kcal/Wh] P1 [W] I [A] Ref. mass flow [kg/h]
pe/pc
[°C] -23/54
[°F] -10/130
330,31128284,21,364,641,17243,01,487,11
[°C] -7/54
[°F] 20/130
647,02210556,81,755,961,50370,51,9515,85
[°C] 7,2/54
[°F] 45/130
1105,23775951,22,267,721,94489,22,4527,46
[°C] -35/40
[°F] -31/104
173,9594149,71,123,830,97155,01,214,30
[°C] -10/45
[°F] 14/113
560,91916482,81,766,021,52318,51,7514,87
[°C] 5/50
[°F] 41/122
935,43195805,02,107,181,81444,72,2626,82

Performance Tables

Detailed performance data is provided for different operating conditions:

Configuration 1 (R134a, 220-240V/50Hz)

Conditions Cooling Capacity Efficiency Power Current Mass Flow
[W] [Btu/h] [kcal/h] COP [W/W] EER [Btu/Wh] [kcal/Wh] P1 [W] I [A] [kg/h]
Cond. pressure pc=45/113
[°C/°F] -35/-31
123,6422106,40,983,350,84126,01,232,67
[°C/°F] -25/-13 216,6740186,41,254,281,08172,91,374,69
[°C/°F] -15/5 368,21257316,91,655,631,42223,31,558,03
Return gas temp. RGT=32/90
[°C/°F] -10/14
467,71597402,51,876,401,61249,41,6510,24
[°C/°F] 0/32 717,82452617,82,378,092,04303,11,8715,87
Liquid temp. Tliq=45/113
[°C/°F] 5/41
869,92971748,62,638,992,27330,41,9919,37
[°C/°F] 10/50 1040,83555895,82,919,942,50357,62,1223,36
Cond. pressure pc=55/131
[°C/°F] -35/-31
96,432983,00,762,580,65127,61,242,30
[°C/°F] -25/-13 181,7621156,41,023,480,88178,11,384,35
[°C/°F] -15/5 315,11076271,21,334,541,14237,01,607,59
Return gas temp. RGT=32/90
[°C/°F] -10/14
401,61372345,71,495,091,28269,21,739,71
[°C/°F] 0/32 618,02110531,81,836,231,57338,62,0315,12
Liquid temp. Tliq=55/131
[°C/°F] 5/41
749,22559644,72,006,811,72375,42,2018,46
[°C/°F] 10/50 896,73062771,72,177,411,87413,62,3822,29

Configuration 2 (R134a, 208-230V/60Hz)

Conditions Cooling Capacity Efficiency Power Current Mass Flow
[W] [Btu/h] [kcal/h] COP [W/W] EER [Btu/Wh] [kcal/Wh] P1 [W] I [A] [kg/h]
Cond. pressure pc=45/113
[°C/°F] -35/-31
147,7504127,11,063,610,91139,81,173,19
[°C/°F] -25/-13 259,6886223,41,274,341,09204,11,355,62
[°C/°F] -15/5 439,41501378,21,655,621,42266,81,569,58
Return gas temp. RGT=32/90
[°C/°F] -10/14
557,61904479,81,876,391,61298,11,6712,20
[°C/°F] -5/23 695,92377598,92,117,211,82329,71,7915,30
Liquid temp. Tliq=45/113
[°C/°F] 0/32
855,52922736,22,378,082,04361,61,9218,92
[°C/°F] 7,2/45 1124,83841968,02,759,402,37408,72,1125,12
Cond. pressure pc=55/131
[°C/°F] -35/-31
117,8402101,40,832,840,72141,61,182,80
[°C/°F] -25/-13 219,7750189,01,043,560,90210,71,375,25
[°C/°F] -15/5 377,41289324,81,334,541,14283,81,629,09
Return gas temp. RGT=32/90
[°C/°F] -10/14
479,91639413,01,495,081,28322,41,7711,60
[°C/°F] -5/23 599,52047515,91,655,651,42362,51,9214,57
Liquid temp. Tliq=55/131
[°C/°F] 0/32
737,32518634,51,826,231,57404,42,0918,03
[°C/°F] 7,2/45 970,03313834,82,077,071,78468,32,3623,99

Configuration 3 (R513A, 220-240V/50Hz)

Conditions Cooling Capacity Efficiency Power Current Mass Flow
[W] [Btu/h] [kcal/h] COP [W/W] EER [Btu/Wh] [kcal/Wh] P1 [W] I [A] [kg/h]
Cond. pressure pc=45/113
[°C/°F] -35/-31
138,4473119,10,993,370,85140,21,263,36
[°C/°F] -25/-13 235,4804202,61,254,271,08188,11,425,74
[°C/°F] -15/5 390,91335336,41,635,571,40239,41,619,58
Return gas temp. RGT=32/90
[°C/°F] -10/14
491,91680423,41,856,321,59266,01,7212,09
[°C/°F] -5/23 743,42539639,82,327,932,00320,11,9518,44
Liquid temp. Tliq=45/113
[°C/°F] 0/32
894,83056770,12,588,802,22347,42,0722,32
[°C/°F] 10/50 1064,23634915,92,849,702,44374,72,2026,72
Cond. pressure pc=55/131
[°C/°F] -35/-31
108,236993,10,752,570,65143,61,282,95
[°C/°F] -25/-13 195,3667168,01,003,420,86195,21,445,35
[°C/°F] -15/5 329,61126283,61,294,411,14255,21,679,08
Return gas temp. RGT=32/90
[°C/°F] -10/14
415,81420357,81,444,931,24288,01,8111,50
[°C/°F] -5/23 629,12148541,41,755,991,51358,52,1217,57
Liquid temp. Tliq=55/131
[°C/°F] 0/32
757,22586651,71,916,531,65395,82,3021,28
[°C/°F] 10/50 900,53075774,92,077,081,78434,32,4825,49

Configuration 4 (R513A, 208-230V/60Hz)

Conditions Cooling Capacity Efficiency Power Current Mass Flow
[W] [Btu/h] [kcal/h] COP [W/W] EER [Btu/Wh] [kcal/Wh] P1 [W] I [A] [kg/h]
Cond. pressure pc=45/113
[°C/°F] -35/-31
165,5565142,41,063,610,91156,61,214,02
[°C/°F] -25/-13 282,1963242,71,274,321,09222,81,416,87
[°C/°F] -15/5 466,61594401,61,635,561,40286,81,6311,43
Return gas temp. RGT=32/90
[°C/°F] -10/14
586,62003504,81,846,291,59318,51,7514,42
[°C/°F] -5/23 726,12480624,92,077,081,78350,21,8717,93
Liquid temp. Tliq=45/113
[°C/°F] 0/32
886,23026762,62,327,922,00382,22,0021,98
[°C/°F] 7,2/45 1154,33942993,42,699,192,31429,12,1928,87
Cond. pressure pc=55/131
[°C/°F] -35/-31
132,2451113,80,822,820,71160,31,223,60
[°C/°F] -25/-13 236,1806203,21,023,480,88231,51,446,46
[°C/°F] -15/5 394,81348339,81,294,401,11306,21,7010,87
Return gas temp. RGT=32/90
[°C/°F] -10/14
496,91697427,61,444,911,24345,31,8513,74
[°C/°F] -5/23 615,32101529,51,595,451,37385,92,0217,09
Liquid temp. Tliq=55/131
[°C/°F] 0/32
750,92564646,21,755,991,51428,22,1920,97
[°C/°F] 7,2/45 978,03340841,71,996,781,71492,32,4627,57

PDF preview unavailable. Download the PDF instead.

kle86gftx 106g5903 r134a 220v 208v 50hz 60hz 08-2025 ds Microsoft Excel für Microsoft 365

Related Documents

Preview Secop KLE4.0GFTX Compressor Technical Data Sheet
Comprehensive technical data, specifications, and performance tables for the Secop KLE4.0GFTX compressor, including details on configurations, dimensions, electrical data, and operating pressure ranges for R134a refrigerant.
Preview SECOP KLE4.8GFTX Compressor Technical Data and Specifications
Comprehensive technical data sheet for the SECOP KLE4.8GFTX compressor. Details include compressor design specifications, general configurations (Conf. 1 & 2), application suitability (LBP, MBP, HBP), electrical data, dimensions, mounting accessories, ambient temperature limits, operation pressure ranges, and detailed performance data under various standard conditions (ASHRAE, EN12900) for both 220-240V/50Hz and 208-230V/60Hz operation. Features R134a and R513A refrigerants.
Preview SECOP KLE4.8GFTX Compressor Technical Data Sheet
Detailed technical specifications, dimensions, electrical data, and performance tables for the SECOP KLE4.8GFTX compressor, designed for R134a refrigerant, covering configurations for 220-240V/50Hz and 208-230V/60Hz.
Preview Secop FRK8.5G Compressor Technical Data and Specifications
Detailed technical specifications, performance data, dimensions, and electrical information for the Secop FRK8.5G compressor, available in 220-240V 50Hz and 208-230V 60Hz configurations.
Preview SECOP FRK6G Compressor Technical Data Sheet
Detailed technical specifications, dimensions, electrical data, and performance tables for the SECOP FRK6G compressor, designed for R134a refrigerant and operating on 220-240V/50Hz and 208-230V/60Hz power supplies.
Preview SECOP FRK7.5G Compressor Technical Data Sheet - Specifications and Performance
Detailed technical specifications, dimensions, electrical data, operating conditions, and performance tables for the SECOP FRK7.5G compressor. Includes data for 220-240V/50Hz and 208-230V/60Hz configurations.
Preview SECOP FRK5G Compressor Technical Data Sheet
Detailed technical specifications, dimensions, electrical data, and performance tables for the SECOP FRK5G compressor. Covers configurations for 220-240V/50Hz and 208-230V/60Hz, including operating conditions, power consumption, and refrigerant compatibility.
Preview SECOP KLE4.0GFMX Compressor Technical Data Sheet
Comprehensive technical specifications for the SECOP KLE4.0GFMX compressor, detailing configurations, dimensions, operating conditions, and performance data for R134a and R513A refrigerants. Includes electrical characteristics and mounting information.