IMMERGAS VICTRIX PRO V2

Wall-hung light commercial condensing gas boiler

HYDROGEN READY

Overview

The VICTRIX PRO V2 is a modular condensing boiler with a sealed chamber and forced draught, designed exclusively for heating applications. It is BIM READY, offering advanced integration capabilities for building information modeling.

Image Description: A modern, white, wall-hung Immergas VICTRIX PRO V2 boiler is shown. It features a sleek design with a digital control panel on the front, displaying operational information.

Image Description: A cross-section of a multi-story commercial building illustrates the integration of heating systems. Multiple Immergas VICTRIX PRO V2 boilers are shown installed in a cascade configuration, connected by pipework. Solar panels are visible on the roof, and the building design incorporates green spaces, suggesting an eco-friendly approach.

Key Features

Advantages

Installation Flexibility

The VICTRIX PRO V2 offers versatile installation options:

Image Description: Multiple VICTRIX PRO V2 boilers are shown connected in a cascade setup on a floor-standing frame, demonstrating a high-capacity heating solution.

Condensing Module and Combustion

Image Description: A close-up view of the internal stainless steel condensing module, highlighting its heat exchanger coils.

Image Description: A scenic image of a green field under a blue sky, accompanied by an "A+" rating, symbolizing high seasonal energy efficiency.

Regulation and Control

Image Description: An illustration of the Immergas control unit, featuring a clear digital display showing temperature, date, and time, along with operational buttons for system management.

Image Description: An image displays the internal components of the VICTRIX PRO V2 boiler, showing the heat exchanger, combustion chamber, and pipework.

Technical Characteristics

The VICTRIX PRO V2 range offers a comprehensive set of technical specifications across its models:

Main Characteristics Summary

Electrical connection to the master boiler Temperature settings Maximum number of boilers Water distribution zones Connection in series Thermal solar system connection
2 BUS wires: max length 50 meters Central heating: COMFORT, ECO, Anti-Freeze
DHW temperature
8 3 (1 direct and 2 mixed) + 1 DHW pump Up to nº3 Cascade and Zones Regulator kits and nº6 expansion kits. Only the master panel will be connected to the boiler Possibility to install and manage a thermal solar system without an additional external control unit

Technical Data Tables

The following tables detail the specifications for VICTRIX PRO V2 models from 35 kW to 150 kW.

Models 35, 55, 60, 68 V2

Technical characteristics Measurement unit VICTRIX PRO 35 V2 VICTRIX PRO 55 V2 VICTRIX PRO 60 V2 VICTRIX PRO 68 V2
Natural gas boiler article number 3.033850 3.033851 3.033858 3.033859
LPG gas boiler article number 3.033850GPL 3.033851GPL 3.033858GPL 3.033859GPL
Energy class A A A A
Template article number 1.047417 1.047417 1.047417 1.047417
Maximum heat input kW 34,9 51,0 59,9 65,0
Minimum heat input kW 3,9 5,4 7,8 7,8
Maximum effective heat output (80/60°C) kW 33,9 49,8 58,5 63,4
Minimum effective heat output (80/60°C) kW 3,7 5,1 7,5 7,5
Maximum effective heat output (50/30°C) kW 36,9 54,2 63,9 69,2
Minimum effective heat output (50/30°C) kW 4,1 5,7 8,3 8,3
Central heating seasonal efficiency ηs % 94 94 94 94
Efficiency at 100% Pn (80/60°C) % 97,0 97,6 97,7 97,5
Efficiency at 100% Pn (50/30°C) % 105,8 106,2 106,8 106,5
Efficiency at 100% Pn (40/30°C) % 107,7 106,8 108,3 107,8
Efficiency at partial load 30% (return flow temperature 30°C) % 109,2 109,6 109,6 109,4
Chimney losses with burner on (100% Pn) (80/60°C) % 2,7 2,3 2,2 2,3
Chimney losses with burner off % 0,028 0,019 0,017 0,020
Casing losses with burner on (100% Pn) (80/60°C) % 0,3 0,1 0,1 0,1
Casing losses with burner off % 0,3 0,2 0,2 0,2
NOx class 6 6 6 6
Weighted NOx mg/kWh 37 39 41 39
Weighted CO mg/kWh 27 24 17 17
Gas flow rate to burner at max, and min. heat output with methane (G20) m³/h 3,69/0,41 5,40/0,57 6,34/0,83 6,88/0,83
Maximum fan available head (max/min) Pa 90-1 190-2 195-4 230-4
Flue exhaust mass flow rate at nominal heat output (G20) kg/h 54/6 82/9 96/13 104/13
CO₂ at nominal/minimum heat output (G20) % 9,6/9,1 9,2/8,7 9,3/9,0 9,3/9,0
CO at nominal/minimum heat output (G20) mg/kWh 257/3 235/3 171/3 192/3
Maximum/Minimum fume temperature (G20) °C 79/60 74/60 71/65 74/65
Maximum operating temperature °C 95 95 95 95
Heating system adjustable temperature °C 15-90 15-90 15-90 15-90
Maximum operating pressure of heating circuit bar 4,5 4,5 4,5 4,5
Electric power supply V/Hz 230/50 230/50 230/50 230/50
Nominal power absorption A 1,0 1,8 2,2 2,3
Installed electric power W 130 158 295 300
Power absorbed by pump W 77,8 73,0 182,0 182,0
Power absorbed by fan W 45,0 65,0 95,0 103,0
Electrical insulation rating IP X5D X5D X5D X5D
Full appliance weight (empty) kg 52,4 (50,0) 59,8 (57,0) 64,2 (61,0) 64,2 (61,0)
Appliance water content litres 2,4 2,8 3,2 3,2

Models 80, 100, 120, 150 V2

Technical characteristics Measurement unit VICTRIX PRO 80 V2 VICTRIX PRO 100 V2 VICTRIX PRO 120 V2 VICTRIX PRO 150 V2
Codice caldaia metano 3.033852 3.033853 3.033854 3.033855
Codice caldaia GPL 3.033852GPL 3.033853GPL 3.033854GPL 3.033855GPL
Energy class A A A A
Template article number 1.047417 1.047417 1.047417 1.047417
Maximum heat input kW 75,0 93,0 114,5 141,0
Minimum heat input kW 7,8 10,1 11,7 29,0
Maximum effective heat output (80/60°C) kW 73,2 90,9 112,3 138,3
Minimum effective heat output (80/60°C) kW 7,5 9,8 11,3 28,3
Maximum effective heat output (50/30°C) kW 79,4 98,8 121,7 149,9
Minimum effective heat output (50/30°C) kW 8,3 10,7 12,4 30,8
Central heating seasonal efficiency ηs % 94 94 94 93
Efficiency at 100% Pn (80/60°C) % 97,6 97,7 98,1 98,1
Efficiency at 100% Pn (50/30°C) % 105,9 106,2 106,3 106,3
Efficiency at 100% Pn (40/30°C) % 105,8 108,2 108,4 107,2
Efficiency at partial load 30% (return flow temperature 30°C) % 109,5 109,4 109,7 109,5
Chimney losses with burner on (100% Pn) (80/60°C) % 2,3 2,2 1,8 1,8
Chimney losses with burner off % 0,013 0,016 0,016 0,017
Casing losses with burner on (100% Pn) (80/60°C) % 0,1 0,1 0,1 0,1
Casing losses with burner off % 0,16 0,17 0,18 0,18
NOx class 6 6 6 6
Weighted NOx mg/kWh 33 34 30 34
Weighted CO mg/kWh 24 23 19 20
Gas flow rate to burner at max, and min. heat output with methane (G20) m³/h 7,94/0,83 9,84/1,07 12,12/1,24 14,92/3,07
Maximum fan available head (max/min) Pa 295-3 230-3 360-4 350-16
Flue exhaust mass flow rate at nominal heat output (G20) kg/h 121/13 149/17 185/19 226/48
CO₂ at nominal/minimum heat output (G20) % 9,2/9,0 9,3/8,9 9,2/8,9 9,3/8,9
CO at nominal/minimum heat output (G20) mg/kWh 246/10 235/7 219/4 230/7
Maximum/Minimum fume temperature (G20) °C 79/65 74/60 71/60 73/60
Maximum operating temperature °C 95 95 95 95
Heating system adjustable temperature °C 15-90 15-90 15-90 15-90
Maximum operating pressure of heating circuit bar 4,5 5,4 5,4 5,4
Electric power supply V/Hz 230/50 230/50 230/50 230/50
Nominal power absorption A 2,5 2,7 3,0 3,2
Installed electric power W 320 330 410 580
Power absorbed by pump W 182,0 183,0 183,0 306,0
Power absorbed by fan W 120,0 155,0 250,0 247,0
Electrical insulation rating IP X5D X5D X5D X5D
Full appliance weight (empty) kg 64,2 (61,0) 104,0 (95,0) 111,0 (101,0) 124,0 (112,0)
Appliance water content litres 3,2 9,0 10,0 12,0

Dimensions and Connections

Detailed technical drawings provide precise dimensions and connection points for the VICTRIX PRO V2 boilers.

Image Description: Technical drawings show the physical dimensions, connection points (Gas 'G', System Flow 'M', System Return 'R', Air Intake 'A', Flue Expulsion 'S', Condensate Drain 'SC'), and recommended clearances for the VICTRIX PRO V2 35/55/60/68/80 V2 models. It includes details for separator kits and concentric kits.

Image Description: Technical drawings illustrate the physical dimensions, connection points (Gas 'G', System Flow 'M', System Return 'R', Air Intake 'A', Flue Expulsion 'S', Condensate Drain 'SC'), and recommended clearances for the VICTRIX PRO V2 100/120/150 V2 models. It includes details for separator kits and concentric kits.

Head-Flow Rate Curves

The following graphs illustrate the head-flow rate performance for various VICTRIX PRO V2 models, showing the relationship between pump head (Prevalenza in kPa) and flow rate (Portata in l/h) at different pump speeds (e.g., 100%, 77%). The pump power absorption is also indicated.

Image Description: A series of graphs titled "VICTRIX PRO V2 head-flow rate curve" are presented for different model groups (35 V2, 55 V2, 60-68-80 V2, 100 V2, 120 V2, 150 V2). Each graph plots "Prevalenza (kPa)" on the y-axis against "Portata (l/h)" on the x-axis, with lines representing different pump speeds and shaded areas indicating pump power absorption.

Thermoregulation

Implementing a thermoregulation device can significantly enhance the seasonal efficiency of the heating system. Immergas offers a range of optional accessories for advanced control:

Image Description: Images display various thermoregulation devices, including digital chronothermostats (CRONO 7, CRONO 7 WIRELESS), external probes, and the Cascade and Zones Regulator Kit, showcasing their compact designs and digital interfaces.

Flue Systems

VICTRIX PRO V2 boilers are compatible with a range of dedicated flue kits designed for air suction and fume exhaust. These kits ensure high resistance to corrosion, ease of installation, and functional fit, utilizing bayonet fastening systems and special sealing gaskets.

Configuration B23 (Open Chamber, Fan Assisted)

This configuration includes various kits for vertical and horizontal flue discharge, air intake, and outdoor installations:

Configuration C (Sealed Chamber, Fan Assisted)

This configuration offers kits for sealed chamber installations:

Image Description: An illustration demonstrates a vertical ducting solution for flue gas exhaust, showing the connection from the boiler through bends and extension pipes to a terminal outlet, suitable for existing chimneys or vertical shafts.

Image Description: Illustrations showcase components of the Ø 80 mm flexible ducting system, including flexible ducting kits, support bends, vertical outlet kits, and chimney hole closing panels.

Image Description: Illustrations depict exhaust manifold kits and associated extension pipes and bends designed for indoor installation in boiler rooms, particularly for cascade setups.

Image Description: Images display various flue system components such as terminal outlets, stub pipes, bends, gasket kits, clapet valve kits, and cover kits for outdoor installation.

Option Kits

A comprehensive selection of optional kits is available to complement the VICTRIX PRO V2 system, ensuring quality and reliability:

Hydraulic Optional for Cabinet Installation

Free Standing Installation

Hydraulic Optional for Single Installation

Hydraulic Optional for Cascade Installation

Image Description: Images showcase various optional kits, including boiler cabinets, free-standing support frames, manifold kits, safety kits, flue system components, and hydraulic accessories, illustrating their design and purpose.

Company Information

Immergas S.p.A.

Address: 42041 Brescello (RE) - Italy

Phone: +39 0522 689011

Fax: +39 0522 680617

Website: immergas.com

Immergas is a certified company (UNI EN ISO 9001:2015) specializing in the design, manufacture, and post-sale assistance of gas boilers, gas water heaters, and related accessories.

Social Media: Follow Immergas on Facebook, YouTube, and Instagram.

PDF preview unavailable. Download the PDF instead.

VICTRIX-PRO-V2-EXPORT compressed Adobe InDesign 18.5 (Windows) iLovePDF

Related Documents

Preview Immergas VICTRIX PRO V2: High-Efficiency Condensing Gas Boiler for Light Commercial Use
Discover the Immergas VICTRIX PRO V2, a wall-hung condensing gas boiler offering exceptional efficiency, Hydrogen Ready technology, and flexible installation for commercial and residential buildings. Explore technical specifications and accessories.
Preview Immergas VICTRIX PRO V2: High-Efficiency Light Commercial Condensing Gas Boilers
Discover the Immergas VICTRIX PRO V2 series, a range of wall-hung condensing gas boilers designed for light commercial and residential applications. Featuring high efficiency, hydrogen-ready technology, and flexible installation options, these boilers offer advanced performance and environmental benefits.
Preview Immergas VICTRIX PRO V2: High-Efficiency Condensing Gas Boilers for Commercial & Residential Use
Explore the Immergas VICTRIX PRO V2 series of wall-hung light commercial condensing gas boilers. Featuring high efficiency, flexible installation, Hydrogen Ready technology, and advanced control options for optimal heating performance.
Preview Immergas VICTRIX PRO V2 EU: High Power Condensing Boilers Technical Sheet
Comprehensive technical sheet for the Immergas VICTRIX PRO V2 EU series of high-power, wall-hung condensing boilers. Details specifications, features, models (35-180 EU), installation options, accessories, and technical data for efficient heating solutions.
Preview Immergas VICTRIX PRO V2 EU: High Power Condensing Boilers Technical Sheet
Explore the Immergas VICTRIX PRO V2 EU range of high-power, wall-hung condensing boilers. Discover advanced features, technical specifications, installation flexibility, and environmental benefits for efficient heating solutions.
Preview Immergas VICTRIX PRO V2 EU: High Power Condensing Boilers
Discover the Immergas VICTRIX PRO V2 EU range of high-power, wall-hung condensing boilers. Engineered for efficiency, flexibility, and reduced emissions, these boilers are ideal for modern heating systems.
Preview Immergas VICTRIX PRO 1 I Series: High Power Condensing Boilers - Technical Overview
Discover the Immergas VICTRIX PRO 1 I series of wall-hung modular condensing boilers, engineered for high-power heating. This technical document details specifications, features, and installation options for large residential, commercial, and industrial applications, emphasizing efficiency and environmental performance.
Preview Immergas VICTRIX PRO 2 ErP Condensing Boilers: Technical Specifications and Manual
Explore the Immergas VICTRIX PRO 2 ErP series of wall-hung condensing boilers. This technical manual details specifications, dimensions, installation, and features for models 35-55, 80, 100, and 120 ErP, highlighting their high efficiency and versatility for various heating needs.