Trane BACnet® Communication Interface for Chillers (BCI2-C)

Field Kit Order Number: KIT19852

Models: RTWD, RTAC, CGAM

Introduction

Read this manual thoroughly before operating or servicing this unit.

Warnings, Cautions, and Notices

Safety advisories appear throughout this manual as required. Your personal safety and the proper operation of this machine depend upon the strict observance of these precautions.

Types of Advisories:

Important Environmental Concerns

Scientific research has shown that certain man-made chemicals can affect the earth's naturally occurring stratospheric ozone layer when released to the atmosphere. Trane advocates the responsible handling of all refrigerants, including industry replacements for CFCs and HCFCs.

Important Responsible Refrigerant Practices

Trane believes that responsible refrigerant practices are important to the environment, customers, and the air conditioning industry. All technicians who handle refrigerants must be certified according to local rules. For the USA, the Federal Clean Air Act (Section 608) sets forth the requirements for handling, reclaiming, recovering, and recycling of certain refrigerants and the equipment used in these service procedures. Know the applicable laws and follow them.

Proper Field Wiring and Grounding Required!

Failure to follow code could result in death or serious injury. All field wiring MUST be performed by qualified personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in NEC and your local/state/national electrical codes.

Personal Protective Equipment (PPE) Required!

Failure to wear proper PPE for the job being undertaken could result in death or serious injury. Technicians, in order to protect themselves from potential electrical, mechanical, and chemical hazards, MUST follow precautions in this manual and on the tags, stickers, and labels, as well as the instructions below:

Follow EHS Policies!

Failure to follow instructions below could result in death or serious injury.

Copyright

This document and the information in it are the property of Trane, and may not be used or reproduced in whole or in part without written permission. Trane reserves the right to revise this publication at any time, and to make changes to its content without obligation to notify any person of such revision or change.

Trademarks

All trademarks referenced in this document are the trademarks of their respective owners.

Specifications, Requirements, and Dimensions

The following table and illustration provides specifications, requirements, and dimensions of the BCI2-C controller.

Table 1. Specification and requirements

Category Specification
Storage Temperature -44°C to 95°C (-48°F to 203°F)
Storage Relative humidity Between 5% to 95% (non-condensing)
Operating Temperature -40°C to 70°C (-40°F to 158°F)
Operating Humidity Between 5% to 95% (non-condensing)
Power 24 Vdc ±15%, maximum load 90 mA
Altitude 6,500 ft maximum (1,981 m)
Installation U.L. 840: Category 3
Pollution U.L. 840: Degree 2

Requirements

Figure 1. Controller dimension

A diagram showing the physical dimensions of the BCI2-C controller. Key dimensions include:

Installing BCI2-C in the Chiller Control Panel

Before installing the BCI2-C kit, open the box and verify that the following parts are enclosed:

Parts List

Part Number Description
X13651793001 Module; BCI2-C
X19060374040 Wire Harness, 4 COND, 20 AWG
573178900001 Bracket; BCI2-C Module Mounting
X25330033100 Screw; Phillips Panhead 0.375 inch, Thread Rolling Zinc Plate # 6-32
X25020783130 Screw; TORX Panhead 0.75 inch, Thread Rolling Zinc Plate # 6-32
23092075 CGAM-W Frame Units - Schematic
23115511 CGAM - V Frame Units - Schematic
23115510 CGAM Slant Frame Units - Schematic
23092097 RTAC - 2 Compressor Units Schematic
23094621 RTAC - 3 Compressor Units, X-Line Schematic
23094622 RTAC - 3 Compressor, Units Y-Delta Schematic
23094623 RTAC - 4 Compressor Units X-Line Schematic
23094624 RTAC - 4 Compressor Y-Delta Schematic
23097584 RTWD/RTUD 60-250 ΤΟN WATER COOLED CHILLER Schematic
23097585 RTWD/RTUD 60-250 ΤΟN WATER COOLED CHILLER Schematic
One (1) copy of service literature shipped with each unit (located in the control panel)

Important:

Visually inspect contents for obvious defects or damage. All components have been thoroughly inspected before leaving the factory. Any claims for damage incurred during shipment should be filed immediately with the carrier.

Installation

Important: Before beginning installation, it is important to read the following safety warnings. Procedures presented in this guide should be performed only by qualified HVAC technicians.

Live Electrical Components!

Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury. When necessary to work with live electrical components, have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks.

Hazardous Voltage!

Failure to disconnect power before servicing could result in death or serious injury. Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/tagout procedures to ensure the power can not be inadvertently energized. Verify that no power is present with a voltmeter.

Note: All mounting holes for brackets and DIN rail have been pre-drilled.

To install the BCI2-C:

  1. Disconnect all power from the chiller.
  2. Open the control panel and mount the brackets (573178900001) to the control panel using two (2), #6-32 x 0.375 Phillips pan head, thread forming screws (X25330033100). Use the mounting locations for the specific chiller type as shown in the following illustrations:

Figure 2. RTWD/RTUD

Diagram showing the installation of the BCI2-C on an RTWD/RTUD chiller control panel.

Figure 3. RTAC

Diagram showing the installation of the BCI2-C on an RTAC chiller control panel.

Figure 4. CGAM

Diagram showing the installation of the BCI2-C on a CGAM chiller control panel.

Figure 5. BCI2-C link IMC

Diagram illustrating the BCI2-C circuit board with key components labeled, including IMC, IMC Status LEDs, Link, and Link Comm Status LEDs.

Mounting a CGAM Slant BCI2-C

Figure 6. CGAM slant

Diagram showing the mounting of the BCI2-C on a CGAM slant chiller.

Setting Rotary Dial Address Using Embedded BCI2 Software Tool

Previous versions of BCI-C had rotary dials to set the controller address. The BCI2-C controller does not have rotary dials to set the address. A default address is set at the factory and recorded on a label applied to the circuit board. The address can be changed using the embedded BCI2 Service Tool. Follow these instructions to change the address of the controller:

  1. Use a USB-A to USB-B cable. Plug the USB-B end into the Service Port on the BCI2. Plug the USB-A end into a laptop.
  2. Open a browser in the laptop.
  3. Enter 198.80.18.1
  4. The BCI2 Service Tool will be served up from the BCI2 controller.
  5. Navigate to Installation > Identification and Communication > Protocol Configuration > Edit.
  6. Set the Rotary Dial Setting (address) by clicking the line and typing in the new address.
  7. If the Device ID needs to be changed, check the box next to Use Software Device ID and enter the desired device ID.

Note: All devices are MSTP managers with valid MAC addresses of 001 to 127 for BACnet.

Figure 7. Setting rotary dial address

Screenshot of the BCI2 Service Tool interface showing the "Identification and Communications" section, with fields for Name, Description, Location, Protocol Configuration, Device ID, Rotary Dial Setting, and Baud Rate.

Connecting and Configuring the BCI2-C with Tracer TU Software

This section describes how to connect to the Tracer TU software and configure the BCI2-C controller. Before beginning, if the TU service tool is not installed, refer to the Tracer TU Service Tool Getting Started Guide (TTU-SVN02). This document will provide information about features, capabilities, and requirements of TU.

Connecting to Tracer TU

To connect to Tracer TU:

  1. Connect the USB cable directly from the laptop to the BCI2-C controller or to a panel USB port connected to the controller.
  2. Click either the Tracer TU desktop icon or the Tracer TU program item in the Tracer TU group on the Start menu. The Tracer TU splash screen appears briefly followed by the Startup Task Panel.

Figure 8. Startup task panel

Screenshot of the Tracer TU Startup Task Panel, showing options for "Offline Tasks" and "Connect Using" (Direct Connection, TU Adapter - Wired, TU Adapter - Wireless, Network Connection, Remote Connection via Trane Connect).

Important: If using a PC with multiple USB ports, it is conceivable to connect using the same process outlined below for the same piece of equipment. This is normal operation. Observe existing USB standards for cable length. (For more information go to informational Websites, such as http://www.USB.org.)

  1. Select the Direct Connection (Via USB cable) radio button if it is not already selected.
  2. Click the Connect button and the Unit Summary page displays after successful connection.

Configuring the BCI2-C

Configuring the BCI2-C is performed by means of the TU Controller Settings tab. Use this utility to configure date and time, units of measure, and protocol.

Important: Before beginning, the user will need the Tracer TU software, Version 11.6 or higher.

To configure the BCI2-C:

  1. Select the Controller Settings tab from the horizontal tab set in the TU window.

Note: The content of this screen is based on the type of controller that is connected and the system protocol used to communicate with the controller.

Figure: Controller Settings Tab

Screenshot of the Tracer TU "Controller Settings" tab, showing fields for Name, Date and Time, Protocol, Controller Units, and Notification Classes.

  1. Enter a meaningful name for the controller as shown above.
  2. Click Date and Time to set the preferred date/time formats and then click Save. The BCI2-C uses standard BACnet services for time synchronization. (Refer to BACnet® Communication Interface for Chiller (BCI2-C) Integration Guide (BAS-SVP055*-EN).

Note: The actual dates and times are not saved during power loss.

  1. Click the Protocol and select the desired Baud Rate in the drop-down list box.
  2. Click the Controller Units and select the desired units of measure for data communicated across the BACnet link. The units of measure cannot be changed once the BCI2-C is configured and bound to the CH530.

Important: Failure to set the units of measure will result in having to restore factory defaults, reconfigure, and rebind the BCI2-C. To restore, reconfigure, and rebind the BCI2-C, refer to the next section, “Clearing the Controller to Reconfigure and Rebind the BCI2-C,” p. 13.

  1. If a software Device ID is required, check the Use Software Device ID box and enter the desired BACnet Device ID.
  2. Click Save.

Clearing the Controller to Reconfigure and Rebind the BCI2-C

Clearing the controller and then reconfiguring and rebinding the BCI2-C is necessary for two reasons:

To clear the controller:

  1. Establish the connection between Tracer TU and the BCI2-C controller.
  2. Select the Controller Settings tab from the vertical tab set located on the right side of the TU window.
  3. On the controller settings page, there is a clear controller button displayed in the upper right-hand portion of the screen display.

Figure: Clear Controller Button

Screenshot of the Tracer TU "Controller Settings" page highlighting the "Clear Controller" button.

  1. Click the Clear Controller button and a pop-up window will display with a message that asks for confirmation to reset the device. Click Yes.
  2. A pop-up window displays confirming that the controller has been reset, indicating that the controller will be rebooted. Click OK. The BCI2-C controller is restored to its factory default state after it reboots.
  3. Follow Steps 1 through 7 in the previous section to reconfigure the BCI2-C controller.
  4. Go to "Connecting and Configuring the BCI2-C with Tracer TU Software," p. 12 for binding if needed.

Connecting and Configuring the BCI2-C with BCI2 Service Tool

This section describes how to configure the BCI2-C controller using the embedded BCI2 Service Tool.

  1. Use a USB-A to USB-B cable. Plug the USB-B end into the Service Port on the BCI2. Plug the USB-A end into a laptop.
  2. Open a browser in the laptop.
  3. Enter 198.80.18.1
  4. The BCI2 Service Tool will be served up from the BCI2 controller.

To enter a name, navigate to Installation > Identification and Communication > Identification > Edit. Enter a name, description, and location, and then click Save.

Figure: Identification and Communications Screen

Screenshot of the BCI2 Service Tool's "Identification and Communications" section, showing fields for Name, Description, and Location.

To set the time and date, navigate to Installation > Regional Specifications > Edit. Enter date and time, and then click Save.

Figure: Regional Specifications Screen

Screenshot of the BCI2 Service Tool's "Regional Specifications" section, showing fields for Date, Time, and Time Zone.

To clear the BCI-2 controller, navigate to Tools > Backup and Restore > Clear Controller. When prompted, click Continue.

The BCI2-R is cleared and ready to accept a new configuration.

Figure: Backup and Restore Screen

Screenshot of the BCI2 Service Tool's "Backup and Restore" section, showing options for Backup, Export Backup, Edit Backup Schedule, Restore, and Device Operations (Clear Controller).

To configure Baud Rate, Rotary address and Device ID, navigate to Installation > Identification and Communication > Protocol Configuration > Edit.

Figure: Protocol Configuration Screen

Screenshot of the BCI2 Service Tool's "Protocol Configuration" section, showing fields for System Protocol, Device ID, Rotary Dial Setting, BACnet Segment Timeout, BACnet APDU Timeout, BACnet APDU Retries, and BACnet MSTP Configuration (Baud Rate, Max Managers).

To change system units navigate to Installation > System Units.

Figure: System Units Screen

Screenshot of the BCI2 Service Tool's "System Units" section, showing fields for Temperature, Temperature Delta, Thermal Ramp Rate by Time, Thermal Ramp Rate by Temperature, Gaseous Pressure, Fluidic Pressure, and Gaseous Flow, with options to select units.

Configuring a CH530 for BACnet with TechView Software

The BCI2-C can be installed only in chillers that have main processor (MP) software (used with CH530 Series chillers) supporting the BACnet option. BACnet is only supported in the following MP software:

Note: The TechView software includes the current version of MP software for the CH530 series of products. To download the latest versions of TechView software, go to http://www.trane.com/commercial/designanalysis/techview.aspx.

Figure 9. Trane Tracer CH530 Unit Control Service Tools

Screenshot of the Trane Tracer CH530 Unit Control Service Tools interface, showing various configuration options.

After verifying the correct version level of software, ensure that all other LLIDs are successfully bound and communicating and then:

  1. Restore power to the chiller and then connect the TechView to the Dynaview.
  2. Verify the correct version of software.
  3. Navigate to the Configuration view and choose the Options tab.
  4. Select BACnet Interface for the BAS communication option.

Figure 10. Activate binding

Screenshot of the BCI2-C Configuration screen within TechView, showing the "Activate For Binding" button.

  1. Navigate to Binding View and locate the device in the device setup area.
  2. When prompted, use the BCI2 Service Tool to activate the BCI2-C for binding. Navigate to Installation > BCI2-C Configuration > Activate for Binding.

Note: The Activate for Binding button is used for binding the BCI2-C instead of a Service Button or a magnet, as has been the case in the past.

  1. Select OK at the prompt to initiate the binding.

Note: For more detailed information about binding or unbinding, refer to the KestrelView Online Help.

Additional Resources

Note: For further assistance, contact your local Trane sales office.

Models: RTWD BACnet Communication Interface for Chillers BCI2-C, RTWD BACnet, Communication Interface for Chillers BCI2-C, Interface for Chillers BCI2-C, Chillers BCI2-C, RTAC, CGAM

File Info : application/pdf, 24 Pages, 3.86MB

PDF preview unavailable. Download the PDF instead.

RF-SVN006B-EN 07152022

References

Acrobat Distiller 22.0 (Windows)

Related Documents

Preview Trane BCI2-C Installation Instructions for BACnet Communication Interface for Chillers
Comprehensive installation guide for the Trane BACnet Communication Interface for Chillers (BCI2-C), detailing setup, configuration, and integration with HVAC systems for models RTWD, RTAC, and CGAM.
Preview Trane BACnet Communication Interface (BCI2-I) Integration Guide for IntelliPak
This integration guide from Trane provides detailed information on configuring and using the BACnet Communication Interface (BCI2-I) with IntelliPak and Commercial Self-Contained HVAC systems. Learn about BACnet protocols, service tools, and device management.
Preview BACnet Communication Interface for Chiller (BCI-C) Integration Guide
This guide provides information on the BACnet Communication Interface for Chillers (BCI-C), a non-programmable communications module that allows HVAC equipment to communicate on a BACnet network. It covers the BACnet protocol, rotary switches and LEDs, data point definitions, and chiller model compatibility.
Preview Trane BACnet Communication Interface 2 for IntelliPak and CSC Units Data Sheet
Product data sheet for the Trane BACnet Communication Interface 2 (BCI2-I), a module that enables heating, ventilation, and air-conditioning (HVAC) equipment, including IntelliPak and Commercial Self-contained (CSC) units, to communicate on a BACnet network. It details features, benefits, specifications, and physical dimensions.
Preview Trane RCDB - Symbio 800 Controls Upgrade Kit Installation for RTAC CH530 Rotary Chiller
Detailed installation guide for the Trane RCDB - Symbio 800 Controls Upgrade Kit, designed for RTAC CH530 Rotary Chillers. Covers safety, parts, tools, and step-by-step procedures for upgrading chiller control systems.
Preview Trane Serie R RTAC: Enfriadora de Líquido de Alto Rendimiento
Descubra la enfriadora de líquido Trane RTAC Serie R, diseñada para alta fiabilidad, eficiencia energética y rendimiento superior en aplicaciones industriales y comerciales. Conozca sus características y especificaciones.
Preview Trane Air-Fi Wireless System: Installation, Operation, and Maintenance Guide
Comprehensive guide for the Trane Air-Fi Wireless System, covering installation, operation, and maintenance of the Air-Fi Wireless Communications Interface (WCI) and Air-Fi Wireless Communications Sensors (WCS). Learn about device compatibility, network setup, security, and troubleshooting.
Preview Trane Tracer TU Adapter Installation and Operation Guide
Comprehensive installation and operation instructions for the Trane Tracer TU Adapter (Wired/Wireless), including safety warnings, setup procedures, and troubleshooting.