BACnet® Communication Interface 2
For: IntelliPak™ and Commercial Self-contained (CSC) Units
Document Type: Data Sheet Ordering Number: C175259100001 Description: IntelliPak 1, 2, and CSC; for field-installed kits Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or serious injury. When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that are attached to the equipment. All trademarks referenced in this document are the trademarks of their respective owners. The BACnet® Communication Interface for IntelliPak™ (BCI2-I) device is a communications module that allows heating, ventilation, and air-conditioning (HVAC) equipment to communicate on a BACnet communications network. This device is a non-programmable communication module that connects directly to the IntelliPak family of equipment by means of an inter-process communication (IPC) buss. This factory- or field-installed device is designed to be used on IntelliPak 1 and 2 rooftop units, and IntelliPak Commercial Self-contained Units (CSC). Note: The BCI2-I is not designed for fresh air units (FAU). The following table provides specifications and requirements for the BCI2-R controller. The BACnet Communication Interface board has the following approximate dimensions: Diagram Description: The document includes a visual representation of the printed circuit board (PCB) for the BACnet Communication Interface. The PCB is populated with various electronic components, including resistors, capacitors, integrated circuits (ICs), transistors, LEDs, connectors, and labeling for different sections and functions such as 'AREA A', 'Service Port', 'Factory Address', 'New Address', 'LED TX', '2D RX', and 'ACTUATOR'.Product Identification
⚠ SAFETY WARNING
Trademarks
Overview
Features and Benefits
Features Benefits BCI2-I Installation The device is provided as either a factory- or field-mounted unit. Self-configuring/Data Point Manager The device can determine data points based on the type of IntelliPak equipment and the installed equipment options. BACnet protocol The device supports BACnet protocol per ASHRAE 135-2004 and meets requirements for BACnet Testing Laboratory (BTL) certification as an BACnet Building Controller (B-BC) profile device. Multiple diagnostics on control points Allows for advanced, remote control, and troubleshooting of equipment. Compatible with Trane Air-Fi® Wireless Communication System Provides wireless communication between Trane BACnet unit and system controllers and zone sensors. This allows faster, easier, lower-risk installation and life-cycle savings due to future space re-configuration, upgrades, and expansions. Specifications and Controller Dimensions
Table 1. BCI2-R Specifications
Parameter Storage Operating Temperature -48°F to 203°F (-44°C to 95°C) -40°C to 70°C (-40°F to 158°F) Relative humidity Between 5% to 95% (non-condensing) Between 5% to 95% (non-condensing) Power N/A 24 Vdc ±15%, maximum load 90 mA (for DC)
24 Vac ±15% nominal, 6 VA, Class 2 (Maximum VA = 12VA) (for AC)Mounting weight of controller N/A Mounting surface must support: 0.80 lb. (0.364 kg) Physical Dimensions