RenewAire HE 10RT Energy Recovery Ventilator - EC Motor
NEW! OUTDOOR UNIT
Specifications
Ventilation Type: Static plate, heat and humidity transfer
Airflow Range: 250-1100 CFM
AHRI 1060 Certified Core: One L125-G5
Standard Features:
- Non-fused disconnect
- 24VAC transformer/relay package
- Cross-core differential pressure ports
- Independent blower control
- Filters: Total Qty. 2, MERV 8: 20" x 20" x 2"
Unit Weight: 261-415 lbs., varies by option(s)
Max. Shipping Dimensions & Weight (on pallet): 60" L x 30" W x 82 1/4" H, 455 lbs.
Motor(s): Qty. 2, 370W ea., Direct drive EC motorized impeller packages (208-230V/1Ph/60Hz)
Options
- Qty. 2, Direct drive EC motorized impeller packages: 480W 120V/1Ph/60Hz (Advanced), 680W 208-230V/1Ph/60Hz (Advanced), 860W 460V/3Ph/60Hz (Advanced)
- Fused disconnect
- Integrated programmable controls: enhanced, premium
- Class 1 low leakage motorized isolation dampers: FA, EA or both airstreams
- Factory mounted filter alarms: both airstreams
- Double wall construction
- Exterior paint: white, custom colors
Accessories
- Filters: MERV 13, 2" (shipped loose)
- Backdraft damper: 12"
- Automatic balancing damper: 4", 5", 6"
- Potentiometer speed control: remote installed
- Roof curb: standard 14"
- Curb wind clip
- Engineered combo curb for Trane or Carrier RTUS
- Digital time clock: wall mount (TC7D-W), in exterior enclosure (TC7D-E)
- Carbon dioxide sensor/control: wall mount (CO2-W), duct mount (CO2-D)
- IAQ sensor: wall mount (IAQ-W), duct mount (IAQ-D)
- Motion occupancy sensor/control: ceiling mount (MC-C), wall mount (MC-W)
- Smoke detector: duct mount (SD-D)
- Indoor electric duct heater: RH series (1-11.5 kW), EK series (1-175 kW)
- Indirect gas-fired duct furnace: GH series (50-400 MBH); Installed downstream of any fans
- Duct flange kit: square 14" x 14", 2 flanges
EC Motor Operating Range and Fan Performance
The document includes performance curves for the HE10RT with different motor options (1P/120V, 1P/208-230V, and 3P/460V). These charts illustrate the relationship between Airflow (CFM) and External Static Pressure (in. w.g.), along with the recommended operating range for the advanced EC motor.
HE10RT MOTOR 1P/120V Options
Airflow (CFM) | External Static Pressure (Inches Water Column) | Unit Power Consumption (Watts) |
---|---|---|
200 | 3.00 | 567 |
295 | 3.00 | 739 |
367 | 3.00 | 870 |
495 | 2.54 | 978 |
580 | 2.25 | 1033 |
675 | 1.91 | 1080 |
770 | 1.58 | 1113 |
865 | 1.24 | 1133 |
960 | 0.89 | 1142 |
1055 | 0.53 | 1140 |
1150 | 0.15 | 1129 |
1150 | 0.00 | 1017 |
Note: Airflow performance includes effect of clean, standard filter supplied with unit.
HE10RT MOTOR 1P/208-230V Options
Airflow (CFM) | External Static Pressure (Inches Water Column) | Unit Power Consumption (Watts) |
---|---|---|
200 | 2.78 | 566 |
295 | 2.72 | 658 |
444 | 2.48 | 791 |
495 | 2.37 | 832 |
580 | 2.15 | 894 |
675 | 1.74 | 900 |
770 | 1.35 | 900 |
865 | 0.97 | 900 |
960 | 0.58 | 900 |
1100 | 0.00 | 900 |
1150 | 0.27 | 1209 |
1150 | 0.00 | 919 |
Note: Airflow performance includes effect of clean, standard filter supplied with unit.
HE10RT MOTOR 3P/460V Options
Airflow (CFM) | External Static Pressure (Inches Water Column) | Unit Power Consumption (Watts) |
---|---|---|
200 | 3.00 | 829 |
224 | 3.00 | 860 |
295 | 2.91 | 925 |
390 | 2.76 | 1015 |
485 | 2.60 | 1105 |
580 | 2.40 | 1191 |
675 | 2.18 | 1273 |
770 | 1.92 | 1346 |
865 | 1.62 | 1408 |
960 | 1.28 | 1456 |
1055 | 0.89 | 1488 |
1150 | 0.45 | 1501 |
1150 | 0.00 | 1267 |
Note: Airflow performance includes effect of clean, standard filter supplied with unit.
Electrical Data
Option | Watts | Volts | Hz | Phase | FLA per motor | Min. Cir. Amps | Max. Overcurrent Protection Device |
---|---|---|---|---|---|---|---|
[EE] Standard | 370 | 208-230 | 60 | Single | 1.73 | 3.9 | 20 |
[AA] Advanced | 480 | 120 | 60 | Single | 6.5 | 14.6 | 15 |
[AA] Advanced | 680 | 208-230 | 60 | Single | 5 | 11.3 | 15 |
[AA] Advanced | 860 | 460 | 60 | Three | 1.22 | 2.7 | 15 |
Dimensions and Mounting
The document provides detailed diagrams for unit mounting and application, including front, left, right, and top views. It also shows the HE10RT curb cross-section. Key dimensions and airflow orientations are illustrated.
Abbreviations:
- EA: Exhaust Air to Outside
- OA: Outside Air Intake
- RA: Room Air to be Exhausted
- SA: Supply Air to Inside
- RTR: Rooftop Vertical RA Only
- RTV: Rooftop Vertical RA & SA
- RTF: Rooftop Vertical SA Only
- RTH: Rooftop Horizontal RA & SA
Installation Orientation: Unit must be installed in the orientation shown. Airstreams cannot be switched.
Notes:
- Unless otherwise specified, dimensions are rounded to the nearest eighth of an inch.
- Specifications may be subject to change without notice.