An image shows a wooden spool wound with blue heating cable. Logos indicate KIWA certification for EN ISO/IEC 17020 and a KIWA certification mark with the number 1913, suggesting compliance with standards. The Ebeco F-10 is a self-regulating heating cable designed for frost protection of pipes and hoses, suitable for both internal and external installation.
Due to its self-regulating construction, the heating cable can be cut to the required length and crossed over itself without the risk of overheating. The cable automatically adjusts its power output based on the ambient temperature and installation method. It always emits power, ensuring a heightened water temperature. For optimal energy efficiency, it is recommended to control the heating cable with a thermostat (e.g., E 85 816 10).
The F-10 cable is meter-marked and approved for drinking water applications, including its accessories.
Use Areas
The Ebeco F-10 heating cable is primarily intended for frost protection of water and wastewater pipes, as well as hoses. It can be installed both externally on the pipe surface and internally within the pipe.
Technical Specifications
Connecting Voltage
220-240 V
Maximum Connecting Length (at 0°C)
Installation Type | Max Length (10 A / 16 A) |
---|---|
External Installation | 100 m / 115.5 m |
Internal Installation | 61.5 m / 89.5 m |
Dimensioning and Performance
When installed internally, the F-10 cable can protect a 32 mm pipe with 20 mm insulation down to -30 °C. For external installation under the same conditions, the cable provides frost protection down to -20 °C.
For applications requiring higher heat output or for larger pipe dimensions, the cable can be coiled around the pipe, installed in parallel (double), or a thicker layer of insulation can be applied.
A diagram illustrates the connection of the heating cable to a power source and thermostat, showing the cable running along a pipe. Another diagram shows the heating cable coiled around a pipe, with insulation applied over the cable and pipe.
Installation Notes
For internal installations, it is necessary to use the E 89 604 10 completion kit for internal mounting (or equivalent like SSTL 81 761 86 in Finnish documentation). The cable is marked with length indicators.
Ensure that joints and connection boxes are placed in locations protected from water ingress.
The installation should be documented with a sketch or drawing showing cable lengths, splice locations, and power connections.
Test Protocol
The heating cables must be connected for at least 5 minutes before current measurement. Note that the current strength will vary with temperature due to the self-regulating nature of the cables. The entire heating cable installation must be documented with a sketch or drawing detailing cable lengths, splice locations, and power feeds.
A table with columns for Fuse number, Cable number, Cable length (m), Insulation Resistance (MΩ, minimum 10 MΩ), and Current (A) is provided for recording test results.
Fuse nr | Cable nr | Cable length (m) | Insulation Resistance (MΩ) min 10 MΩ | Current (A) |
---|---|---|---|---|
Installation Status:
- ✔️ Installation performed according to mounting instructions.
- ✔️ Splices and boxes are placed to avoid water ingress.
- ✔️ Installation documented with sketch/drawing.
Installer Information:
Date: _________________________
Signature: _________________________
Printed Name: _________________________
Company: _________________________
Warranty Information
EB-Trace F-10 Product Warranty
Ebeco AB provides a 10-year product warranty for material defects on products and accessories supplied by Ebeco. If material defects occur during the warranty period, Ebeco AB will repair or offer a replacement product at no cost to the buyer.
Ebeco AB also provides a 5-year product warranty for supplied control units.
The warranty is valid only if the installation is performed by an authorized electrician in accordance with applicable regulations and Ebeco's mounting instructions. The warranty certificate, including the test protocol, must be completed and signed by the electrician who performed the installation. The heating cable installation must also be documented with a photo, sketch, or drawing showing the layout before it is covered.
The warranty does not cover installations performed by unauthorized electricians, or if unauthorized electricians have made modifications or repairs. The warranty also does not cover damage resulting from the use of incorrect materials or construction, or from installation errors. Furthermore, damage caused by vandalism, fire, lightning strikes, water damage, negligence, abnormal use, or accidents is not covered.
In the event of a material defect covered by the warranty, Ebeco AB must be notified before any action is taken.
To claim the warranty, the warranty certificate with the accompanying material specification and the completed and signed test protocol must be presented.
EBECO AB
Martin Larsson, VD
The installation was performed by: _________________________ according to the attached material specification.
[drinking water approved symbol]
Contact Information
EBECO AB
Lärjeågatan 11
415 02 Göteborg, Sweden
Phone: +46 31-707 75 50
Email: info@ebeco.se