Delta TP02G-AS1 Instruction Sheet

Warning

English: TP02G-AS1 is an OPEN-TYPE device. It should be installed in a control cabinet free of airborne dust, humidity, electric shock and vibration. To prevent non-maintenance staff from operating TP02G-AS1, or to prevent an accident from damaging TP02G-AS1, the control cabinet in which TP02G-AS1 is installed should be equipped with a safeguard. For example, the control cabinet in which TP02G-AS1 is installed can be unlocked with a special tool or key.

English: DO NOT connect AC power to any of I/O terminals, otherwise serious damage may occur. Please check all wiring again before TP02G-AS1 is powered up. After TP02G-AS1 is disconnected, Do NOT touch any terminals within a minute. Make sure that the ground terminal on TP02G-AS1 is correctly grounded in order to prevent electromagnetic interference.

French: TP02G-AS1 est un module OUVERT. Il doit être installé que dans une enceinte protectrice (boitier, armoire, etc.) saine, dépourvue de poussière, d'humidité, de vibrations et hors d'atteinte des chocs électriques. La protection doit éviter que les personnes non habilitées à la maintenance puissent accéder à l'appareil (par exemple, une clé ou un outil doivent être nécessaire pour ouvrir a protection).

French: Ne pas appliquer la tension secteur sur les bornes d'entrées/Sorties, ou l'appareil TP02G-AS1 pourra être endommagé. Merci de vérifier encore une fois le câblage avant la mise sous tension du TP02G-AS1. Lors de la déconnection de l'appareil, ne pas toucher les connecteurs dans la minute suivante. Vérifier que la terre est bien reliée au connecteur de terre afin d'éviter toute interférence électromagnétique.

Introduction

Product Outline

Diagram showing the front panel of the TP02G-AS1 with labels for Alarm LED Indicator, RS-232 LED Indicator, RS-485 LED Indicator, Displaying Area, Escape/Exit Key, Enter Key, Arrow Keys (Up, Down, Left, Right), and Function Keys (F0-F9).

Panel Function Explanation

Panel component Explanation
Alarm LED indicator (RED) Status 1: When power is on, LED will blink slowly for three times. Status 2: When there is an abnormal situation, LED will blink quickly along with an alarm sound.
RS-232 LED indicator (yellow) LED will blink when transmits program and communicates via RS-232.
RS-485 LED indicator (green) LED will blink when communicates via RS-485.
Displaying area Liquid Crystal Module display area. It is used to display current program status.
Escape/Exit key It is used to cancel an incorrect input, or to exit a programming step.
Enter key It is used to input a value or accept a programming command.
Arrow keys UP/Pg Up: It is used to increase the value or move up one page. Pg Dn/DOWN: It is used to decrease the value or move down one page. Left: This key is left direction key and it can be used to select the position of the value. Right: This key is right direction key and it can be used to select the position of the value.
Function keys F0/0: It is used as a constant 0, or the user can define it as function F0. F1/1: It is used as a constant 1, or the user can define it as function F1. F2/2: It is used as a constant 2, or the user can define it as function F2. F3/3: It is used as a constant 3, or the user can define it as function F3. F4/4: It is used as a constant 4, or the user can define it as function F4. F5/5: It is used as a constant 5, or the user can define it as function F5. F6/6: It is used as a constant 6, or the user can define it as function F6. F7/7: It is used as a constant 7, or the user can define it as function F7. F8/8: It is used as a constant 8, or the user can define it as function F8. F9/9: It is used as a constant 9, or the user can define it as function F9.

Back Panel

Diagram showing the back panel of the TP02G-AS1 with connections for RS-232, RS-485, and power input.

Dimension

Diagrams showing the front panel dimensions, right side view, vertical view, and mounting dimensions of the TP02G-AS1.

Front panel dimensions: 147.00 mm [5.79 in] width, 97.00 mm [3.82 in] height.

Mounting dimensions: 135-136.5 mm [5.31-5.37 in] width, 85 mm [3.35 in] height. Thickness range: 0.5-9.0mm.

Installation

Instructions for installing the TP02 series into a panel opening. Emphasizes using the mounting fixed support accessory for firm mounting and warns about potential damage if screws are over-tightened. Recommends leaving sufficient space (more than 50mm) around the unit for heat dissipation. Notes that only the front panel is guaranteed by ingress protection rating.

Specifications

Function Specifications

Item TP02G-AS1
Screen type STN-LCD
Display color Monochromatic
Backlight The back-light automatic turn off time is 1 ~ 99 minutes (0 = DO NOT turn off). The back-light life is about 50 thousand hours at 25°C.
Resolution 160 x 32 dots; 5×8 dots, 25 characters×8 rows; 8×8 dots, 16 characters×8 rows; 8×12 dots, 16 characters×5 rows; 8×16 dots, 16 characters×4 rows
Display range (W) x (H) = 72 x 22 (unit: mm)
Contrast adjustment 15 levels of adjustment
Display screen Language/font: ASCII: Alphanumeric (including European characters); Taiwan: (Big 5 codes) Traditional Chinese Fonts; China: (GB2324-80 codes) Simplified Chinese Fonts
Font size: ASCII: 5 × 8, 8 × 8, 8 × 12, 8 × 16
Alarm LED indicator (RED): 1. Power on indication (blink for three times); 2. Communication error alarm; 3. Special indication by user programming
RS-232 LED indicator (yellow) It will blink when transmitting program and communicating by using RS-232.
RS-485 LED Indicator (green) It will blink when communicating by using RS-485.
Program memory 256KB flash memory
RAM of system 32K Byte
External interface Serial communication port RS-232 (COM1): Unsynchronized transmission method: RS-232; Data length: 7 or 8 bits, Stop bits: 1 or 2 bits; Parity: none/odd/even, Transmission speed: 4,800 bps ~115,200 bps; RS-232: 9 PIN D-SUB male
Extension communication port RS-485 (COM2): Unsynchronized transmission method: RS-485; Data length: 7 or 8 bits, Stop bits: 1 or 2 bits; Parity: None/Odd/Even, Transmission speed: 4,800 bps ~115,200 bps; RS-485: 5 PIN removal terminal
Extension interface: 1. Update firmware version; 2. The slot for program copy card
5 PIN removal terminal Include 24V DC input and RS-485 communication input

Electrical Specifications

Specifications TP02G-AS1
Communication interface COM1: RS-232 COM2: RS-485
Waterproof class of front panel IP66 / NEMA4X / UL Type4X (Indoor use only)
Operating temperature for hardware 0 ~ 50°C; 20 ~ 90%RH (non-condensing)
Storage temperature for hardware -20~60°C
Vibration 5Hz≤f<9Hz = Continuous: 1.75mm / Occasional: 3.5mm; 9Hz≤f≤150Hz = Continuous: 0.5g / Occasional: 1.0g
Shock 15g peak, 11ms duration, half-sine, three shocks in each direction per axis, on 3 mutually perpendicular axes (total of 18 shocks)
Radiated emission CISPR11, Class A
Electrostatic discharge immunity EN61000-4-2
Radiated immunity EN61000-4-3
Electrical fast transient EN61000-4-4
Altitude 0~2000 meters
Weight/dimensions 0.24kg; 147 × 97 × 35.5mm (Width(W) × Height(H) × Deep(D))
Cooling method Natural air cooling

Password Function

1. If the user forgot the password, the password can be cleared by using the following code: 8888. This universal code will clear the password and all TP02 series internal programs. The TP02 series will be reset to the factory settings by using this code also. Please pay close attention when using it.

2. The password can be the alphabet from A to Z or the number from 0 to 9. But it must use the function keys F0 ~ F9 to input the password characters. Please refer to the following table:

  • F0: scrolls in a loop as follows 0→A→B→C→D→E→F→0.
  • F1: scrolls in a loop as follows 1→G→H→I→J→K→1.
  • F2: scrolls in a loop as follows 2→L→M→N→O→P→2.
  • F3: scrolls in a loop as follows 3→Q→R→S→T→U→ V→3.
  • F4: scrolls in a loop as follows 4→W→X→Y→Z→4.
  • F5: It just can be used to be constant 5.
  • F6: It just can be used to be constant 6.
  • F7: It just can be used to be constant 7.
  • F8: It just can be used to be constant 8.
  • F9: It just can be used to be constant 9.

Hardware Operation

When the user wants to startup TP02 series, a 24V DC power is needed. After applying 24V DC power to TP02 series, it will enter into the startup display and then enter the user-designed program. Pressing Esc key and holding on for 5 seconds can return to system menu. There are five selections in the system menu and are described below.

Selections Explanation
Download program Use the connection cable (UC-PRG020-12A (2M)) to connect the TP02 serial communication port RS-232 to a PC. Then use the TPEditor/DIAScreen software to download an application program to TP02.
Upload program Use the connection cable (UC-PRG020-12A (2M)) to connect the TP02 serial communication port RS-232 to a PC. Then use the TPEditor/DIAScreen software to upload an application program from TP02.
Copy program Transfer a program between two TP02 units. 1: transmit programs; 2: receive programs. When transmit programs and data between two TP02 units. Set one TP02 to “Receive Program” mode and the other TP02 to "Transmit Program" mode. Please use twisted pair wires to connect the two units via the RS-485 ports.
TP02 settings There are 8 items that used to modify TP02 system settings:
  1. Communication protocol: Setting the address of TP02, the control port of PLC, and the communication string for either RS-232 or RS-485.
  2. Contrast: Adjust the contrast of LCM display screen.
  3. Back-light: adjust the automatic turn off time of LCM. Setting range is 00 ~ 99 minutes. If set to 00, the LCM Back-light will not turn off.
  4. Buzzer: Used to set the buzzer sound, normal mode or quiet mode.
  5. Language setting: Used to set the displayed language. English, Traditional Chinese, Simplified Chinese or user defined language.
  6. Password setting: Used to set, enable, and disable the password function. If the password function is enabled, it will require the user to input a password before entering any system menu. The factory password is 1234.
  7. Startup display: Used to select the TP02 startup display. User can select “user defined” to use the file that designed by TPEditor/ DIAScreen and download to TP02.
  8. Comm. indicator: The user can determine if the RS-232 and RS-485 LEDs will blink or not during communication.

Communication Connection

There are two methods to connect to PLC:

  1. Using TP02 serial communication port (COM1) RS-232: set 8-pin DIP switch to RS-485 mode and connect the cable (UC-MS010-02A(1M)/UC-MS020-01A(2M)/UC-MS030-01A(3M)) to program communication I/O RS-232C of PLC.
  2. Using extension communication port (COM2) RS-485: set 8-pin DIP switch to RS-485 mode and connect 5-pin removal terminal of extension communication port to RS-485 of PLC with twisted pair.

Diagrams illustrating the connection of a PC to TP02G via UC-PRG020-12A (2M) / UC-PRG030-10A (3M) cables.

Diagrams illustrating the connection of a DVP-PLC to TP02G via UC-MS010-02A(1M)/UC-MS020-01A(2M)/UC-MS030-01A(3M) cables.

Diagrams illustrating the connection of an AH-PLC to TP02G via UC-MS030-03A(3M) cable.

Diagrams illustrating the connection of an AS-PLC to TP02G via DB9 (MALE) to DB9 (FEMALE) standard cable.

Models: TP02G-AS1, TP-0143030-01, TP02G-AS1 HMI Text Panel, TP02G-AS1, HMI Text Panel, Text Panel

File Info : application/pdf, 7 Pages, 5.46MB

PDF preview unavailable. Download the PDF instead.

Delta-TP02G-AS1-TP-Series-HMI-Text-Panel-Instruction-Sheet

References

Acrobat Distiller 19.0 (Windows)

Related Documents

Preview Delta TP02G-AS1 Operator Panel: Instruction Sheet and Specifications
A comprehensive guide to the Delta TP02G-AS1 operator panel, covering installation, hardware operation, panel functions, specifications, password management, and communication connections. Includes detailed diagrams and safety warnings.
Preview Delta DOP-107EG HMI: Instruction Sheet and Hardware Specifications
Comprehensive guide to the Delta DOP-107EG Human Machine Interface (HMI), covering general precautions, installation, wiring, pin assignments, and detailed hardware specifications for industrial automation.
Preview DELTA DOP-W Series HMI: Installation, Operation, and Specifications
Comprehensive instruction sheet for DELTA DOP-W series HMI products (DOP-W105B, DOP-W127B, DOP-W157B), covering safety precautions, wiring, pin definitions, dimensions, and detailed specifications.
Preview Delta DOP-107SV HMI Touch Panel Instruction Sheet
Instruction sheet for the Delta DOP-107SV High Color Wide Screen User-Friendly HMI Touch Panel, detailing general precautions, communication port pin assignments, part descriptions, mounting dimensions, installation and wiring, and hardware specifications.
Preview DELTA TP70P-22XA1R Instruction Sheet - Industrial HMI Module
Official instruction sheet for the DELTA TP70P-22XA1R Open Type HMI module. Provides details on installation, assembly, dimensions, technical specifications, I/O configuration, pin definitions, compliance, and global contact information.
Preview Delta DOP-B10S615/DOP-B10E615 HMI Instruction Sheet
Instruction sheet for Delta DOP-B10S615 and DOP-B10E615 Human Machine Interface (HMI) products, detailing installation, safety precautions, serial communication pin definitions, parts identification, and technical specifications.
Preview Delta Industrial Automation Products Catalog: PLCs, HMIs, Servo Drives, and More
Comprehensive catalog of Delta industrial automation products, including Programmable Logic Controllers (PLCs) from various series (DVP, AS, AH, ES, EX, TP), Human Machine Interfaces (HMIs), AC servo drives and motors, industrial PCs, Ethernet switches, and accessories. Features detailed specifications, applications, and pricing.
Preview Delta DOP-3S07S3E2 / DOP-3S10S3E2 HMI Instruction Sheet and Specifications
Detailed instruction sheet and technical specifications for Delta DOP-3S07S3E2 and DOP-3S10S3E2 Human Machine Interface (HMI) panels, covering general precautions, installation, wiring, pin assignments, part descriptions, and hardware specifications.