Philips Dynalite DDNP1501 Network Power Supply
Installation Instructions
Safety and Installation Requirements
⚠ Devices must be installed in an approved enclosure by a qualified electrician in accordance with all national and local electrical and construction codes and regulations.
Product Overview and Specifications
The DDNP1501 is a Network Power Supply unit from Philips Dynalite.
Physical Dimensions:
- Width: 105 mm (4.1 in)
- Height: 59 mm (2.3 in)
- Depth: 75 mm (2.9 in)
Environmental Conditions:
- Operating Temperature: 0°C to 40°C (32°F to 104°F)
- Humidity: ≤ 95% (non-condensing)
Certifications and Ratings:
- IEC Pollution Degree: II
- IEC Overvoltage Category: III
- Compliance Marks: CE, UKCA, C-Tick, G-Mark
Wiring and Connection Details
Diagram 2A: RS-485 DyNet Cable Connection
The RS-485 DyNet communication bus requires specific wiring:
- Cable Type: RS-485 DyNet
- Wire Gauge: 0.3-2.5 mm² (22-12 AWG)
- Torque: 0.4 Nm (3.5 Lb-in)
- Current Rating: ≤ 2A
- Connections:
- Shield (Shld)
- Ground (Gnd)
- Data+ (D+)
- Data- (D-)
- +12V
Diagram 2B: Connection to Control Unit
Connect the RS-485 DyNet cable from the DDNP1501 to the designated port on the control unit.
Diagram 3: Power Input and Output Terminals
Power Input:
- Voltage: 100-240 V~
- Current: 0.5 A
- Terminals: L (Line), N (Neutral), E (Earth/Ground)
Power Output:
- Voltage: 15V---
- Current: 1A (@ 120V~) / 1.5A (@ 230V~)
- Terminals: +12V, D-, D+, GND, SHLD
Diagram 4: General Wiring Connections
Ensure appropriate wire gauge (≤ 2.5 mm², 13+ AWG) is used for connections to L, N, and E terminals.
Diagram 5: RS-485 DyNet Cable Termination
Properly terminate the RS-485 DyNet cable to the device's input terminals.
Diagram 6: Terminal Block Connections
Securely connect wires to the appropriate terminal blocks on the unit.