Trane & Mitsubishi Electric City Multi Model Number Reference Guide
Outdoor Unit Model Number Reference Guide
This guide provides a breakdown of the model number structure for Trane and Mitsubishi Electric's City Multi outdoor units.
CITY MULTI R2-SERIES (HEAT RECOVERY)
- TURY (Air-source): Targeted for commercial applications. Provides simultaneous cooling & heating through a branch circuit (BC) controller. Capacity: 6-28 tons. Requires branch circuit controller.
- TQRY (Water-source): Targeted for commercial applications. Provides simultaneous cooling & heating through a branch circuit (BC) controller. Capacity: 6-28 tons. Requires branch circuit controller.
Features for R2-Series:
- Provides simultaneous cooling & heating.
- Three-phase power.
- Connect up to 50 indoor units with 50-150% connected capacity allowed.
- Capacity: 6-28 tons.
CITY MULTI Y-SERIES (HEAT PUMP)
- TUHY (Air-source): Targeted for commercial applications. All indoor units operate in the same mode. Capacity: 6-36 tons.
- TQHY (Water-source): Targeted for commercial applications. All indoor units operate in the same mode. Capacity: 6-36 tons.
Features for Y-Series:
- All indoor units operate in the same mode.
- Three-phase power.
- Connect up to 50 indoor units with 50-130% connected capacity allowed.
- Capacity: 6-36 tons.
S-SERIES
- TUMY (Heat Pump): Targeted for light commercial or large-scale residential applications. All indoor units operate in the same mode. Single-phase power. Connect up to 12 indoor units with 50-130% connected capacity allowed. Capacity: 3-5 tons. H2i® models: 3 and 4 ton capacities.
Features for S-Series:
- All indoor units operate in the same mode.
- Single-phase power.
- Connect up to 12 indoor units with 50-130% connected capacity allowed.
- Capacity: 3-5 tons.
- H2i® models available.
NV-SERIES
- NTXSP (Heat Pump): Targeted for residential applications. Capacity: 0.75-5 tons. Single-phase power. Range from 1-to-1 systems to multi-zone systems with up to 8 zones.
- NTYSS (Cooling Only): Targeted for residential applications. Capacity: 0.75-5 tons. Single-phase power. Range from 1-to-1 systems to multi-zone systems with up to 8 zones.
- NTXM (Multi-zone Heat Pump): Targeted for residential applications. Capacity: 0.75-5 tons. Single-phase power. Range from 1-to-1 systems to multi-zone systems with up to 8 zones. Note: Simultaneous cooling & heating is not available with NTXM Branch Box systems.
Features for NV-Series:
- Targeted for residential applications.
- Capacity: 0.75-5 tons.
- Single-phase power.
- Supports 1-to-1 systems to multi-zone systems with up to 8 zones.
P-SERIES
- TRUZ (Heat Pump): Targeted for residential and light commercial applications with 24/7 cooling requirements. Capacity: 1-3.5 tons. Single-phase power. Designed for 1-to-1 installations.
- TRUY (Cooling Only): Targeted for residential and light commercial applications with 24/7 cooling requirements. Capacity: 1-3.5 tons. Single-phase power. Designed for 1-to-1 installations.
Features for P-Series:
- Targeted for residential and light commercial applications.
- Suitable for 24/7 cooling requirements.
- Capacity: 1-3.5 tons.
- Single-phase power.
- Designed for 1-to-1 installations.
Model Number Breakdown (Example: TURYP1683AN40AN)
BRAND NAME: T = Trane
CONFIGURATION: U = Air Cooled
UNIT TYPE: R = Heat Recovery
PERFORMANCE: P = Standard Efficiency
VOLTAGE: 3 = 208/230V/3P/60Hz
MODULE SIZE: A = Single
GENERATION CODE: N = 9th Generation
REFRIGERANT: 4 = R410a
MAJOR CHANGE: 0 = 1st Generation
CAPACITY (BTUH): 168 = 168,000
MINOR CHANGE: A = 1st Generation
COIL COATING: N = Standard (No Coating)
Indoor Unit Model Number Reference Guide
This guide provides a breakdown of the model number structure for Trane and Mitsubishi Electric's City Multi indoor units.
Model Number Breakdown (Example: TPKFYP024BM140A)
BRAND NAME: T = Trane
MODEL FAMILY: P = Packaged AC
APPLICATION: K = Wall Mounted
UNIT TYPE: FYP = Indoor Unit
CAPACITY (BTUH): 024 = 24,000
CONFIGURATION: BM = Small Cabinet (Wall Mounted, 1 way cassette)
UNIT TYPE: M = Main
VOLTAGE: 1 = 208/230V/1P/60Hz
GENERATION: 0 = 1st Generation
MINOR DESIGN SEQUENCE: A = Original Model
REFRIGERANT: 4 = R410a
BC Controller Model Number Reference Guide
This guide provides a breakdown of the model number structure for Trane and Mitsubishi Electric's City Multi BC Controllers.
Model Number Breakdown (Example: TCMBM0108JA11N4)
BRAND NAME: T = Trane
MODEL NUMBER: CMB = Branch Controller
UNIT TYPE: M = Main
# OF BRANCHES: 0108 = 8 Branches
UNIT APPLICATION: JA1 = JA1 Main
VOLTAGE: 1 = 208/230V/1P/60Hz
GENERATION CODE: N = 9th Generation
REFRIGERANT: 4 = R410A