Lennox Blower Replacement Kit Installation Instructions

Document Number: 508432-01

Revision Date: 04/2025

Supersedes: 05/2024

Kit Part Numbers: 626031-01 & -02; 31A56 & 57

For Use With Units: LGM/LGT092-150

Shipping and Packing List

Package 1 of 1 contains:

Ordered and shipped separately for J Volt Units:

Installation Steps Overview

  1. Open access panels. See Figure 1.
  2. Disconnect B3 Modbus connection and PT6 connection (LGM only) in the blower section. See Figure 2.
  3. Disconnect P48 in the controls area. See Figure 4.
  4. Cut wire ties where necessary and pull P48 wiring harness from the control area into the blower section.
  5. Use the handle on the blower assembly to slide the assembly out of the unit.
  6. Note the heat exchanger dimples (tri-dimple or offset-dimple) to select the appropriate replacement limit switches.
  7. Install the replacement blower assembly flanges into rails on the blower deck and secure with four screws.
  8. Uncoil the P48 wiring harness secured to the replacement blower housing.
  9. Route the P48 harness end through the unit to the control area.
  10. Connect B3 Modbus and PT6 connections as shown in Figure 2.
  11. Bundle harnesses and use wire ties to secure kit harnesses to unit harnesses.

Firmware Update

Required before proceeding:

  1. Update the Unit Controller firmware to version 09.02.0320 or newer.
  2. Set configuration ID 1, (7) System Blower Sub-Type, to “5” - Direct-Plus blower MODUS. Use the menu path: RTU MENU > SETUP > INSTALL.

Application

This kit replaces a 450mm blower with a 500mm blower. The 31A56 is used on Y-volt units and the 31A57 is used on G- & J-Volt units.

Replace Blower Motor

Important Note: Direct-drive motors may not stop immediately when power is interrupted to the Unit Controller. Always disconnect unit power before opening the blower compartment. The Controller's digital inputs must be used to shut down the blower. Refer to the Unit Controller manual for specific operation sequences.

  1. Disconnect electrical power to the unit. Wait five minutes before continuing service procedures to allow internal capacitors time to fully discharge and avoid electrical shock.
  2. Remove four screws securing the blower assembly to the unit. See Figure 5.
  3. If the unit was equipped with a blower proving switch, remove the switch from the existing blower housing and attach it to the replacement blower assembly in the same manner.
  4. For LGM Units Only: Disconnect the pressure tubing from the PT6 pressure sensor. Remove two screws and detach the sensor/bracket assembly (noting its orientation) from the existing blower housing. Install the sensor/bracket onto the replacement blower assembly and reattach the tubing.

Install New Limit Switch

Move the limit switch from the left side of the blower to the right side of the blower. See Figure 6.

  1. Remove and retain screws securing the limit switch on the left side of the blower assembly. Discard the old limit switch.
  2. Remove and retain screws securing the patch plate on the right side of the blower deck.
  3. Place the patch plate over the opening left by the discarded switch on the left side of the blower. Secure with retained screws.
  4. Select the replacement switch based on the heat exchanger type (see Figure 5 for heat exchanger dimples):
    • Tri-Dimple Heat Exchangers (See Figure 7):
      • Std. Heat (6 tubes; 150°F) - Part Number: 49L8901
      • Med. Heat (9 tubes; 175°F) - Part Number: 49L8601
      • High Heat (11 tubes; 185°F) - Part Number: 100847-10
    • Offset-Dimple Heat Exchangers (See Figure 8):
      • Std. Heat (6 tubes; 150°F) - Part Number: 100847-04
      • Med. Heat (9 tubes; 190°F) - Part Number: 100847-12
      • High Heat (11 tubes; 185°F) - Part Number: 100847-10
  5. Install the selected switch on the right side of the blower and secure with retained screws.
  6. Cut the wire ties securing the discarded switch. Route wires to the replacement switch on the right side of the blower and connect them to the terminals.

Install T4 Transformer (575 / J-Volt Only)

  1. Install the bracket in the unit (provided in some units). Secure with provided hardware. See Figure 9.
  2. Secure the transformer and fuses onto the bracket.

Connect Wiring

  1. G-Volt Units: Connect the J48 power harness to P48 (previously routed from the replacement blower). See Figure 4.
  2. J-Volt Units: Remove and discard the existing J48 harness routed to TB13. See Figure 4. Make kit harness connections as shown in Figure 10.

Safety Warnings and Cautions

⚠️ WARNING

To prevent serious injury or death:

  1. Lock-out/tag-out procedures must be followed before performing maintenance.
  2. If system power is required (e.g., for smoke detector maintenance), disable power to the blower, remove the fan belt where applicable, and ensure all controllers and thermostats are set to the “OFF” position before performing maintenance.
  3. Always keep hands, hair, clothing, jewelry, tools, etc., away from moving parts.

General Installation Warning: Improper installation, adjustment, alteration, service, or maintenance can cause property damage, personal injury, or loss of life. Installation and service must be performed by a licensed professional installer (or equivalent), service agency, or the gas supplier.

⚠️ CAUTION

As with any mechanical equipment, personal injury can result from contact with sharp sheet metal edges. Be careful when handling this equipment.

Diagram Descriptions

Figure 1: Unit Access Panels

Diagram showing the blower access door and control access area of the unit.

Figure 2: Blower Section Wiring

Diagram of the blower section, illustrating connections for the PT6 pressure sensor, B3 Modbus control connector, and routing of P48 power wiring. It shows the PT6 pressure sensor connection and the B3 Modbus connector, with instructions to bundle and secure excess P48 power wiring.

Figure 3: PT6 Sensor for LGM Units

Diagram showing the PT6 sensor and mounting bracket specifically for LGM units. It details the pressure tubing connection, bracket screws, and the PT6 pressure sensor itself, mounted on a bracket.

Figure 4: Control Area Wiring

Diagram of the control area, showing wiring connections including TB13, P48, and connections to the blower. It illustrates the P48 connection point and the TB13 terminal block, with a line indicating the path "TO BLOWER".

Figure 5: Blower Assembly Removal

Illustration depicting the blower assembly being slid out of the unit. Labels point to the blower assembly, PT6 pressure sensor, and the optional blower proving switch. It also indicates the location of screws (2 on each side) to be removed for detachment. A note emphasizes the importance of identifying heat exchanger dimples (tri-dimple or offset-dimple) to select the correct limit switch.

Figure 6: S10 Limit Switch Installation

Diagram illustrating the process of removing and installing the S10 limit switch. It shows the removal of the existing limit switch and covering the opening with a patch plate from the right side of the blower, and then installing the new limit switch provided in the kit.

Figure 7: Tri-Dimple Heat Exchanger

Illustration of a heat exchanger with a tri-dimple pattern.

Figure 8: Offset-Dimple Heat Exchanger

Illustration of a heat exchanger with an offset-dimple pattern.

Figure 9: T4 Transformer Installation

View from the control/compressor access area showing the T4 transformer (ordered separately), the mounting bracket (factory option), and F27 fuses/holders (quantity 3 on LGT). It indicates the back side of the disconnect box.

Figure 10: J-Volt Harness Connections

Wiring diagram for J-Volt harness connections. It shows connections from J48, J293/P293, F27 (Line and Load), and the T4 transformer (Input and Output) to TB13 (L1, L2, L3 in the control box) and P48 (to blower).
Models: 626031-01, 626031-01 Blower Replacement Kit, Blower Replacement Kit, Replacement Kit

PDF preview unavailable. Download the PDF instead.

508432-01c Adobe PDF Library 17.0 Adobe InDesign 20.1 (Windows)

Related Documents

Preview Lennox Blower Assembly Replacement Kit Installation Instructions
Detailed installation instructions for the Lennox Blower Assembly Replacement Kit used with LGM/LCM092-150U units. Includes shipping and packing list, application details, and step-by-step installation procedures.
Preview Lennox EL297UHVK Furnace Wiring Diagrams Addendum
This document provides addendum information and wiring diagrams for the Lennox EL297UHVK furnace, supplementing installation instructions.
Preview Lennox Core Unit Controller (M4) Firmware Update Installation Instructions
Step-by-step guide for installing firmware updates on the Lennox Core Unit Controller (M4) using a USB flash drive and the CORE Service app. Includes instructions for preparing the USB drive, updating firmware, and managing system profiles.
Preview Lennox Integrated Control Replacement Kit 23C48 Installation Instructions
Installation guide for the Lennox Integrated Control Replacement Kit 23C48, providing step-by-step instructions and wiring diagrams for single-stage furnaces with constant torque indoor blower motors.
Preview Lennox Ignition Control Replacement Kit Installation Instructions (19W94)
Comprehensive installation guide for the Lennox Ignition Control Conversion Kit 19W94, detailing the process for replacing ignition controls in 80MGF(X)-1/3 and 80MGF(X)/G24M(X)-2/4/6 gas units. Includes safety precautions, packing list, step-by-step instructions, wiring diagrams, and operational sequences.
Preview Float Switch Kit Installation Instructions for Lennox Rooftop Units
Comprehensive installation guide for the Float Switch Kit (602799-08; 21Z07) designed for Lennox LG/LC/LH/LD/SG/SC 024-360 series rooftop units. Covers application, parts, installation steps, and unit controller configuration for M2, M3, and M4 controllers.
Preview Installation Instructions for Cold Weather Kit for Packaged Units
Detailed installation instructions for the Cold Weather Kit, designed to enable gas valve operation in low outdoor temperatures for various Lennox packaged HVAC units. Includes parts lists, compatibility tables, and step-by-step wiring and mounting procedures for multiple unit series.
Preview Lennox LGT/LCT Series Rooftop Unit Installation Instructions
Comprehensive installation manual for Lennox LGT/LCT series packaged rooftop units (7.5 to 12.5 tons). Covers safety warnings, unit dimensions, parts arrangement, rigging, electrical connections, gas piping, condensate drains, high altitude derate, mobile app usage, cooling and heating operation, service procedures, and troubleshooting.