SJE VERTICALMASTER® PUMP SWITCH

Mechanically-Activated Switch for Limited Space Applications

The SJE VerticalMaster® mechanically-activated pump switch is designed for direct control of pumps up to 1/2 HP at 120 VAC and 1 HP at 230 VAC for:

It works well in small sump chambers, effluent applications, and laundry trays, as well as in large tanks.

The SJE VerticalMaster® pump switch is not sensitive to turbulence. It is available for pump down applications only.

FEATURES

PUMP DOWN / ON POSITION

Diagram shows contacts closed with yoke.

PUMP DOWN / OFF POSITION

Diagram shows contacts open with yoke.

OPTIONS

This switch is available:

UL Recognized for Water & Sewage

SJE RHOMBUS.

Part # Description (Pump Down Only) Shipping Weight
1003590* 10VM1WP 1.73 lbs.
1003772 10VM2WP 1.77 lbs.
1003776 10VMWOP 1.65 lbs.
1003769 15VM1WP 2.08 lbs.
1003773 15VM2WP 2.12 lbs.
1003777 15VMWOP 2.00 lbs.
1003770 20VM1WP 2.43 lbs.
1003774 20VM2WP 2.47 lbs.
1003778 20VMWOP 2.35 lbs.
1003771 30VM1WP 3.13 lbs.
1003775 30VM2WP 3.17 lbs.
1003779 30VMWOP 3.05 lbs.

*This item is an SJE Rhombus Quick Ship product which normally ships within 1 business day from receipt of order at no additional charge.

1 = 120VAC, 2 = 230VAC, WP = With Plug, WOP = With Out Plug

NOTE: Descriptions are grouped by cable length measured in feet (10, 15, 20, 30).

MOUNTING BRACKET and HOSE CLAMP are standard.

PACKAGING: Boxed - Standard

ADDITIONAL CABLE: Longer cable lengths available.

SPECIFICATIONS

PUMPING RANGE: 0.75 to 6.5 inches (2 cm to 17 cm)

CABLE: flexible 16 gauge, 2 conductor (UL, CSA) SJOW or SJTOW, water-resistant (CPE).

MOUNTING BRACKET AND CLAMP: stainless steel

LIFT ROD: injection molded acetal plastic

FLOAT STOP: neoprene

SWITCH AND FLOAT HOUSING: high impact, corrosion resistant, PVC housing for use in sewage and non-potable water up to 125°F (52°C)

Overall dimensions: 12 inch high x 5 inch x 3 inch wide (30.5 cm x 12.7 cm x 7.6 cm)

Switch housing dimensions: 2 inch high x 2.8 inch diameter (5 cm x 7.1 cm)

Float housing dimensions: 2.3 inch high x 2.8 inch diameter (5.8 cm x 6.9 cm)

ELECTRICAL:

Voltage 50Hz/60Hz Max. Pump Run Current Max. Pump Start Current Recommended Pump HP
Single Phase 120 VAC 13 amps 60 amps 1/2 HP or less
230 VAC 12 amps 60 amps 1 HP or less

NOTE: This switch must be used with pumps that provide integral thermal overload protection.

A Pump Switch is designed for Horsepower (HP) rated loads and is not suitable for control (pilot duty) applications. It will fail prematurely when switching loads less than 1 Amp at 120 VAC. Select a float switch from our Control Switch offering for control applications.

OTHER INFORMATION

PUMP DOWN is normally open contacts for emptying.

DIRECT WIRING: Units used for direct wiring (without plug) may be used in either 120 VAC or 230 VAC applications within specified amp ratings.

California Prop 65 requires the following: WARNING Cancer and Reproductive Harm - www.P65Warnings.ca.gov

For more information, visit www.sjerhombus.com or email: customer.service@sjeinc.com. Call Toll Free 888-342-5753.

PDF preview unavailable. Download the PDF instead.

9500108I VM Adobe PDF Library 16.0 Adobe InDesign 16.4 (Windows)

Related Documents

Preview SJE Rhombus Control Panel Catalog
Explore the comprehensive range of SJE Rhombus control panels, including EZ Series, Build-A-Panel Plus, and In-Site CL Bluetooth models for single-phase simplex and duplex pump control and system monitoring. Find detailed product information, ordering guides, and specifications.
Preview SJE VERTICALMASTER 3 PLUS Float Switch Installation Instructions
Comprehensive installation guide for the SJE VERTICALMASTER 3 PLUS Float Switch, covering safety warnings, product features, step-by-step installation, maintenance, and warranty information.
Preview SJE PumpMaster® Pump Switches: Mechanically-Activated Wide-Angle Switches
Detailed information on SJE PumpMaster®, PumpMaster® Plus, and PumpMaster® SPDT mechanically-activated wide-angle pump switches for water and sewage applications. Features, specifications, part numbers, and electrical ratings.
Preview SJE Rhombus IFS In-Site Single Phase Simplex Control Panel for Pump Monitoring
Explore the SJE Rhombus IFS In-Site Single Phase Simplex control panel, designed for efficient pump control, system monitoring, and event logging in water and wastewater applications. Features include timed/demand dose, C-Level™ sensors, and USB data logging.
Preview Tank Alert 4X Alarm System - SJE Rhombus
Easy-to-install liquid level alarm system with NEMA 4X enclosure for indoor or outdoor use. Monitors liquid levels in various water applications with a high or low level alarm.
Preview SJE Rhombus Installer Friendly Series (IFS) In-Site Single Phase Duplex Pump Control System
Explore the SJE Rhombus Installer Friendly Series (IFS) In-Site Single Phase Duplex control panel for water and sewage applications. Features demand or timed dose control, system monitoring, event logging via USB, and an intuitive touch pad interface.
Preview SJE Rhombus Installer Friendly Series (IFS) Three Phase Simplex Pump Control Panel
Learn about the SJE Rhombus Installer Friendly Series (IFS) Three Phase Simplex control panel, a versatile system for demand or timed dose pump control and monitoring in water and sewage applications. Features include C-Level™ sensor compatibility, touch pad interface, and various configuration options.
Preview SJE Rhombus Troubleshooting Guide: Solutions for Pump and Control Systems
Comprehensive troubleshooting guide for SJE Rhombus pump and control systems, covering common issues, installation tips, and detailed diagnostics for various models.