SJE Rhombus Installer Friendly Series (IFS) Three Phase Simplex
Demand Dose or Timed Dose, Float or C-Level™ Sensor Controlled System for Pump Control and System Monitoring
Product Overview
The IFS simplex control panel from SJE Rhombus is designed for efficient pump control and system monitoring in water and sewage applications. It manages a single 208/240/480 VAC three-phase pump. The panel features an intuitive touch pad interface on the inner door for easy programming and monitoring, allowing for field conversion between timed dose and demand dose modes. It is also compatible with the EZconnex® float system and the C-Level™ sensor for continuous level monitoring.
The C-Level™ sensor provides continuous level data to the panel, enabling pump activation levels to be adjusted via the touch pad. The C-Level™ CL40 sensor operates within a range of 3-39.9 inches (7.6-101.3 cm), while the C-Level™ CL100 sensor operates from 3-99.5 inches (7.6-252.7 cm).
Touch Pad Features
- A. Level Status Indicators: Illuminate to show activated floats or set points. An alarm is triggered if a float operates out of sequence.
- B. HOA (Hand-Off-Automatic) Buttons: Control the pump's operating mode with clear indication. In Hand mode, the system defaults to Automatic operation once the stop level or redundant off level is reached.
- C. Pump Run Indicator: Illuminates when the pump is activated.
- D. LED Display: Provides comprehensive system information, including: level in inches or centimeters (for C-Level™ sensor), operating mode, pump elapsed time (hh:mm), event/cycle counts, alarm counter, float error count, timed dose override counter (for timed dose only), and ON/OFF times (for timed dose only).
- E. NEXT Push Button: Used to cycle through the information displayed on the LED screen.
- F. UP and SET Push Buttons: Allow users to set pump ON/OFF times (for timed dose) and activation levels (for C-Level™ sensor).
Key Components
The IFS panel houses several key components for robust operation:
- 1. Enclosure Base: A NEMA 4X rated enclosure made of ultraviolet-stabilized thermoplastic, measuring 14 x 12 x 6 inches (35.56 x 30.48 x 15.24 cm), with removable mounting feet for versatile installation.
- 2. Red LED Beacon: Offers a 360° visual alert for alarm conditions.
- 3. Exterior Alarm Switch: A Test/Normal/Silence switch allows for testing the horn and light, and silencing the horn during an alarm. The alarm automatically resets when the condition is cleared.
- 4. Motor Protective Switch: Provides adjustable overload protection, branch circuit protection, and acts as a pump disconnect.
- 5. IEC Motor Contactor: Manages pump operation by switching electrical lines.
- 6. Multi-tap Transformer: Converts primary voltages (208/240/480 VAC) to 120 VAC for control and alarm functions.
- 7. Float Connection Terminal Block: For connecting float switches.
- 8. Control Power Indicator/Fuse Light: Confirms control power presence; an alarm sounds if the control fuse is blown.
- 9. Alarm Power Indicator/Fuse Light: Confirms alarm power presence.
- 10. Incoming Power Connection Terminal Block: For main power input.
- 11. Terminal Block Float Wiring Label: Guides float wiring connections.
- 12. Ground Lugs: For proper grounding.
- 13. Alarm Horn: Emits an audible alarm (83-85 decibel rating) for critical events (not visually depicted).
Note: Component layout and enclosure size may vary based on selected options, voltage, and amp ratings. Schematic/Wiring Diagrams and Pump Specification Labels are located inside the panel.
The C-Level™ sensor is covered by US Patent No. 8,336,385; 8,567,242; 8,650,949. Canadian patents and trademarks also apply.
Configuration and Options
The Installer Friendly Series (IFS) Three Phase Simplex panel offers extensive customization through its pricing worksheet. Key configuration parameters include:
Configuration Parameter | Selection | Description |
---|---|---|
Control Panel | IFS | Installer Friendly Series |
Model Type | 5 | Three Phase Simplex (includes Option 8AC as standard) |
Alarm Package | 1 | Alarm Package (includes test/normal/silence switch, fuse, red light, & horn) |
Enclosure Rating | W | Weatherproof, NEMA 4X (engineered thermoplastic) |
Pump Full Load Amps (FLA) | (Select range, e.g., 001 for 1.0-1.6 FLA, 101 for 1.6-2.5 FLA, up to 705 for 20.0-25.0 FLA) | Specifies the pump's full load amperage rating for appropriate protection. |
Float Switch Application | H | Floats - Pump Down (select Option 17 below) |
E | EZconnex® Float Switch System (select Option 33 or 34 below) | |
X | No Floats | |
C | C-Level™ Sensor (select Option 24 or 29). For high water alarm and/or redundant off, also select Option 3E and/or 4A & 4D. |
Detailed Options List:
Option Code | Description | Option Code | Description |
---|---|---|---|
3A | Alarm Flasher | 17C | Sensor Float® / Internally Weighted (per Float) - Mercury |
3B | Manual Alarm Reset | 17D | Sensor Float® / Externally Weighted (per Float) - Mercury |
3E | High Water Alarm Float (must also select Option 17) Only Available with Float Switch Application = C | 17G | SJE MilliAmpMaster™ / Pipe Clamp (per Float) - Mechanical |
4A | Redundant Off (must also select Option 4D if floats are required) | 17H | SJE MilliAmpMaster™ / Externally Weighted (per Float) - Mechanical |
4D | Redundant Off Float (must also select Option 4A and Option 17) | 17J | Sensor Float® / Pipe Clamp (per Float) - Mercury |
5A | Thermal Cutout/Heat Sensor Auto Reset (for pumps with thermal switch leads) | 24E | C-Level™ CL40 Sensor with 4' Vent Tube and 20' Cord |
5E | Seal Failure Circuit and Red Indicator (2 Wire) | 24F | C-Level™ CL40 Sensor with 4' Vent Tube and 40' Cord |
6A | Auxiliary Alarm Contact, Form C | 24G | C-Level™ CL40 Sensor with 8' Vent Tube and 20' Cord |
8AC | Display Board - Includes: ETM Counter, Events (Cycles) Counter, Alarm Counter (included as standard) | 24H | C-Level™ CL40 Sensor with 8' Vent Tube and 40' Cord |
10E | Lockable Latch - NEMA 4X | 24X | No C-Level™ CL40 Sensor |
10G | Lightning Arrestor | 29A | C-Level™ CL100 Sensor with 10' Vent Tube and 20' Cord |
10K | Anti-condensation Heater | 29B | C-Level™ CL100 Sensor with 10' Vent Tube and 40' Cord |
11C | Additional NEMA 1 Remote Alarm Panel (must also select Option 6A) | 29X | No C-Level™ CL100 Sensor |
11D | Additional NEMA 4X Remote Alarm Panel (must also select Option 6A) | 33D | EZconnex® 3-Port, 25', with 10' Floats (3) / Pipe Clamp |
16A | 10' Cord in Lieu of 20' Cord (per Float) | 33E | EZconnex® 3-Port, 50', with 10' Floats (3) / Pipe Clamp |
16B | 15' Cord in Lieu of 20' Cord (per Float) | 33G | EZconnex® 3-Port, 25', with 20' Floats (3) / Pipe Clamp |
16C | 30' Cord in Lieu of 20' Cord (per Float) | 33H | EZconnex® 3-Port, 50', with 20' Floats (3) / Pipe Clamp |
16D | 40' Cord in Lieu of 20' Cord (per Float) | 34D | EZconnex® 4-Port, 25', with 10' Floats (3) / Pipe Clamp, Sealing Plug |
34E | EZconnex® 4-Port, 50', with 10' Floats (3) / Pipe Clamp, Sealing Plug | ||
34G | EZconnex® 4-Port, 25', with 20' Floats (3) / Pipe Clamp, Sealing Plug | ||
34H | EZconnex® 4-Port, 50', with 20' Floats (3) / Pipe Clamp, Sealing Plug |
Note: Pump down applications only. Industry practices suggest that a secondary device, such as a float switch, be used for redundant activation of the high level alarm and pump shut off when using the C-Level™ sensor.
California Proposition 65 Warning: WARNING Cancer and Reproductive Harm - www.P65Warnings.ca.gov