Honeywell Home HZ322 TrueZONE® Panel

SUBMITTAL SHEET

Submittal Information

Job Name:
Engineer:
Mechanical Contractor:
Contractor's P.O. No.:
Representative:
Notes:
Model(s):HZ322Qty.Notes
HZ322K (Kit)Qty.Notes
Approval:
Service:
Tag No.:

Application

The HZ322 TrueZONE® panel controls:

Features

Specifications

Input Ratings: Voltage: 18-30 VAC 50/60 Hz powered by a transformer of 40 VA or more

Current Draw: Zone Panel: 7.5 VA max. All VA specifications at 24 VAC.

Wiring: 18- or 20-gauge solid (not stranded) wire

Humidity Ratings: 5% to 90% RH non-condensing

Temperature Ratings: Shipping: -20° to 150 °F (-29° to 66 °C); Operating: -40° to 165 °F (-40° to 74 °C)

Dimensions: See Figure 1.

Mounting: Mounts with either 2 screws at center line to mount onto 2 x 4, or with 4 screws at corners for wall mount.

Recommended Thermostats: See Table 1.

Recommended Dampers: See Tables 2 and 3. For maximum number of dampers per zone see Table 4.

Accessories: See Table 5.

Emissions: Complies with FCC Class B, part 15 requirements.

Figure 1. HZ322 TrueZONE Panel Dimensions

A rectangular white control panel with a digital display and several indicator lights. The panel has dimensions of 8 inches (203 mm) in width, 11-1/2 inches (292 mm) in height, and 1-55/64 inches (47 mm) in depth.

Table 1. Recommended thermostats

RedLINK thermostats:
TH8110R1008(wired or wireless*) Single stage heat and cooling. No IAQ.
TH8320R1003(wired or wireless*) 2H/2C heat pump without aux, 2H/1C with AUX or 2H/2C conventional. No IAQ.
TH8321R1001(wired or wireless*) 2H/2C heat pump without aux, 2H/1C with AUX or 2H/2C conventional. Hum, Dehum, or Vent control when used as wired thermostat, or wireless to a THM5421R1021 EIM. EIM wired to one of the zones.
THX9421R5021 Prestige(2-wire R and C. Wireless to THM4000R/HZ322 or THM5421R1021 EIM.*) 2H/2C heat pump without aux, 2H/1C with AUX or 2H/2C conventional. Hum, Dehum, and Vent control when used with THM5421R1021 EIM. EIM wired to one of the zones.
TH6320R1004 programmable FocusPRO(wireless*) 2H/2C heat pump without aux, 2H/1C with AUX or 2H/2C conventional. No IAQ.
TH5320R1002 non-programmable FocusPRO(wireless*) 2H/2C heat pump without aux, 2H/1C with AUX or 2H/2C conventional. No IAQ.
Wired thermostat:
Battery powered, hard-wired, or mechanicalThe HZ322 is compatible with most standard thermostats. The HZ322 allows you to choose stage 2 (and stage 3) control to be by thermostat, timer, or % of zones. If you want the thermostats to control staging, multi-stage thermostats are required.
Power stealing or phantom voltage (Lyric round, etc.)We do not recommend using thermostats that operate on phantom voltage or power-stealing mode with the HZ322. Some of these models have an optional C wire. Models tested with a C wire worked correctly with the HZ322.

* RedLINK models without IAQ control need a THM4000R1000 wireless adaptor. One adaptor can be used for up to 3 RedLINK thermostats on HZ322. If IAQ control is required from the TH8321R1001 or THX9421R5021 model, a THM5421R1021 is required for the thermostat controlling IAQ equipment. That EIM wires to one of the zones on the HZ322.

Table 2. Recommended residential dampers

ZoneTypeActuationRoundRectangular
ZoneSpring-open/power-closedARDZD
BypassPower-open/power-closedRRD
BarometricCPRDNone

Table 3. Recommended commercial dampers

ZoneTypeActuationRoundRectangular
ZonePower-open/power-closedMARDD2 with ML6161A2009*
BypassPower-open/power-closedMARD with SPCD2 with ML6161A2009* and SPC

*Or equivalent damper and actuator.

Table 4. Maximum dampers*

Ambient Temp.Maximum Damper VA per Zone
100°F (38°C)28.8
160°F (71°C)16.8

* Use an SDCR (Secondary Damper Control Relay) for additional dampers.

• Maximum dampers per panel is limited by transformer size.

• Ensure transformer is large enough to power the panel (7.5 VA) and dampers.

Table 5. Accessories

DescriptionPart Number
40 VA transformerAT140A1042*
75 VA transformerAT175A1008
Discharge air temperature sensor (DATS)C7735A1000*
Outdoor Air Sensor (wired)C7089U1006
Wireless adaptorC7089R1013 (THM4000R1000 wireless adaptor required)
Outdoor Air Sensor (wired)THM4000R1000
Secondary damper control relaySDCR

*Included in HZ322K kit.

Manufacturer Information

Resideo Technologies, Inc.

1985 Douglas Drive North, Golden Valley, MN 55422

1-800-468-1502

Website: www.resideo.com

©2021 Resideo Technologies, Inc. All rights reserved. The Honeywell Home trademark is used under license from Honeywell International, Inc. This product is manufactured by Resideo Technologies, Inc. and its affiliates.

Models: HZ322 TrueZONE Panel, HZ322, TrueZONE Panel

File Info : application/pdf, 4 Pages, 535.09KB

PDF preview unavailable. Download the PDF instead.

68-3072

References

Acrobat Distiller 21.0 (Windows)

Related Documents

Preview Honeywell Home HZ322 TrueZONE Professional Installation Guide
A comprehensive guide for the professional installation of the Honeywell Home HZ322 TrueZONE panel, covering specifications, wiring, configuration, and operation for HVAC zoning systems.
Preview Honeywell Home RedLINK Zoning Options Technical Reference Manual
This technical reference manual details Honeywell Home RedLINK zoning system configurations for various HVAC setups, including FocusPRO, Prestige, and VisionPRO thermostats. It covers system types, parts lists, and wiring diagrams for IAQ and non-IAQ applications.
Preview Honeywell Home HZ221 TrueZONE Zone Panel Installation Guide
Professional installation guide for the Honeywell Home HZ221 TrueZONE Zone Panel. Covers specifications, accessories, installation steps, wiring diagrams, operation, and warranty information.
Preview Honeywell Evohome Zoning System - Product Specification and Ordering Information
Detailed specifications, features, and ordering information for the Honeywell Evohome Zoning System, a smart home heating and cooling control solution. Learn about its advanced features, technical data, and compatible accessories.
Preview Honeywell Home C7835A1009 Discharge Air Temperature Sensor Installation and Operation
Installation and operation guide for the Honeywell Home C7835A1009 Discharge Air Temperature Sensor (DATS), a duct-mounted probe for HVAC capacity control. Includes wiring, troubleshooting, and resistance cross-reference.
Preview Honeywell Home PRO 1000 Series Non-Programmable Thermostat User Guide
Comprehensive guide to the Honeywell Home PRO 1000 Series non-programmable thermostat, covering product information, controls, operation, troubleshooting, and electrical specifications. Features include easy-to-understand controls, clear display indicators, and built-in compressor protection.
Preview Honeywell RLV3150 Electronic Thermostat: User Guide & Installation
Detailed user guide and installation instructions for the Honeywell RLV3150 Electronic Thermostat. Learn about application, controls, wiring, configuration, troubleshooting, specifications, and warranty.
Preview Honeywell Home T6 Pro Programmable Thermostat Installation Instructions
Comprehensive installation guide for the Honeywell Home T6 Pro Programmable Thermostat, covering setup, wiring, system configuration, and troubleshooting for models TH6320U2008, TH6220U2000, and TH6210U2001.