Schneider Electric MCSeT Series: Civil Engineering Guide

Digitally Native Upto 24 kV Air-insulated Switchgear With EvoPacT HVX Vacuum Circuit Breaker

Document Reference: BQT8706400-03

Publication Date: 06/2025

Legal Information

The information provided in this document contains general descriptions, technical characteristics and/or recommendations related to products/solutions. This document is not intended as a substitute for a detailed study or operational and site-specific development or schematic plan. It is not to be used for determining suitability or reliability of the products/solutions for specific user applications. It is the duty of any such user to perform or have any professional expert of its choice (integrator, specifier or the like) perform the appropriate and comprehensive risk analysis, evaluation and testing of the products/solutions with respect to the relevant specific application or use thereof.

The Schneider Electric brand and any trademarks of Schneider Electric SE and its subsidiaries referred to in this document are the property of Schneider Electric SE or its subsidiaries. All other brands may be trademarks of their respective owner.

This document and its content are protected under applicable copyright laws and provided for informative use only. No part of this document may be reproduced or transmitted in any form or by any means (electronic, mechanical, photocopying, recording, or otherwise), for any purpose, without the prior written permission of Schneider Electric.

Schneider Electric does not grant any right or license for commercial use of the document or its content, except for a non-exclusive and personal license to consult it on an "as is" basis.

Schneider Electric reserves the right to make changes or updates with respect to or in the content of this document or the format thereof, at any time without notice.

To the extent permitted by applicable law, no responsibility or liability is assumed by Schneider Electric and its subsidiaries for any errors or omissions in the informational content of this document, as well as any non-intended use or misuse of the content thereof.

SeT Series Overview

Featuring outstanding medium-voltage (MV) and low-voltage (LV) switchboards, motor control centres and power distribution solutions for high-performance power applications, Schneider Electric's SeT Series is optimized solutions based on high levels of safety and an optimized footprint. Built on a modular architecture and incorporating smart connected devices for maximum safety, reliability, performance and energy efficiency, the SeT Series is delivered to customers directly from Schneider Electric plants or via a global network of licensed partner panel builders, who are trained and audited to provide quality equipment and support.

Safety Information

Important Information

Read these instructions carefully, and look at the equipment to become familiar with the device before trying to install, operate, service, or maintain it. The following special messages may appear throughout this documentation or on the equipment to warn of potential hazards or to call attention to information that clarifies or simplifies a procedure.

The addition of this symbol ⚠️ to a "Danger" or "Warning" safety label indicates that an electrical hazard exists which will result in personal injury if the instructions are not followed.

This is the safety alert symbol ⚠️. It is used to alert you to potential personal injury hazards. Obey all safety messages that follow this symbol to avoid possible injury or death.

DANGER indicates a hazardous situation which, if not avoided, will result in death or serious injury.

WARNING indicates a hazardous situation which, if not avoided, could result in death or serious injury.

CAUTION indicates a hazardous situation which, if not avoided, could result in minor or moderate injury.

NOTICE is used to address practices not related to physical injury.

Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material.

A qualified person is one who has skills and knowledge related to the construction and operation of electrical equipment and its installation, and has received safety training to recognize and avoid the hazards involved.

Safety Precautions

Safety Rules

DANGER

HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH

Failure to follow these instructions will result in death or serious injury.

NOTICE

HAZARD OF INCORRECT HANDLING AND INADEQUATE STORAGE CONDITION

Failure to follow these instructions can result in equipment damage.

Cleaning Instructions

DANGER

HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH

Failure to follow these instructions will result in death or serious injury.

About the Document

Intended Use

This civil engineering guide describes air-insulated MV switchgear units of the MCSET.

The operations described in this guide should be performed by a qualified personnel with proven experience regarding:

This civil engineering guide is an integral part of the product and should be stored such that it is readily accessible at all times and can be used by persons who work on the switchgear. If the switchgear is relocated to another site, this guide should be passed on to the new operator along with the unit.

This guide does not describe every imaginable individual case or every customer-specific version of the product. For more information that is not included in this guide, contact Schneider Electric.

Validity Note

This guide is valid only for MCSeT cubicle. The design provides easy rack-in/rack-out operation without the need for a separate trolley. This MCSeT cubicle is an extension of the MCSeT range and delivers performances up to 24 kV, equipped with EvoPacT HVX VCB and CVX Contactor. It also has other functional trolley like the EvoPacT Metering Truck (MTX).

For product compliance and environmental information (RoHS, REACH, PEP, EOLI, and so on), go to the Green Premium page on the Schneider Electric website.

The information contained in this guide is likely to be updated at any time. Schneider Electric strongly recommends that you have the most recent and up-to-date version available on www.se.com/ww/en/download.

The technical characteristics of the devices described in this guide also appear online. To access the information online, go to the Schneider Electric home page at www.se.com.

Product Related Information

Air-insulated MV switchgear units of the MCSeT series are designed exclusively for switching and distributing electrical power.

DANGER

HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH

The MCSeT switchgear must be used only in scope of specified standards and specific technical data.

Failure to follow these instructions will result in death or serious injury.

Safety Provisions

Introduction

Before performing work on the cubicle, it is essential that you comply with the following instructions:

DANGER

HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH

Before removing covers and performing assembly or maintenance work:

Failure to follow these instructions will result in death or serious injury.

WARNING

HAZARD OF MOVING PARTS IN MECHANICAL DRIVES

Before performing mounting and maintenance work, comply with the below safety rules:

Failure to follow these instructions can result in death, serious injury, or equipment damage.

WARNING

HAZARD OF SHARP-EDGED SHEET METAL AND METAL PARTS

During installation and maintenance work, comply with the below safety rules:

Failure to follow these instructions can result in death, serious injury, or equipment damage.

Applicable Standards and Regulations

The applicable standards and regulations are as follows:

NOTE:

Behavior in case of Incidents or Accidents

If an internal arc fault occurs, the MCSeT switchgear is equipped with pressure relief absorbers or ports to help prevent the cubicles and switchgear from being blown off.

This civil engineering guide does not include information regarding the safety of buildings in case of internal faults (pressure load of the switchgear room and necessary pressure relief ports). Pressure calculations for switchgear rooms, including recommendations for pressure relief ports, are available upon request for a fee. For more details, contact Schneider Electric.

In case of fire or internal faults, toxic and caustic decomposition products are produced. Comply with the locally applicable accident and safety provisions. Make sure that the first-aid measures are taken in case of injury to persons.

Dimensions and Weights

Cubicles without Internal Arc Accessories

The list of cubicles with one Current Transformer (CT) per phase in the MCSET are:

Figure 1: Dimensions of Cubicles

NOTE: The images shown here are for illustration purpose only.

Table 1: Dimensions of I/F, BSC, BSR, and BME Cubicles

Rated voltage (kV) I/F BSC BSR BME
650 800 1000 650 800 1000 650 800 1000 650 800 1000
12/17.5 Width W (mm) 650 800 1000 650 800 1000 650 800 1000 650 800 1000
Height H (mm)(1) 2240 2240 2240 2240 2240 2240 2240 2240 2240 2240 2240 2240
Depth D (mm)(2) 1440 1440 1440 1440 1440 1440 1440 1440 1440 1440 1440 1440
Approximate weight with packing (kg)(3) 800 920 1050 720 840 970 480 630 750 470 720 -
Approximate weight without packing (kg)(3) 700 820 950 620 740 870 380 530 650 350 620 -
24 Height H (mm)(1) 2400 2400 2400 2400 2400 2400 2400 2400 2400 2400 2400 2400
Depth D (mm)(2) 1860 1860 1860 1860 1860 1860 1860 1860 1860 1860 1860 1860
Approximate weight with packing (kg)(3) 1160 1470 - 1190 1510 - 800 1030 - 765 980 -
Approximate weight without packing (kg)(3) 1020 1330 - 1120 1440 - 730 960 - 700 910 -

(1) The specified height covers standard LV compartment and does not include internal arc accessories.

(2) The mentioned depth refers to a single CT with bottom cable entry; it may differ for other designs.

(3) Fully equipped cubicle with surge arrester and fixed Voltage Transformer (VT).

NOTE:

Switchboard Tunnel

Switchboard with Internal Arc Accessories

DANGER

HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH

Failure to follow these instructions will result in death or serious injury.

Recommendations

Figure 2: Ceiling Height for Internal Exhaust

NOTE: The images shown here are for illustration purpose only.

Table 2: Ceiling Height for Internal Exhaust

Rated voltage (kV) Ceiling height H2 (mm)
12/17.5 3400
24 3500

Figure 3: Ceiling Height for External Exhaust 12/17.5 kV

NOTE: The images shown here are for illustration purpose only.

Table 3: Ceiling Height for External Exhaust 12/17.5 kV

Rated voltage (kV) Ceiling height H2 (mm)
12/17.5 3000

Figure 4: Ceiling Height for IP 41/42 External Exhaust 24 kV

NOTE: The images shown here are for illustration purpose only.

Figure 5: Ceiling Height for IP 4X External Exhaust 24 kV

NOTE: The images shown here are for illustration purpose only.

Table 4: Ceiling Height for External Exhaust 24 kV

External Exhaust Ceiling height H2 (mm)
IP 41/42 3280
IP 4X 3150

Switchboard Spacing

HAZARD OF INCORRECT DIMENSIONS

Adhere to the specified spacing dimensions of the switchboard mentioned in Civil Engineering with Maintenance Space/Cable Trench, page 15.

Failure to follow these instructions can result in injury or equipment damage.

Civil Engineering with Maintenance Space/Cable Trench

Figure 6: Civil Engineering with Maintenance Space/Cable Trench

A This space should remain clear to allow for the opening of the gas exhaust outlets in the event of internal arcing. Do not keep any devices in this zone (lights, equipment storage, cable tray, air condition duct, beam, and so on). It is also the location for the installation of the tunnel.

Table: Dimension A (mm)

Cubicle 12/17.5 kV 24 kV
External exhaust 200 200
Internal exhaust 420 380

B: Total height of the cubicle height with internal exhaust/external exhaust.

Table: Dimension B (mm)

Cubicle 12/17.5 kV 24 kV
IP4X IP41/42 IP4X
External exhaust 2710 3080 2950
Internal exhaust 2970 3140 3070

C: Main earthing bar.

D: Reserved slab space for routing the MV cables.

E: Reserved slab space for routing of LV cables.

F: The height of the cable trench should be kept in line with the cable's bending radius, as outlined in the supplier's catalog.

G: Access to room.

(1) Minimum dimensions to be complied with when installing the MCSET switchboard with minimum LV box height.

NOTE:

Spacing Around the Switchboard

HAZARD OF INCORRECT DIMENSIONS

Adhere to the specified spacing dimensions around the switchboard, refer to Figure 5.

Failure to follow these instructions can result in injury or equipment damage.

Top view of the switchboard

Figure 7: Top View of the Switchboard and Surrounding Spacing

The L dimension depends on the cubicles of the switchboard.

A: This dimension should be equal to:

B: 35 mm end cover.

C: Should be 800 mm for lateral access & 500 mm if no access.

D: Minimum 1200 mm for opening the door.

E: The dimensions are as follows:

F: Main earth bar for the switchboard.

NOTE:

Position of MV Cables

I/F Cubicle with 1 CT per Phase – 12/17.5 kV, 650 mm

The maximum external cable diameter for single-core cables is Ø 50 mm. Maximum allowable cable size is 630 mm².

Figure 8: MV Cable Entry with a Single Run

Figure 9: MV Cable Entry with Two Runs

I/F Cubicle with 1 CT per Phase – 800 mm

The maximum external cable diameter for single-core cables is Ø 50 mm. Maximum allowable cable size is 630 mm².

Figure 10: MV Cable Entry with a Single Run

Figure 11: MV Cable Entry with Two Runs

I/F Cubicle with 1 CT per Phase – 24 kV, 1000 mm

The maximum external cable diameter for single-core cables is Ø 50 mm. Maximum allowable cable size is 630 mm².

Figure 13: MV Cable Entry with Two Runs

Figure 14: MV Cable Entry with Four Runs

I/F Cubicle with 1 CT per Phase – 24 kV, 1000 mm

The maximum external cable diameter for single-core cables is Ø 50 mm. Maximum allowable cable size is 630 mm².

Figure 17: MV Cable Entry with a Single Run

Figure 18: MV Cable Entry with Two Runs

Figure 19: MV Cable Entry with Four Runs

Top Busway Entry

Figure 20: Top view of 800 mm Top Busway Entry Cubicle 24 kV

Figure 21: Top view of 1000 mm Top Busway Entry Cubicle 24 kV

Civil Works Slab

Reserved Area in Civil Works Slab

Figure 22: Ground Plan of a MCSeT Switchgear Within a Switchgear Room

A: C-channel rail

B: Opening for routing external low-voltage cables

C: Opening for routing high-voltage cables

D: The depth of the cable trench should be maintained according to the bending radius of the cable, as specified in the supplier's catalog.

E: The width of the cubicles

Table: Dimension C (mm)

Cubicle width E (mm) Rated voltage 12/17.5 kV Rated voltage 24 kV
650 400 550
800 550 750
1000 750 750

Detailed View of Bottom Plate

Figure 23: Bottom Plate of 650 mm Cubicle

Figure 24: Bottom Plate of 800 mm Cubicle 12/17.5 kV

Figure 25: Bottom Plate of 800 mm Cubicle 24 kV

Figure 26: Bottom Plate of 1000 mm Cubicle 12/17.5 kV

Figure 27: Bottom Plate of 1000 mm Cubicle 24 kV

Figure 28: Bottom Plate of 800 mm Top Busway Entry Cubicle 24 kV

Figure 29: Bottom Plate of 1000 mm Top Busway Entry Cubicle 24 kV

Switchboard with I/F Cubicle, and Reserved Space Over All Civil Engineering

Figure 30: General Arrangement for Cable Entry

A: Foundation rail

B: Top surface of the foundation rail from 3-5 mm above the floor

C: Cover of the control cable conduit 8 = 5 mm corrugated steel plate

D: Control cable trench 150 x 150 mm

Table: Dimension (mm)

Rated voltage (kV) H1 E F G I
12/17.5 2240 890 1290 1325 1440
24 2400 1160 1710 1780 1860

Floor Finishing and Fastening of the Cubicles

Assembly

Safety Provisions

WARNING

HAZARD OF TOPPLING

When handling the moving devices, pay attention to uneven floor surfaces (for example, cracks, projections and so on) of the switchgear room.

Failure to follow these instructions can result in death, serious injury, or equipment damage.

WARNING

HAZARD OF FALLING

Failure to follow these instructions can result in death, serious injury, or equipment damage.

Instructions for Assembly

MCSET cubicles are delivered with E/S in ON position.

The VCBs are always shipped in open state (OFF) with the energy-storing device released.

NOTICE

HAZARD OF INAPPROPRIATE ASSEMBLY

Failure to follow these instructions can result in equipment damage.

Floor Finishing

Surface Condition

Before the switchgear is positioned at its site of installation, check that the fastening points are at level.

NOTICE

HAZARD OF INSTALLING UNDER INADEQUATE CONDITIONS

Failure to follow these instructions can result in equipment damage.

Laser check is required for accurate check of the floor levelness. Floor level is more essential for correct assembly and performance of the product.

Floor Strength

The floor should have a compression withstand ≥ 33 MPa to roll the extraction tool on it without any damage.

Fastening of the Cubicles

WARNING

HAZARD OF INSTALLING UNDER INADEQUATE CONDITIONS

Make sure that the height difference across the entire width of the switchgear does not exceed 6 mm during lifting.

Failure to follow these instructions can result in death, serious injury, or equipment damage.

NOTICE

HAZARD OF INSTALLING UNDER INADEQUATE CONDITIONS

Failure to follow these instructions can result in equipment damage.

NOTICE

HAZARD OF INAPPROPRIATE ASSEMBLY

Comply with precise measurements for the placement of the cubicle, as the positioning of the first cubicle determines the placement of the remaining cubicles.

Failure to follow these instructions can result in equipment damage.

Fastening on Concrete Foundations

Follow the below steps to fasten the cubicle to the floor on standard civil engineering works:

  1. Position first cubicle on the floor in accordance with the switchgear-specific space assignment plan, Reserved Area in Civil Works Slab, page 26.
  2. Remove the cable compartment cover. Refer to Access to the Main Circuit Compartments, User Guide (BQT8706400).
  3. Once the cubicle is positioned:
    • Verify that the cubicle front is correctly aligned both horizontally and vertically.
    • If necessary, raise the cubicle and insert shims below the cubicle near the fastening points until the correct horizontal position is achieved, refer to Figure 31.
  4. Fasten the cubicle with screws to the two fastening points on both the front end and the rear end.

Figure 31: Cubicle Fastening on Concrete Foundation

1. Screw M10 x 30

2. Spring lock washer M10

3. Plain washer

4. Shim plate(1)

5. Slotted set screw M10 x 30

6. Plate 3 mm

(1) Add shim plates as needed.

Additional Fastening Variant (C-Channel)

Follow the below steps to fasten the cubicle on C-channel rails on standard civil engineering works:

  1. Drill holes into the C-channel frames at the intended cubicle fastening points, refer to Figure 32.
  2. Position the cubicle on the C-channel rails, aligning the fastening points.
  3. Insert dowel pin and other suitable fasteners (provided by Schneider Electric), refer to Figure 33.
  4. Securely fasten the cubicle to the C-channel rails at the designated points.

NOTE:

Figure 32: Dimension of the Floor Space and C-Channel Rails

Table: Dimensions (mm)

Rated voltage (kV) A B C
12/17.5 1340 1180 1080
24 1860 1700 1600

Figure 33: Cubicle Fastening on Base Frame

A: Allen screw M12 x 45

B: Washer M12

C: Square washer

D: Dowel pin

E: C-channel rail

Configuration of Incoming MV Cables

HAZARD OF INCORRECT CABLE INSTALLATION

Comply with the guidelines specified by the manufacturer for the following:

Failure to follow these instructions can result in injury or equipment damage.

Other incoming configurations are possible, if there is greater clearance under the cubicle.

NOTE: If the cable box is used, adapt the depth of the maintenance space. For any queries regarding the configuration, contact Schneider Electric customer support.

Civil Engineering with Maintenance Space

MV Cables Rear Entry

Intended for cables up to 240 mm².

Figure 34: MV Cables Rear Entry

NOTE: Not recommended for 630 mm² cables and above.

MV Cables Entry from the Side Near a Wall

Intended for cables up to 240 mm².

Figure 35: MV Cables Entry from the Side near Wall

NOTE: Not recommended for 630 mm² cables and above.

MV Cables Entry from the Side at a Distance from a Wall

It is recommended for all cable diameters up to 630 mm².

According to the distance from the wall to the nearest MV cable (A), the dimension should be ≥ 2000 m for 630 mm² cables.

Figure 36: MV Cables Entry from the Side at a Distance from a Wall

Civil Engineering with a Cable Trench

MV Cables Rear Entry

Intended for cables up to 240 mm².

Figure 37: MV Cables Rear Entry

NOTE: Not recommended for 630 mm² cables and above.

MV Cables Entry from the Side Near a Wall

Intended for cables up to 240 mm².

Figure 38: MV Cables Entry from the Side near a Wall

NOTE: Not recommended for 630 mm² cables above.

Glossary

A

AFL: Accessibility Front Lateral

AFLR: Accessibility Front Lateral Rear

B

BME: Busbar Metering and Earthing

BSC: Bus Section Coupler

BSR: Bus Section Riser

C

CT: Current Transformer

E

E/S: Earthing Switch

EvoPacT HVX: Vacuum Circuit Breaker

EvoPacT MTX: Metering Truck

F

F: Feeder

I

I: Incomer

L

LV: Low Voltage

M

MV: Medium Voltage (voltage class up to 24 kV)

V

VCB: Vacuum Circuit Breaker

VDIS: Voltage Detecting and Indicating System

VT: Voltage Transformer

Models: BQT8706400-03 Air Insulated Switchgear, BQT8706400-03, Air Insulated Switchgear, Insulated Switchgear, Switchgear

File Info : application/pdf, 42 Pages, 20.63MB

PDF preview unavailable. Download the PDF instead.

BQT8706400-03-CG-MCSeT-Upto 24-kV

References

PDFlib PDI 10.0.2p2 (C /Win64)

Related Documents

Preview Schneider Electric SeT Series MCSeT Receipt Guide
This guide provides essential information for receiving, inspecting, and storing Schneider Electric's SeT Series MCSeT air-insulated switchgear with EvoPacT HVX Vacuum Circuit Breaker. It covers safety provisions, dimensions, weights, and handling procedures.
Preview Schneider Electric Medium Voltage Switchgear Components Catalog 2021
Explore the comprehensive 2021 catalog from Schneider Electric, featuring a wide range of components for Medium Voltage switchgear. Discover solutions for circuit breakers, contactors, switches, disconnectors, and fuses, designed for enhanced connectivity, flexibility, and efficiency.
Preview Schneider Electric SM6 Modular Units Catalog: Air Insulated Switchgear up to 36kV
Explore the Schneider Electric SM6 modular units, a comprehensive catalog detailing air insulated switchgear solutions up to 36kV for Medium Voltage Distribution. Discover features, benefits, and applications.
Preview Schneider Electric PIX Air Insulated Switchgear Installation, Operation, and Maintenance Guide
Comprehensive guide for the installation, operation, and maintenance of Schneider Electric's PIX series Air Insulated Switchgear with Roll on Floor Circuit Breaker, covering 12-17.5 kV and up to 40 kA.
Preview Schneider Electric HVX Vacuum Circuit-Breaker Manual
Comprehensive technical manual for Schneider Electric's HVX series vacuum circuit-breakers, covering assembly, operation, maintenance, and technical specifications. Designed for specialist electricians.
Preview EasyPact EXE - GOST Medium Voltage Distribution Catalog | Schneider Electric
Discover the Schneider Electric EasyPact EXE GOST catalog, detailing medium voltage vacuum circuit breakers. Learn about their design for enhanced safety, simplicity, and flexibility, suitable for infrastructure, industrial, and power grid applications.
Preview EasyPact MVS T3 Air Circuit Breaker for AC: Technical Overview
Detailed information on the Schneider Electric EasyPact MVS T3 air circuit breaker, including its features, technical highlights, certifications, connection flexibility, and endurance specifications for 1140V AC applications.
Preview Schneider Electric PowerPact 4 Circuit Breaker Datasheet PP41603X
Detailed technical specifications for the Schneider Electric PowerPact 4 molded case circuit breaker, model PP41603X. This datasheet covers its thermal-magnetic trip unit, 160A rating, 36kA breaking capacity, and complementary features.