Schneider Electric MCSeT Series: Civil Engineering Guide
Digitally Native Upto 24 kV Air-insulated Switchgear With EvoPacT HVX Vacuum Circuit Breaker
Document Reference: BQT8706400-03
Publication Date: 06/2025
Legal Information
The information provided in this document contains general descriptions, technical characteristics and/or recommendations related to products/solutions. This document is not intended as a substitute for a detailed study or operational and site-specific development or schematic plan. It is not to be used for determining suitability or reliability of the products/solutions for specific user applications. It is the duty of any such user to perform or have any professional expert of its choice (integrator, specifier or the like) perform the appropriate and comprehensive risk analysis, evaluation and testing of the products/solutions with respect to the relevant specific application or use thereof.
The Schneider Electric brand and any trademarks of Schneider Electric SE and its subsidiaries referred to in this document are the property of Schneider Electric SE or its subsidiaries. All other brands may be trademarks of their respective owner.
This document and its content are protected under applicable copyright laws and provided for informative use only. No part of this document may be reproduced or transmitted in any form or by any means (electronic, mechanical, photocopying, recording, or otherwise), for any purpose, without the prior written permission of Schneider Electric.
Schneider Electric does not grant any right or license for commercial use of the document or its content, except for a non-exclusive and personal license to consult it on an "as is" basis.
Schneider Electric reserves the right to make changes or updates with respect to or in the content of this document or the format thereof, at any time without notice.
To the extent permitted by applicable law, no responsibility or liability is assumed by Schneider Electric and its subsidiaries for any errors or omissions in the informational content of this document, as well as any non-intended use or misuse of the content thereof.
SeT Series Overview
Featuring outstanding medium-voltage (MV) and low-voltage (LV) switchboards, motor control centres and power distribution solutions for high-performance power applications, Schneider Electric's SeT Series is optimized solutions based on high levels of safety and an optimized footprint. Built on a modular architecture and incorporating smart connected devices for maximum safety, reliability, performance and energy efficiency, the SeT Series is delivered to customers directly from Schneider Electric plants or via a global network of licensed partner panel builders, who are trained and audited to provide quality equipment and support.
Safety Information
Important Information
Read these instructions carefully, and look at the equipment to become familiar with the device before trying to install, operate, service, or maintain it. The following special messages may appear throughout this documentation or on the equipment to warn of potential hazards or to call attention to information that clarifies or simplifies a procedure.
The addition of this symbol ⚠️ to a "Danger" or "Warning" safety label indicates that an electrical hazard exists which will result in personal injury if the instructions are not followed.
This is the safety alert symbol ⚠️. It is used to alert you to potential personal injury hazards. Obey all safety messages that follow this symbol to avoid possible injury or death.
DANGER indicates a hazardous situation which, if not avoided, will result in death or serious injury.
WARNING indicates a hazardous situation which, if not avoided, could result in death or serious injury.
CAUTION indicates a hazardous situation which, if not avoided, could result in minor or moderate injury.
NOTICE is used to address practices not related to physical injury.
Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material.
A qualified person is one who has skills and knowledge related to the construction and operation of electrical equipment and its installation, and has received safety training to recognize and avoid the hazards involved.
Safety Precautions
Safety Rules
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
- Apply appropriate Personal Protective Equipment (PPE) and follow safe electrical work practices. See standards or local equivalent.
- This EvoPacT HVX Vacuum Circuit Breaker and the MCSeT equipment must only be installed and serviced by qualified electrical personnel.
- Perform work only after reading and understanding all of the instructions contained in this guide.
- Turn off all the power sources before working on or inside the equipment.
- Turn off or trip the Vacuum Circuit Breaker (VCB) and discharge the mechanism.
- Always use a properly calibrated voltage sensing device to confirm power is off.
- Use only Schneider Electric specific tools (operating crank, extraction table, and so on).
- Check all devices, covers, and doors are in correct position before turning on the power.
- Beware of potential hazards and carefully inspect the work area for tools and objects that may have been left inside the equipment.
- Do not modify the mechanical or electrical parts.
- Do not bypass the interlocks before operation.
- Do not operate with protective barriers removed.
Failure to follow these instructions will result in death or serious injury.
NOTICE
HAZARD OF INCORRECT HANDLING AND INADEQUATE STORAGE CONDITION
- Comply with the handling rules and avoid causing any shocks to the device.
- If the equipment is stored before its final installation, observe the storage conditions.
Failure to follow these instructions can result in equipment damage.
Cleaning Instructions
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
- Do not use solvents or alcohol for cleaning the equipment.
- Do not use high-pressure cleaner for cleaning the equipment.
Failure to follow these instructions will result in death or serious injury.
About the Document
Intended Use
This civil engineering guide describes air-insulated MV switchgear units of the MCSET.
The operations described in this guide should be performed by a qualified personnel with proven experience regarding:
- The MCSET series
- All relevant safety provisions
This civil engineering guide is an integral part of the product and should be stored such that it is readily accessible at all times and can be used by persons who work on the switchgear. If the switchgear is relocated to another site, this guide should be passed on to the new operator along with the unit.
This guide does not describe every imaginable individual case or every customer-specific version of the product. For more information that is not included in this guide, contact Schneider Electric.
Validity Note
This guide is valid only for MCSeT cubicle. The design provides easy rack-in/rack-out operation without the need for a separate trolley. This MCSeT cubicle is an extension of the MCSeT range and delivers performances up to 24 kV, equipped with EvoPacT HVX VCB and CVX Contactor. It also has other functional trolley like the EvoPacT Metering Truck (MTX).
For product compliance and environmental information (RoHS, REACH, PEP, EOLI, and so on), go to the Green Premium page on the Schneider Electric website.
The information contained in this guide is likely to be updated at any time. Schneider Electric strongly recommends that you have the most recent and up-to-date version available on www.se.com/ww/en/download.
The technical characteristics of the devices described in this guide also appear online. To access the information online, go to the Schneider Electric home page at www.se.com.
Product Related Information
Air-insulated MV switchgear units of the MCSeT series are designed exclusively for switching and distributing electrical power.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
The MCSeT switchgear must be used only in scope of specified standards and specific technical data.
Failure to follow these instructions will result in death or serious injury.
Safety Provisions
Introduction
Before performing work on the cubicle, it is essential that you comply with the following instructions:
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Before removing covers and performing assembly or maintenance work:
- Ensure that the system is isolated from high voltage, supply voltage, and properly grounded.
- Ensure that the VCB/Contactor is in test condition, the Earthing Switch (E/S) is closed, and access is locked.
- Follow the Lock Out Tag Out (LOTO) process to perform any work on switchboard.
- Install barriers, cables, and polycarbonates in accordance with the design specifications wherever necessary.
Failure to follow these instructions will result in death or serious injury.
WARNING
HAZARD OF MOVING PARTS IN MECHANICAL DRIVES
Before performing mounting and maintenance work, comply with the below safety rules:
- Isolate from the supply voltage.
- Release the energy-storing device of the VCB by performing the OFF-ON-OFF operation.
- Activate the make-proof E/S to ON position, to ensure that the equipment is ready for use (if any).
- Do not remove the mechanisms during maintenance work.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
WARNING
HAZARD OF SHARP-EDGED SHEET METAL AND METAL PARTS
During installation and maintenance work, comply with the below safety rules:
- Apply appropriate PPE and follow safe electrical work practices. See standards or local equivalent.
- Always cover sharp edges.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
Applicable Standards and Regulations
The applicable standards and regulations are as follows:
- Metal-enclosed AC switchgear for rated voltages > 1 kV up to including 52 kV: IEC 62271-200, Common specification: IEC 62271-1.
- The locally applicable accident prevention, operating and work instructions should be complied.
- Assembly and maintenance: IEC 61936-1.
- Operation of electrical equipment: EN 50110-1.
NOTE:
- The national standards applicable in the country where the equipment is to be installed should be complied.
- Other standards or regulations have to be checked and accessed locally.
Behavior in case of Incidents or Accidents
If an internal arc fault occurs, the MCSeT switchgear is equipped with pressure relief absorbers or ports to help prevent the cubicles and switchgear from being blown off.
This civil engineering guide does not include information regarding the safety of buildings in case of internal faults (pressure load of the switchgear room and necessary pressure relief ports). Pressure calculations for switchgear rooms, including recommendations for pressure relief ports, are available upon request for a fee. For more details, contact Schneider Electric.
In case of fire or internal faults, toxic and caustic decomposition products are produced. Comply with the locally applicable accident and safety provisions. Make sure that the first-aid measures are taken in case of injury to persons.
Dimensions and Weights
Cubicles without Internal Arc Accessories
The list of cubicles with one Current Transformer (CT) per phase in the MCSET are:
- Incomer/Feeder (I/F)
- Bus Section Coupler (BSC)
- Bus Section Riser (BSR)
- Busbar Metering and Earthing (BME)
Figure 1: Dimensions of Cubicles
NOTE: The images shown here are for illustration purpose only.
Table 1: Dimensions of I/F, BSC, BSR, and BME Cubicles
Rated voltage (kV) | I/F | BSC | BSR | BME | |||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|
650 | 800 | 1000 | 650 | 800 | 1000 | 650 | 800 | 1000 | 650 | 800 | 1000 | ||
12/17.5 | Width W (mm) | 650 | 800 | 1000 | 650 | 800 | 1000 | 650 | 800 | 1000 | 650 | 800 | 1000 |
Height H (mm)(1) | 2240 | 2240 | 2240 | 2240 | 2240 | 2240 | 2240 | 2240 | 2240 | 2240 | 2240 | 2240 | |
Depth D (mm)(2) | 1440 | 1440 | 1440 | 1440 | 1440 | 1440 | 1440 | 1440 | 1440 | 1440 | 1440 | 1440 | |
Approximate weight with packing (kg)(3) | 800 | 920 | 1050 | 720 | 840 | 970 | 480 | 630 | 750 | 470 | 720 | - | |
Approximate weight without packing (kg)(3) | 700 | 820 | 950 | 620 | 740 | 870 | 380 | 530 | 650 | 350 | 620 | - | |
24 | Height H (mm)(1) | 2400 | 2400 | 2400 | 2400 | 2400 | 2400 | 2400 | 2400 | 2400 | 2400 | 2400 | 2400 |
Depth D (mm)(2) | 1860 | 1860 | 1860 | 1860 | 1860 | 1860 | 1860 | 1860 | 1860 | 1860 | 1860 | 1860 | |
Approximate weight with packing (kg)(3) | 1160 | 1470 | - | 1190 | 1510 | - | 800 | 1030 | - | 765 | 980 | - | |
Approximate weight without packing (kg)(3) | 1020 | 1330 | - | 1120 | 1440 | - | 730 | 960 | - | 700 | 910 | - |
(1) The specified height covers standard LV compartment and does not include internal arc accessories.
(2) The mentioned depth refers to a single CT with bottom cable entry; it may differ for other designs.
(3) Fully equipped cubicle with surge arrester and fixed Voltage Transformer (VT).
NOTE:
- For a 4000 A cubicle with a width of 1000 mm, the depth is 1640 mm.
- All weights mentioned in this document may vary. The actual weights are specified on the cubicle packaging.
Switchboard Tunnel
Switchboard with Internal Arc Accessories
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
- Do not step on the switchboard roof to access the device and avoid installing any devices such as lamps above the switchboard.
- Ensure to maintain Schneider recommended minimum ceiling height for internal and external exhaust. For details, refer to Figure 2, Figure 3, Figure 4 and Figure 5.
Failure to follow these instructions will result in death or serious injury.
Recommendations
Figure 2: Ceiling Height for Internal Exhaust
NOTE: The images shown here are for illustration purpose only.
Table 2: Ceiling Height for Internal Exhaust
Rated voltage (kV) | Ceiling height H2 (mm) |
---|---|
12/17.5 | 3400 |
24 | 3500 |
Figure 3: Ceiling Height for External Exhaust 12/17.5 kV
NOTE: The images shown here are for illustration purpose only.
Table 3: Ceiling Height for External Exhaust 12/17.5 kV
Rated voltage (kV) | Ceiling height H2 (mm) |
---|---|
12/17.5 | 3000 |
Figure 4: Ceiling Height for IP 41/42 External Exhaust 24 kV
NOTE: The images shown here are for illustration purpose only.
Figure 5: Ceiling Height for IP 4X External Exhaust 24 kV
NOTE: The images shown here are for illustration purpose only.
Table 4: Ceiling Height for External Exhaust 24 kV
External Exhaust | Ceiling height H2 (mm) |
---|---|
IP 41/42 | 3280 |
IP 4X | 3150 |
Switchboard Spacing
HAZARD OF INCORRECT DIMENSIONS
Adhere to the specified spacing dimensions of the switchboard mentioned in Civil Engineering with Maintenance Space/Cable Trench, page 15.
Failure to follow these instructions can result in injury or equipment damage.
Civil Engineering with Maintenance Space/Cable Trench
Figure 6: Civil Engineering with Maintenance Space/Cable Trench
A This space should remain clear to allow for the opening of the gas exhaust outlets in the event of internal arcing. Do not keep any devices in this zone (lights, equipment storage, cable tray, air condition duct, beam, and so on). It is also the location for the installation of the tunnel.
Table: Dimension A (mm)
Cubicle | 12/17.5 kV | 24 kV |
---|---|---|
External exhaust | 200 | 200 |
Internal exhaust | 420 | 380 |
B: Total height of the cubicle height with internal exhaust/external exhaust.
Table: Dimension B (mm)
Cubicle | 12/17.5 kV | 24 kV | |
---|---|---|---|
IP4X | IP41/42 | IP4X | |
External exhaust | 2710 | 3080 | 2950 |
Internal exhaust | 2970 | 3140 | 3070 |
C: Main earthing bar.
D: Reserved slab space for routing the MV cables.
E: Reserved slab space for routing of LV cables.
F: The height of the cable trench should be kept in line with the cable's bending radius, as outlined in the supplier's catalog.
G: Access to room.
(1) Minimum dimensions to be complied with when installing the MCSET switchboard with minimum LV box height.
NOTE:
- The depth of the maintenance space should be equal to the bending radius of the cables being used. This helps to prevent cables from experiencing undue stress.
- To place the ramp and remove the withdrawable VT (WVT) from the front side, a minimum of 2000 mm of space is required.
Spacing Around the Switchboard
HAZARD OF INCORRECT DIMENSIONS
Adhere to the specified spacing dimensions around the switchboard, refer to Figure 5.
Failure to follow these instructions can result in injury or equipment damage.
Top view of the switchboard
Figure 7: Top View of the Switchboard and Surrounding Spacing
The L dimension depends on the cubicles of the switchboard.
A: This dimension should be equal to:
- 200 mm for AFL (Accessibility Front Lateral) type of cubicle.
- Minimum 800 mm for AFLR (Accessibility Front Lateral Rear) type of cubicle.
B: 35 mm end cover.
C: Should be 800 mm for lateral access & 500 mm if no access.
D: Minimum 1200 mm for opening the door.
E: The dimensions are as follows:
- Minimum distance for operating must be 1500 mm (minimum distance for face-to-face switchboard configuration must be 2500 mm).
- 1550 mm for operation (extraction and positioning of mobile parts).
- 2060 mm for the extraction of one cubicle with a depth of 1860 mm without displacing the others.
- 1640 mm for the extraction of cubicle with a depth of 1440 mm and 1840 mm for the extraction of cubicle with a depth of 1640 mm without displacing the others.
- To place the ramp and remove the Withdrawable VT (WVT) from the front side, a minimum of 2000 mm of space is required.
F: Main earth bar for the switchboard.
NOTE:
- The cubicle is used for different cubicle setups, including feeder/incomer, bus coupler, bus riser, and bus metering configurations.
- For the extraction of the cubicle, contact Schneider Electric field service.
Position of MV Cables
I/F Cubicle with 1 CT per Phase – 12/17.5 kV, 650 mm
The maximum external cable diameter for single-core cables is Ø 50 mm. Maximum allowable cable size is 630 mm².
Figure 8: MV Cable Entry with a Single Run
Figure 9: MV Cable Entry with Two Runs
I/F Cubicle with 1 CT per Phase – 800 mm
The maximum external cable diameter for single-core cables is Ø 50 mm. Maximum allowable cable size is 630 mm².
Figure 10: MV Cable Entry with a Single Run
Figure 11: MV Cable Entry with Two Runs
I/F Cubicle with 1 CT per Phase – 24 kV, 1000 mm
The maximum external cable diameter for single-core cables is Ø 50 mm. Maximum allowable cable size is 630 mm².
Figure 13: MV Cable Entry with Two Runs
Figure 14: MV Cable Entry with Four Runs
I/F Cubicle with 1 CT per Phase – 24 kV, 1000 mm
The maximum external cable diameter for single-core cables is Ø 50 mm. Maximum allowable cable size is 630 mm².
Figure 17: MV Cable Entry with a Single Run
Figure 18: MV Cable Entry with Two Runs
Figure 19: MV Cable Entry with Four Runs
Top Busway Entry
Figure 20: Top view of 800 mm Top Busway Entry Cubicle 24 kV
Figure 21: Top view of 1000 mm Top Busway Entry Cubicle 24 kV
Civil Works Slab
Reserved Area in Civil Works Slab
Figure 22: Ground Plan of a MCSeT Switchgear Within a Switchgear Room
A: C-channel rail
B: Opening for routing external low-voltage cables
C: Opening for routing high-voltage cables
D: The depth of the cable trench should be maintained according to the bending radius of the cable, as specified in the supplier's catalog.
E: The width of the cubicles
Table: Dimension C (mm)
Cubicle width E (mm) | Rated voltage 12/17.5 kV | Rated voltage 24 kV |
---|---|---|
650 | 400 | 550 |
800 | 550 | 750 |
1000 | 750 | 750 |
Detailed View of Bottom Plate
Figure 23: Bottom Plate of 650 mm Cubicle
Figure 24: Bottom Plate of 800 mm Cubicle 12/17.5 kV
Figure 25: Bottom Plate of 800 mm Cubicle 24 kV
Figure 26: Bottom Plate of 1000 mm Cubicle 12/17.5 kV
Figure 27: Bottom Plate of 1000 mm Cubicle 24 kV
Figure 28: Bottom Plate of 800 mm Top Busway Entry Cubicle 24 kV
Figure 29: Bottom Plate of 1000 mm Top Busway Entry Cubicle 24 kV
Switchboard with I/F Cubicle, and Reserved Space Over All Civil Engineering
Figure 30: General Arrangement for Cable Entry
A: Foundation rail
B: Top surface of the foundation rail from 3-5 mm above the floor
C: Cover of the control cable conduit 8 = 5 mm corrugated steel plate
D: Control cable trench 150 x 150 mm
Table: Dimension (mm)
Rated voltage (kV) | H1 | E | F | G | I |
---|---|---|---|---|---|
12/17.5 | 2240 | 890 | 1290 | 1325 | 1440 |
24 | 2400 | 1160 | 1710 | 1780 | 1860 |
Floor Finishing and Fastening of the Cubicles
Assembly
Safety Provisions
WARNING
HAZARD OF TOPPLING
When handling the moving devices, pay attention to uneven floor surfaces (for example, cracks, projections and so on) of the switchgear room.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
WARNING
HAZARD OF FALLING
- Do not walk upon the topsides of the switchgear cubicles.
- During civil engineering activities, when working on the top of the switchgear cubicles (such as during the installation of deflectors, fans, or pressure relief ducts), temporarily attach a sturdy base plate that is walkable.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
Instructions for Assembly
MCSET cubicles are delivered with E/S in ON position.
The VCBs are always shipped in open state (OFF) with the energy-storing device released.
NOTICE
HAZARD OF INAPPROPRIATE ASSEMBLY
- Ensure there is no condensation, dirt, and dust during assembly of cubicles on all accounts.
- Observe and read assembly drawings before commencing the assembly work.
Failure to follow these instructions can result in equipment damage.
Floor Finishing
Surface Condition
Before the switchgear is positioned at its site of installation, check that the fastening points are at level.
NOTICE
HAZARD OF INSTALLING UNDER INADEQUATE CONDITIONS
- Before positioning the switchgear at its installation site, ensure that the fastening points are at the correct level.
- Unevenness should not exceed ± 2 mm/m and there should not be a height difference of more than 6 mm over the entire width of the switchgear.
Failure to follow these instructions can result in equipment damage.
Laser check is required for accurate check of the floor levelness. Floor level is more essential for correct assembly and performance of the product.
Floor Strength
The floor should have a compression withstand ≥ 33 MPa to roll the extraction tool on it without any damage.
Fastening of the Cubicles
WARNING
HAZARD OF INSTALLING UNDER INADEQUATE CONDITIONS
Make sure that the height difference across the entire width of the switchgear does not exceed 6 mm during lifting.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
NOTICE
HAZARD OF INSTALLING UNDER INADEQUATE CONDITIONS
- Before positioning the switchgear at its installation site, ensure that the fastening points are at the correct level.
- Unevenness should not exceed ± 2 mm/m and there should not be a height difference of more than 6 mm over the entire width of the switchgear.
Failure to follow these instructions can result in equipment damage.
NOTICE
HAZARD OF INAPPROPRIATE ASSEMBLY
Comply with precise measurements for the placement of the cubicle, as the positioning of the first cubicle determines the placement of the remaining cubicles.
Failure to follow these instructions can result in equipment damage.
Fastening on Concrete Foundations
Follow the below steps to fasten the cubicle to the floor on standard civil engineering works:
- Position first cubicle on the floor in accordance with the switchgear-specific space assignment plan, Reserved Area in Civil Works Slab, page 26.
- Remove the cable compartment cover. Refer to Access to the Main Circuit Compartments, User Guide (BQT8706400).
- Once the cubicle is positioned:
- Verify that the cubicle front is correctly aligned both horizontally and vertically.
- If necessary, raise the cubicle and insert shims below the cubicle near the fastening points until the correct horizontal position is achieved, refer to Figure 31.
- Fasten the cubicle with screws to the two fastening points on both the front end and the rear end.
Figure 31: Cubicle Fastening on Concrete Foundation
1. Screw M10 x 30
2. Spring lock washer M10
3. Plain washer
4. Shim plate(1)
5. Slotted set screw M10 x 30
6. Plate 3 mm
(1) Add shim plates as needed.
Additional Fastening Variant (C-Channel)
Follow the below steps to fasten the cubicle on C-channel rails on standard civil engineering works:
- Drill holes into the C-channel frames at the intended cubicle fastening points, refer to Figure 32.
- Position the cubicle on the C-channel rails, aligning the fastening points.
- Insert dowel pin and other suitable fasteners (provided by Schneider Electric), refer to Figure 33.
- Securely fasten the cubicle to the C-channel rails at the designated points.
NOTE:
- The additional fastening variants are available on request. For details, contact Schneider Electric.
- C-channel rails are not provided by Schneider Electric.
Figure 32: Dimension of the Floor Space and C-Channel Rails
Table: Dimensions (mm)
Rated voltage (kV) | A | B | C |
---|---|---|---|
12/17.5 | 1340 | 1180 | 1080 |
24 | 1860 | 1700 | 1600 |
Figure 33: Cubicle Fastening on Base Frame
A: Allen screw M12 x 45
B: Washer M12
C: Square washer
D: Dowel pin
E: C-channel rail
Configuration of Incoming MV Cables
HAZARD OF INCORRECT CABLE INSTALLATION
Comply with the guidelines specified by the manufacturer for the following:
- Adhere to the specified bending radius for the cables.
- Ensure appropriate cable laying/installation methods, the correct force, and techniques for pulling or pushing the cables.
- While handling the cables, ensure that the cables are within the maintenance space as per the specific configuration from insertion point to the cable initiation joint at the transformer.
Failure to follow these instructions can result in injury or equipment damage.
Other incoming configurations are possible, if there is greater clearance under the cubicle.
NOTE: If the cable box is used, adapt the depth of the maintenance space. For any queries regarding the configuration, contact Schneider Electric customer support.
Civil Engineering with Maintenance Space
MV Cables Rear Entry
Intended for cables up to 240 mm².
Figure 34: MV Cables Rear Entry
NOTE: Not recommended for 630 mm² cables and above.
MV Cables Entry from the Side Near a Wall
Intended for cables up to 240 mm².
Figure 35: MV Cables Entry from the Side near Wall
NOTE: Not recommended for 630 mm² cables and above.
MV Cables Entry from the Side at a Distance from a Wall
It is recommended for all cable diameters up to 630 mm².
According to the distance from the wall to the nearest MV cable (A), the dimension should be ≥ 2000 m for 630 mm² cables.
Figure 36: MV Cables Entry from the Side at a Distance from a Wall
Civil Engineering with a Cable Trench
MV Cables Rear Entry
Intended for cables up to 240 mm².
Figure 37: MV Cables Rear Entry
NOTE: Not recommended for 630 mm² cables and above.
MV Cables Entry from the Side Near a Wall
Intended for cables up to 240 mm².
Figure 38: MV Cables Entry from the Side near a Wall
NOTE: Not recommended for 630 mm² cables above.
Glossary
A
AFL: Accessibility Front Lateral
AFLR: Accessibility Front Lateral Rear
B
BME: Busbar Metering and Earthing
BSC: Bus Section Coupler
BSR: Bus Section Riser
C
CT: Current Transformer
E
E/S: Earthing Switch
EvoPacT HVX: Vacuum Circuit Breaker
EvoPacT MTX: Metering Truck
F
F: Feeder
I
I: Incomer
L
LV: Low Voltage
M
MV: Medium Voltage (voltage class up to 24 kV)
V
VCB: Vacuum Circuit Breaker
VDIS: Voltage Detecting and Indicating System
VT: Voltage Transformer