EasyPact MVS New Energy solution
Air Circuit Breaker for AC
EasyPact MVS T3 @1140Vac
Intercept Ambient Issue:
- Achieve high breaking capacity with high voltage
- Reduce condensation impact in inverter cabinet
- Avoid water drop into arc chamber directly because of condensation
Technical Highlight:
- 800A to 4000A ratings
- Suitable for 1140V AC applications
- Complete selectivity with Ics=100%, Icu=Icw 1s=66KA
- 3 poles / Fixed and drawout versions
Connection Flexibility:
- 2 Available connection types: Rear down connections (horizontal, vertical)
- Simply turn a horizontal rear connection 90° to make it a vertical connector (4000A only horizontal connection)
Intelligent ETU:
- ET5S for semi assembly
- ET6A for full assembly
Various Acc and Certifications:
- Motor Mechanism / MX / XF / OF
- Interphase barriers
- Top cover of arc chamber
- IEC 60947-2
Endurance @1500Vdc:
- Maximum Mechanical cycle life up to 25,000 times with maintenance
- Maximum electrical cycle life up to 1,500 times
Sustainability:
- RoHS & REACH
- Online Environment PEP file
EasyPact MVS T3: Fixed Version
New Top Cover:
- Achieve high breaking capacity with high voltage
- Reduce condensation impact in inverter cabinet
- Avoid water drop into arc chamber directly because of condensation
EasyPact MVS T3: Connection
Busbar Size (Horizontal)
| Rating | Busbar Size |
|---|---|
| 800A | 1b 50x10 |
| 1000A | 1b 63x10 |
| 1250A | 2b 40x10 |
| 1600A | 2b 63x10 |
| 2000A | 2b 63x10 |
| 2500A | 2b 80x10 |
| 3200A | 3b 100x10 |
| 4000A | 5b 100x10 |
Copper connection; 40°; No. of 10mm thick bars
Flexibility in bus bar
Rear Terminal orientation from H to V (800-3200A)
4000A only horizontal connection
EasyPact MVS T3: Endurance @ 1140V AC
Electrical endurance (Only without maintenance)
No of cycles x1000
[Bar chart showing electrical endurance for ratings 800A to 4000A, with values around 1.5 for lower ratings decreasing to around 0.5 for 4000A]
Mechanical endurance (With & without maintenance)
No of cycles x1000
[Stacked bar chart showing mechanical endurance for ratings 800A to 4000A. Lower section 'Without maintenance' is around 10-12.5, upper section 'With maintenance' adds another 10-12.5]
EasyPact MVS T3 Order Code Definition
Range Name: MVS
Current Rating:
- 08: 800A
- 10: 1000A
- 12: 1250A
- 16: 1600A
- 20: 2000A
- 25: 2500A
- 32: 3200A
- 40: 4000A
Breaking Capacity: T3: Icu=Ics=Icw 1s=66KA
Pole: 3: 3Pole
Installation: F: Fixed, D: Drawout
Protection: 5: LSI*, 6: LSIG**
Trip Unit Type: 0: No metering, A: Current metering
Operation: 0: Manually operated ACB/SD, 2: Electrical 200/240VAC Incl MX/XF/MCH
* ET5S for semi assembly
** ET6A for full assembly