Airmaster AM 950 C & AM 950 F Mounting Guide

Models: AM 950 C, AM 950 F

Introduction

This manual provides instructions for the correct and safe installation of Airmaster AM 950 C and AM 950 F air handling units. The installation process is divided into two main parts: mounting the unit (covered in this manual) and electrical installation (detailed in the Installation manual). Both manuals are supplied with the unit and can also be downloaded from the Airmaster website.

Target Group: This manual is intended for qualified personnel.

Warning Symbols

The manual uses warning symbols adhering to ISO 3864 and ISO 7010 standards. Visual depictions may vary.

[DANGER] Indicates a hazard with a high level of risk which, if not avoided, will result in death or serious injury.
[WARNING] Indicates a hazard with a medium level of risk which, if not avoided, could result in death or serious injury.
[WARNING] Indicates a risk of crushing of hands.
[CAUTION] Indicates a hazard with a low level of risk which, if not avoided, could result in minor or moderate injury.
[CAUTION] Wear safety footwear as personal protection equipment.
[NOTICE] Failure to comply with the instructions can damage the device and its environment.
[NOTICE] Information, tips, and recommendations.

Liability

Airmaster A/S is not liable for damages resulting from instructions in this manual being violated. The manufacturer reserves the right to make changes without notice. Stated values are nominal and may be affected by local conditions. The warranty is void if this manual is not followed.

Safety Instructions

Breaching instructions marked with a warning symbol carries a risk of personal injury or material damage.

[WARNING]
  • The unit must not be installed in explosion-protected rooms.
  • The unit must not be installed in rooms with flammable or corrosive gas in the air.
  • The unit must not be installed in rooms with abrasive particles in the air.
  • The unit must not be installed in wet rooms.
[CAUTION] Wear safety shoes for personal protection.
[NOTICE] All applicable provisions must be observed when installing the unit in a room with a fire or stove drawing air from the room.
[NOTICE] The unit should not be used without the filters specified in the Operation & Maintenance manual.

Responsibility

[CAUTION]
  • The installation technician is responsible for installing the unit following local rules and standards.
  • The installation technician is responsible for ensuring that the unit is properly secured in a level vertical position.
  • The installation technician is responsible for ensuring that any existing functions in the wall/ceiling (e.g., vapor barrier) are restored and fully functional once the unit has been installed.

Personnel Requirements

The mounting and installation of the unit must be done by qualified personnel. Laypersons should not attempt to install an AM 950 unit.

Product Identification

AM 950 C

Product Name and Type

Product nameAM 950 C
Unit item number9000950601
TypeDecentral air handling unit, ceiling/wall mounted

Figure 1: HHBB version depicts the AM 950 C unit.

Refer to Appendix A for a dimensional drawing.

Specifications

Weight: standard unit, complete340 kg
Dimensions (W x D x H)2167 x 1613 x 505 mm
Duct connectionØ315 mm
Color: casingRAL 9010

Refer to the AM 950 C datasheet for further information, available on the Airmaster website (see section 3.3).

AM 950 F

Product Name and Type

Product nameAM 950 F
Unit item number9000950701
TypeDecentral air handling unit, floor standing

Figure 2: HH and VV version, Figure 3: SSR version, and Figure 4: SSL version show different configurations of the AM 950 F unit.

Refer to Appendix B, Appendix C, and Appendix D for dimensional drawings of these versions.

Specifications

Weight: standard unit, complete297 kg
Dimensions (W x D x H), HH and VV version1150 x 661 x 2260 mm
Dimensions (W x D x H), SSR and SSL version1210 x 661 x 2697 mm
Minimum ceiling height, HH and VV version2300 mm
Duct connectionØ315 mm
Color: casingRAL 9010

Refer to the AM 950 F datasheet for further information, available on the Airmaster website (see section 3.3).

Manufacturer

Airmaster A/S
Industrivej 59
9600 Aars
Denmark

Phone: +45 98 62 48 22
E-mail: info@airmaster.dk
Web site: www.airmaster-as.com

Transportation and Storage

The AM950 unit is packed on a pallet, with one unit per pallet. Ensure the pallet is securely tied during transport to prevent movement or shifting, and avoid dropping or damaging the unit during handling.

[NOTICE] The unit must be stored in a dry area at a temperature between -10 to 30° C.
[NOTICE] The unit can be tilted briefly, for example, when passing through a door. Tilt the unit with the front side upward.

When tilting, support the back side of the unit with blocks of wood or similar to avoid damaging fittings. Always place the unit on its back side when tilting, never on its edges.

AM 950 C

Gross weight (1 unit and pallet)Approx. 370 kg
Net weight (unit)340 kg
Pallet dimensions (L x W)2350 x 800 mm

AM 950 F

Gross weight (1 unit and pallet)Approx. 330 kg
Net weight (unit)297 kg
Pallet dimensions (L x W)2350*1300 mm

Important Information Before You Mount the Unit

Read the instructions in this chapter carefully before you begin.

[WARNING]
  • The floor and walls in the room where the unit is mounted must be even and leveled.
  • Minimum ceiling height is 2300 mm for the AM 950 F unit (see section 3.2.2).
  • Use screws intended for the supporting wall/ceiling material. Ensure the screws can support the unit's weight and fit the unit's attachment points.

If the AM 950 F unit tips over due to an uneven or unlevelled surface, there is a high risk of serious personal injury and damage to the unit.

[NOTICE] Use appropriate lifting equipment. The unit is heavy; do not try to lift or move it by hand.
[NOTICE] Duct holes in the wall must have an outward-downward gradient of 1-2% to prevent heavy rain from entering the unit.

It is recommended to drill duct holes 10-15 mm larger than indicated on the drawings. This allows for subsequent insulation, prevents direct contact with the wall, and facilitates the restoration of a vapor barrier.

Minimum Distance to Building Parts and Room Layout

AM 950 C

Correct positioning is crucial. The following sketch shows important distances to consider before installation:

Figure 5: Minimum distance to building parts, AM 950 C unit illustrates:

AMax. distance from ceiling6 mm
BMin. distance from wall0.5 m
CMin. free space for maintenance work0.95 m
DExternal PIR/motion sensor-
EApprox. space2.25 m (1.8 m – 2.5 m)

Obstacles in the room affect the airflow from the AM 950 C unit. Consider the room layout when choosing the position. See examples of correct vs. incorrect installation in Figure 6.

Figure 6: Correct installation vs. incorrect installation shows visual examples of proper and improper unit placement.

AM 950 F

Correct positioning is important. The unit requires free space for its door to open. Room obstacles can affect airflow, so consider the room layout when selecting the position. Key distances include:

  • A minimum distance of 10 mm on the left-hand side (from the front) is required to open the unit door.
  • A minimum distance of 1150 mm is required in front of the unit for the door to open.

Obstacles like large ceiling lamps can disrupt airflow, creating unwanted flow directions, as illustrated in Figure 7: Obstacles can create unwanted flow directions - illustrative example only.

Tools and Accessories

Before starting the mounting of the AM 950 C or AM 950 F unit, the following tools and accessories are needed:

  • Lifting equipment appropriate for the unit weight (min. 350 kg), e.g., a pallet loader.
  • A core drill (min. Ø315 mm, see Information Box on page 13).
  • Common hand tools, including a spirit level.
  • Sealants and sealing tape.
  • Clean underlay to prevent scratches (e.g., strong cardboard, thick plastic, a blanket).
  • Laths/battens/blocks of wood to support the unit when lifting.

Depending on the customer's order, duct pipes, grilles, and a vapor barrier may also be required. Installation cannot be done correctly without this equipment.

Unpacking

The scope of delivery is detailed on the delivery note. A general list of parts includes:

  • AM 950 unit
  • Airlinq® Orbit control panel, Airlinq® Viva control panel (option)
  • Condensate drain hose (option, included if condensate pump is selected)
  • Duct pipes, grilles, vapor barrier (options)
  • Service cover key
  • Manuals: Mounting manual, Installation manual, Operation & Maintenance manual.

Ensure all parts are present and check for any damage before starting installation.

[CAUTION] Do not start the installation if one or more parts on the delivery note are damaged or missing.

The Mounting Process

AM 950 C

The mounting process for the AM 950 C unit involves eight steps:

  1. Disassemble the side and front covers.
  2. Disassemble the rear bracket.
  3. Mark drill holes for the brackets and ducts.
  4. Drill holes.
  5. Mount the bracket.
  6. Mount the unit.
  7. Reassemble the side and front covers.
  8. Mount duct pipes and grilles and Condensate drainage (option).

The rear bracket is mounted on the unit when shipped and must be disassembled first. The front cover also needs to be removed to attach the unit to the ceiling. Subsequently, mark and drill holes for brackets and ducts. The rear bracket is then mounted, followed by lifting and mounting the unit onto it. Finally, the side and front covers are reassembled. Duct pipes, grilles, and the drain are then mounted to complete the process. Electrical installation, including control panels, is performed separately as per the Installation manual. After mounting, fill out the form on page 2 with unit details.

Disassemble the Side and Front Covers

  1. Disassemble the left-hand side cover, as shown in Figure 8: Disassemble the left-hand side cover. Place the cover on a protective underlay to prevent scratches.
  2. Disassemble the right-hand side cover, as shown in Figure 9: Disassemble the right-hand side cover. Place the cover on a protective underlay.
  3. Disassemble the front cover, as shown in Figure 10: Disassemble the front cover. Place the cover on a protective underlay.

Keep the bolts and washers for reassembly.

Disassemble the Rear Bracket

Disassemble the rear bracket as shown in Figure 11: Disassemble the rear bracket, left-hand side seen from behind and Figure 12: Disassemble the rear bracket, right-hand side seen from behind.

Keep the bolts for mounting the unit onto the bracket.

Mark Drill Holes for the Brackets and Ducts

Rear and Front Brackets
  1. Hold the rear bracket against the wall and ceiling, ensuring it is level (see Figure 13: Mark drill holes for the rear and front brackets).
  2. Mark the holes for the rear bracket.
  3. Mark the holes for the front bracket (part of the unit, cannot be disassembled) using Figure 14: Distances from rear bracket to front bracket and Table 8.
Table 8: Bracket distances
ABCD
1580 mm32 mm321 mm1926 mm
Duct
  1. Hold the rear bracket against the wall and ceiling, ensuring it is level and in the same position as before.
  2. Mark the center of the duct holes using Figure 15: Mark drill holes for the ducts and Table 9.
Table 9: Duct distances
ABC
213 mm184 mm1620 mm

The rear bracket has notches on top to mark the center of duct holes, serving as a reference for measurements.

Drill Holes

Drill the holes. Ensure the correct gradient and size for duct holes, as per the Information Box on page 13. Figure 16: Drill holes illustrates this step.

Mount the Bracket

Mount the bracket using all attachment points on the wall and ceiling. Figure 17: Mount the bracket shows the process.

Mount the Unit

Use appropriate lifting equipment (refer to section 5.2). Place a protective underlay between the lift and the unit to prevent scratches (Figure 18: Lift the unit up and onto the bracket). Lift the unit onto the bracket, ensuring it is hinged correctly. Prevent electrical wires and drain hoses from being squeezed between the wall/ceiling and the unit. Ensure the unit is level.

[WARNING] Do not place your hands between the wall and the unit.

Attach the unit to the bracket on both sides using the large bolts previously removed (see Figure 19: Attach the unit to the bracket, left-hand side and Figure 20: Attach the unit to the bracket, right-hand side). The bracket should fully support the unit. Check that the unit is level.

Mount the front bracket onto the ceiling using all attachment points (see Figure 21: Mount the front bracket to the ceiling). Check that the unit is level.

Reassemble the Side and Front Covers

Reassemble the front and side covers using the previously removed bolts (see Figure 22: Reassemble the left-hand side cover, Figure 23: Reassemble the right-hand side cover, and Figure 24: Reassemble the front cover).

The next step is to mount duct pipes and grilles; continue with section 6.3.

AM 950 F

The mounting process for the AM 950 F unit involves three or four steps:

  1. Mark and drill duct holes.
  2. Mount the unit.
  3. Mount duct pipes and grilles + sealing.
  4. Connect the drain (if supplied with a condensate pump and drain).

Figures in this section refer to the HH version. For VV, SSR, or SSL versions, consider duct hole locations and refer to Appendices B, C, or D for dimensional drawings. Electrical installation follows mounting, as per the Installation manual. After mounting, fill out the form on page 2 with unit details.

Mark and Drill Duct Holes

Ensure correct gradient and size for duct holes, as per the Information Box on page 13.

  1. Mark the holes for the ducts.
  2. Drill duct holes.

Consider wearing a face mask or similar protection equipment to avoid inhaling dust particles during drilling.

Mount the Unit

  1. Before lifting the unit upright, place laths/battens/blocks of wood as shown in Figure 25: Place laths/battens/blocks of wood before lifting the unit. This prevents damage to the height-adjustable feet. Ensure the feet are as short as possible.
  2. Raise the unit into an upright position and place it in its final position, as close to the wall as possible. A pallet loader can be used for moving (see Figure 26: Move the unit into place).
[WARNING] Do not place your hands between the wall and the unit.
[CAUTION] Be careful when moving the unit on the pallet loader. If the unit tilts over, it can cause injury to persons and damage the unit.
  1. Adjust the feet to make the unit level (see Figure 27: Adjust the feet to level the unit).
  2. Attach the brackets on top of the unit to the wall using screws suitable for the wall material. Ensure the unit is firmly secured to the wall (see Figure 28: Attach the bracket on top of the unit to the wall).

Mount Duct Pipes and Grilles

This section describes fitting ducting and sealing. Materials and methods depend on the customer's order, options, and site. The steps are:

  1. Mount the unit (already done).
  2. Fit the ducting.
  3. Mount the outside grille.

Figure 29: Duct pipes and grilles - general overview provides an overview, applicable to units with ducts on the back or through the ceiling.

[NOTICE]
  • Ventilation ducts must be installed according to local standards and rules.
  • Condensation and heat insulation must be performed according to local standards and rules.
  • Fire requirements according to local standards and rules must be observed.

Important Information:

  • Duct length is calculated based on wall/roof thickness.
  • Ensure duct pipes are not twisted or compressed against the unit's spigots, as this increases noise.
  • Intake and exhaust air ducts must be insulated against condensation if within the building envelope, with service access provided.
  • Intake and exhaust air ducts must be insulated against noise if visible, with service access provided.
  • Sealant must be applied inside and outside (see section 6.3.1).
  • An outside grille must be mounted. Refer to the Airmaster website for information on the Boomerain® grille.

Sealing

Figure 30: Sealing the gaps around ducts, sectional drawing depicts a unit with ducts through a wall. The unit (labeled '1') is installed on the inner wall.

Figure 30 shows:

  • 1: Unit
  • 2: Wall
  • 3: Duct and duct pipe
  • 4: Sealing points on the outside
  1. Apply sealant to the duct's outside edges (point '4' in Figure 30).
  2. Apply sealant to the inside around the base and sides of the unit, between the unit and the wall (see Figure 31: Sealing around the unit).

Use a sealant that retains long-term elasticity or expanding sealing tape for a flexible seal, depending on the wall condition.

Condensate Drainage (Option)

The AM 950 unit may be fitted with a condensate pump and hose. Drainage connections depend on the site.

Drainage can be via a waste-water pipe or through the outer wall. If connected to a waste-water pipe, install a water trap to block odors emanating from the system (see Figure 32: Water trap to avoid odors).

If the drainage hose is led through the outer wall, it must be protected against ice formation. Drill a hole with a suitable diameter and an outwardly sloping gradient of 1-2%. Seal the joint between the hose and the outer wall.

Appendices

Appendices contain dimensional drawings for different unit configurations:

  • Appendix A: Dimensional drawing, AM 950 C unit.
  • Appendix B: Dimensional drawing, AM 950 F unit, HHVV.
  • Appendix C: Dimensional drawing, AM 950 F unit, SSR.
  • Appendix D: Dimensional drawing, AM 950 F unit, SSL.

These drawings provide detailed measurements in millimeters.

Models: AM 950 C, AM 950 F, AM 950 C Decentralized Ventilation System, AM 950 C, Decentralized Ventilation System, Ventilation System

File Info : application/pdf, 40 Pages, 3.81MB

PDF preview unavailable. Download the PDF instead.

16101 mm am950c am950f en rev02

References

Adobe PDF Library 25.1.97

Related Documents

Preview Airmaster AM 950 C & AM 950 F Mounting Guide
Comprehensive guide for the mounting and installation of Airmaster AM 950 C and AM 950 F air handling units. Covers safety instructions, product specifications, transportation, storage, and detailed mounting procedures.
Preview Airmaster AM 950 C / AM 950 F Installation and Mounting Guide
Comprehensive guide for the correct and safe installation and mounting of Airmaster AM 950 C and AM 950 F ventilation units. Includes safety instructions, product specifications, and step-by-step mounting procedures.
Preview AIRMASTER AM 950 C / AM 950 F Installation and Mounting Manual
A comprehensive guide for the installation and mounting of AIRMASTER AM 950 C and AM 950 F ventilation units. This manual provides detailed instructions, safety precautions, technical specifications, and step-by-step procedures for a correct and safe setup.
Preview Air Handling Unit AM 950 F HH + VV - Technical Overview
Detailed technical overview and specifications for the AIRMASTER AM 950 F HH + VV air handling unit, including dimensions, connection points, and mounting options.
Preview Airmaster AM 950 C & AM 950 F Installation Guide
Comprehensive installation and network connection guide for Airmaster AM 950 C and AM 950 F ventilation systems. Covers electrical installation, component options, and system setup.
Preview Airmaster AM 950 C / AM 950 F Operation & Maintenance Manual
Comprehensive operation and maintenance guide for Airmaster AM 950 C and AM 950 F air handling units. Covers safety instructions, control functions, LED signals, internal control functions, and service procedures.
Preview AirMaster AM 950 F SSL Technical Specifications and Dimensions
Detailed technical specifications, dimensions, and connection information for the AirMaster AM 950 F SSL ventilation unit. Includes multilingual terminology for key components.
Preview Manuel d'installation Airmaster AM 950 C et AM 950 F : Raccordement électrique et réseau
Guide détaillé pour l'installation et le raccordement électrique et réseau des unités de ventilation Airmaster AM 950 C et AM 950 F. Inclut les consignes de sécurité et les spécifications techniques.