Introduction
The ProSense DPM1 series offers simple, low-cost digital displays for analog process and DC voltage signals. These meters feature a 4-digit red LED display that can be easily scaled into any engineering units from -1999 to 9999, with a selectable decimal point location. Two-point linear scaling values can be entered manually or via a process teaching mode. The meters are powered by an external AC or DC power supply.
The compact 1/32 DIN housing minimizes panel space, and the meter face provides an IP65 rating for protection. Configuration parameters can be locked out to prevent unauthorized changes. ProSense digital panel meters are backed by a 3-year warranty.
Key Features
- Compact 48 x 24mm (1/32 DIN) size
- Simple menu-driven pushbutton configuration
- 10mm 4-digit red LED display (range: -1999 to 9999)
- Selectable decimal point location
- Supports process inputs: ±10V, ±20mA, ±100mV
- Supports DC Voltage inputs: ±200V, ±20V
- AC or DC powered
- Display scaling and process teaching modes available
- Configuration for direct or reverse acting linear processes
- Total configuration lock-out feature
- 3-year warranty
Available DPM1 Models
Model | Description | Weight (lbs) | Price |
---|---|---|---|
DPM1-A-H | ProSense digital panel meter, 1/32 DIN, 10mm 4-digit red LED, input current signal range(s) of +/- 20 mA, input voltage signal range(s) of +/- 200 VDC, +/- 20 VDC, +/- 10 VDC, +/- 100 mVDC, 85 to 265 VAC / 100 to 300 VDC operating voltage. | 0.2 | $93.00 |
DPM1-A-L | ProSense digital panel meter, 1/32 DIN, 10mm 4-digit red LED, input current signal range(s) of +/- 20 mA, input voltage signal range(s) of +/- 200 VDC, +/- 20 VDC, +/- 10 VDC, +/- 100 mVDC, 21 to 53 VAC / 10.5 to 70 VDC operating voltage. | 0.2 | $93.00 |
Technical Specifications
Parameter | Input | Accuracy (@ 23°C ±5°C) | Power Supply and Fuses | Power Consumption | Conversion | Display | Environmental Conditions | Frontal Protection | Agency Approvals | |
---|---|---|---|---|---|---|---|---|---|---|
Voltage | Current | |||||||||
Range | ±200V (fixed), ±20V (fixed), ±10V, ±100mV | ±20mA | Max error: ±(0.1% of reading +3 digits) Temperature coefficient: 100 ppm/°C Warm-Up time: 5 minutes |
DPM1-A-H: 85-265VAC 50/60Hz or 100-300VDC (Recommended fusing: 0.1A/250V) | 1.8W | Technique: Sigma-Delta Resolution: ±15 bits Conversion rate: 20 times/sec |
Range: -1999 to 9999, selectable decimal point position Type: 4-digit 10mm (0.4"), red Display refresh rate: 4 times/sec Display/input overrange indication: 0vE |
Operating temp: -10°C to +60°C (14°F to 140°F) Storage temp: -25°C to +85°C (-13°F to 185°F) Relative humidity: <95% @ 40°C (104°F) Maximum altitude: 2000m |
IP65 | CE, No corrosive gases permitted |
Resolution | 0.1V, 0.01V, 1mV, 0.1mV | 0.01mA | ||||||||
Input Impedance | Volts: 1MΩ mV: 100MΩ |
mA: 20Ω | DPM1-A-L: 21-53VAC 50/60Hz or 10.5-70VDC (Recommended fusing: 0.5A/250V) |
Wiring and Installation
The DPM1 series meters feature two terminal blocks for connections: CN1 for power supply and CN2 for signal input.
Wiring Terminals
Terminal Block | Pin | Function (AC Supply) | Function (DC Supply) | Function (Signal Input) |
---|---|---|---|---|
CN1 | 1 | Neutral | -VDC | N/A |
2 | Line | +VDC | ||
CN2 | 1 | N/A | N/A | -IN (common) |
2 | +100mV DC | |||
3 | +20mA | |||
4 | +10/20VDC | |||
5 | +200VDC |
Connector Specifications
Parameter | CN1 | CN2 |
---|---|---|
Wire cross section | 0.08 to 2.5mm² (28 to 12 AWG) | 0.08 to 0.5mm² (28 to 20 AWG) |
Strip length | 8 to 9mm | 5 to 6mm |
Manufacturer | Wago 231-202/026-000 | Wago 733-105 |
Programming Keys
Located on the bottom of the meter, these keys are used for configuration:
- ENTER: Enters configuration and validates data and parameters.
- SHIFT: Selects mode or shifts the blinking digit during configuration.
- UP: Increases the value of the blinking digit during configuration.
Wire Connection
Use the provided insertion tool (or a screwdriver with appropriate blade size) to connect wires. For each terminal, insert the wire into the terminal opening while using the tool to open the internal clip. Once the wire is in place, release the tool to secure the connection.
Dimensions
Overall dimensions are 48 x 24 x 95mm (1/32 DIN). The required panel cutout is 45 x 22mm, accommodating a maximum panel thickness of 7mm. The case material is Polycarbonate UL 94 V-0.
Quick Start Guide
A QR code is available to access the DPM1-A-H and DPM1-A-L Series Quick Start Guide.
DPM1 Series Selection Guide (Process, Electrical, Pulse/Frequency Inputs)
The ProSense DPM family includes various models beyond the DPM1 series, offering different sizes and input capabilities. The following tables detail DPM1 models based on input type.
Process Input Selection Guide (DPM1 Models)
Model | Size | Display | Inputs | Outputs | Power | Price |
---|---|---|---|---|---|---|
DPM1-A-LP | 1/32 DIN | 10mm, Red LED*, -1999 to 9999, Selectable decimal point | 4-20mA | None | Loop Powered | $72.00 |
DPM1-A-H | 1/32 DIN | 10mm, Red LED*, -1999 to 9999, Selectable decimal point | ±20mA, ±100mV, ±10V, ±20V, ±200V | None | 85-265 VAC, 50/60 Hz / 100-300 VDC | $93.00 |
DPM1-A-L | 1/32 DIN | 10mm, Red LED*, -1999 to 9999, Selectable decimal point | ±20mA, ±100mV, ±10V, ±20V | None | 21-53 VAC, 50/60 Hz / 10.5-70 VDC | $93.00 |
DPM1-T-H | 1/32 DIN | 10mm, Red LED, -1999 to 9999 | RTD Pt100 (3-wire), TC Type J, K, T or N | 2 Relays Form A SPST Normally Open | 85-265 VAC, 50/60 Hz / 100-300 VDC | $103.00 |
DPM1-T-L | 1/32 DIN | 10mm, Red LED, -1999 to 9999 | RTD Pt100 (3-wire), TC Type J, K, T or N | 2 Relays Form A SPST Normally Open | 21-53 VAC, 50/60 Hz / 10.5-70 VDC | $103.00 |
DPM1-A-2R-H | 1/32 DIN | 8mm, Red LED, -1999 to 9999, Selectable decimal point | ±20mA, ±100mV, ±10V, ±60V | 2 Relays Form C SPDT | 85-265 VAC, 50/60 Hz / 100-300 VDC | $113.00 |
DPM1-A-2R-L | 1/32 DIN | 8mm, Red LED, -1999 to 9999, Selectable decimal point | ±20mA, ±10V | 2 Relays Form C SPDT | 21-53 VAC, 50/60 Hz / 10.5-70 VDC | $113.00 |
DPM1-A-A2R-H | 1/32 DIN | 8mm, Red LED, -1999 to 9999, Selectable decimal point | ±20mA, ±10V, ±200V, 100-100k Ohm potentiometer, 1k-50k Ohm resistance, RTD Pt100 (3-wire), RTD Pt1000 (4-wire), TC Type J, K, T or N | 4 Relays Form A Normally Open with shared common, 4-20mA | 85-265 VAC, 50/60 Hz / 100-300 VDC | $152.00 |
DPM1-A-A2R-L | 1/32 DIN | 8mm, Red LED, -1999 to 9999, Selectable decimal point | ±20mA, ±10V, ±200V, 100-100k Ohm potentiometer, 1k-50k Ohm resistance, RTD Pt100 (3-wire), RTD Pt1000 (4-wire), TC Type J, K, T or N | 4 Relays Form A Normally Open with shared common, 4-20mA | 21-53 VAC, 50/60 Hz / 10.5-70 VDC | $152.00 |
Electrical Input Selection Guide (DPM1 Models)
Model | Size | Display | Inputs | Outputs | Power | Price |
---|---|---|---|---|---|---|
DPM1-E-H | 1/32 DIN | 10mm, Red LED, -1999 to 9999, Selectable decimal point | 100/600 VAC or VDC, 1A/5A AC or DC | None | 85-265 VAC, 50/60 Hz / 100-300 VDC | $93.00 |
DPM1-E-L | 1/32 DIN | 10mm, Red LED, -1999 to 9999, Selectable decimal point | 100/600 VAC or VDC, 1A/5A AC or DC | None | 21-53 VAC, 50/60 Hz / 10.5-70 VDC | $93.00 |
Pulse, Frequency Input Selection Guide (DPM1 Models)
Model | Size | Display | Inputs | Outputs | Power | Price |
---|---|---|---|---|---|---|
DPM1-P-H | 1/32 DIN | 10mm, Red LED, 0 to 9999, Selectable decimal point | 7kHz (tachometer rpm or rate modes), 9999Hz (frequency meter mode) | None | 85-265 VAC, 50/60 Hz / 100-300 VDC | $93.00 |
DPM1-P-L | 1/32 DIN | 10mm, Red LED, 0 to 9999, Selectable decimal point | 7kHz (tachometer rpm or rate modes), 9999Hz (frequency meter mode) | None | 1-53 VAC, 10.5-70 VDC | $93.00 |
DPM1-P-A2R-H | 1/32 DIN | 8mm, Red LED, 0 to 9999, Selectable decimal point | 12kHz (tachometer rpm or rate modes), 9999Hz (frequency mode), 100Hz (duty/PWM mode) | 2 Relays Form A SPST Normally Open, 4-20mA | 85-265 VAC, 50/60 Hz / 100-300 VDC | $113.00 |
DPM1-P-A2R-L | 1/32 DIN | 8mm, Red LED, 0 to 9999, Selectable decimal point | 12kHz (tachometer rpm or rate modes), 9999Hz (frequency mode), 100Hz (duty/PWM mode) | 2 Relays Form A SPST Normally Open, 4-20mA | 21-53 VAC, 50/60 Hz / 10.5-70 VDC | $113.00 |
* Illumination based on available loop current and will not be as bright as the powered Digital Panel Meters.