Safety Information
Warning: Electric current! Danger to life! Installation, commissioning, and maintenance work must be carried out by qualified personnel only.
Product Overview
The Eaton S711 is a series of soft starters designed for three-phase motor control. This document provides installation, specification, and operation guidance.
Available Models:
- S711-34012, S711-34017, S711-34025, S711-34032, S711-34047
- S711-34062, S711-34075, S711-34088, S711-34115
- S711-34140, S711-34170, S711-34210, S711-34250
- S711-34320, S711-34410, S711-34480, S711-34560
The S711 Connect App is available for download on the App Store and Google Play.
Main power connections are typically made to terminals 1L1, 3L2, 5L3 for input and 2T1, 4T2, 6T3 for output, connecting to a 3-phase motor (M).
Technical Specifications
Model | Ie (A) | FS | UL Rating, 50°C | IEC Rating Index 1, 40°C | IEC Rating Index 2, 40°C |
---|---|---|---|---|---|
S711-34012 | 12 | 1 | 10 FLA, 480 V AC, 50/60 Hz | AC-53b | 3.5-20: 340 |
S711-34017 | 17 | 1 | 15 FLA, 480 V AC, 50/60 Hz | AC-53b | 3.5-20: 340 |
S711-34025 | 25 | 1 | 22 FLA, 480 V AC, 50/60 Hz | AC-53b | 3.5-20: 340 |
S711-34032 | 32 | 1 | 29 FLA, 480 V AC, 50/60 Hz | AC-53b | 3.5-20: 340 |
S711-34047 | 47 | 1 | 43 FLA, 480 V AC, 50/60 Hz | AC-53b | 3.5-20: 340 |
S711-34062 | 62 | 2 | 56 FLA, 480 V AC, 50/60 Hz | AC-53b | 3.5-20: 340 |
S711-34075 | 75 | 2 | 67 FLA, 480 V AC, 50/60 Hz | AC-53b | 3.5-20: 340 |
S711-34088 | 88 | 2 | 82 FLA, 480 V AC, 50/60 Hz | AC-53b | 3.5-20: 340 |
S711-34115 | 115 | 2 | 107 FLA, 480 V AC, 50/60 Hz | AC-53b | 3.5-20: 340 |
S711-34140 | 140 | 3 | 121 FLA, 480 V AC, 50/60 Hz | AC-53b | 3.5-20: 580 |
S711-34170 | 170 | 3 | 153 FLA, 480 V AC, 50/60 Hz | AC-53b | 3.5-20: 580 |
S711-34210 | 210 | 3 | 191 FLA, 480 V AC, 50/60 Hz | AC-53b | 3.5-20: 580 |
S711-34250 | 250 | 3 | 232 FLA, 480 V AC, 50/60 Hz | AC-53b | 3.5-20: 580 |
S711-34320 | 320 | 4 | 288 FLA, 480 V AC, 50/60 Hz | AC-53b | 3.5-20: 580 |
S711-34410 | 410 | 4 | 371 FLA, 480 V AC, 50/60 Hz | AC-53b | 3.5-20: 580 |
S711-34480 | 480 | 4 | 444 FLA, 480 V AC, 50/60 Hz | AC-53b | 3.5-20: 580 |
S711-34560 | 560 | 4 | 518 FLA, 480 V AC, 50/60 Hz | AC-53b | 3.5-20: 580 |
Control Voltage: AC 110-240 V or DC 24 V.
Nominal Current Rating: Ranges from 12 A to 560 A.
Input/Output Voltage Rating: 400 V AC (200-575 V ±10%).
Phase Reference: 3-phase input/3-phase output.
Dimensions and Mounting
Frame Size 1 & 2 (e.g., S711-34012 to S711-34115):
- Dimensions: Approximately 128 mm (width) x 252 mm (height) x 174.5 mm (depth).
- IP Rating: IP 20.
- Weight: Approximately 3.6 kg (7.94 lbs).
Frame Size 3 (e.g., S711-34140 to S711-34250):
- Dimensions: Approximately 202.6 mm (width) x 385.3 mm (height) x 218.4 mm (depth).
- IP Rating: IP 00.
- Weight: Approximately 11.8 kg (26.02 lbs).
Frame Size 4 (e.g., S711-34320 to S711-34560):
- Dimensions: Approximately 222 mm (width) x 545 mm (height) x 204.5 mm (depth).
- IP Rating: IP 00.
- Weight: Approximately 20.1 kg (44.32 lbs).
Mounting Position: The device can be mounted vertically or horizontally with a maximum tilt of 15 degrees in any direction.
Drilling Pattern: Specific drilling patterns and dimensions are provided for mounting based on frame size (FS1-FS4), requiring M5 or M8 screws. Clearances are required between starters and from solid surfaces.
Cooling: The device requires adequate ventilation. Operating temperature range is -25°C to +60°C (-13°F to +140°F), with derating above 40°C (104°F).
Wiring and Connections
Terminal Connections:
- Input Power: 1L1, 3L2, 5L3.
- Output Power: 2T1, 4T2, 6T3.
- Wire Size and Torque: Refer to specifications for appropriate wire gauges (e.g., 6-70 mm², AWG10-2/0) and torque settings (e.g., 4 Nm, 40 Nm) for different frame sizes.
Installation Types:
- In-line Installation: Standard wiring configuration for connecting the soft starter between the power supply and the motor.
- Inside Delta Installation: Wiring configuration for motors connected in a delta configuration.
Control Inputs (DC and AC):
- DC Input (24V DC): Terminals [1] for Start/Stop, [2] for Enable/Reset, [3] for Digital Input 3 (default: Cmd Override: Terminal), [4] for Digital Input 4 (default: Ext. Fault NO), [Ti+, Ti-] for Motor thermistor input.
- AC Input (110-240V AC): Similar control input functions are available.
- Relay Outputs: Terminals [13, 14] for Main Contactor Output, [23, 24] for Relay Output 2 (default: Bypassed), [33, 34] for Relay Output 3 (default: Fault).
- Communication: [A, B, COM] for Modbus RTU.
Attention: Default control source is keypad. For terminal control, use Digital Input 3 or change parameter P1.4. Default PIN for parameter access is 000000.
Installation Steps
Detailed installation steps are provided for Frame Size 3 and Frame Size 4, including:
- Mounting the device using specified screws and torque settings (e.g., ≤0.7 Nm, ≤2.5 Nm).
- Ensuring correct clearances (e.g., ≤25 mm, ≥15 mm, 11 mm, 13 mm, 17 mm, 27 mm).
- Connecting power and control wiring according to diagrams.
The S711 Connect App interface includes controls for Ready, Run, Trip, Local BLE, Reset, Remote, Back, and OK functions.
EU Conformity
Eaton Industries GmbH declares that the radio equipment S711-34... and S711-KEY-LCD comply with Directive 2014/53/EU. The full text of the EU declaration of conformity is available at Eaton.com/documentation.