Siemens INSTALLATION INSTRUCTIONS

Models ILED-XC and ILED-XW

Intelligent Remote Lamps with Dual Isolators

INTRODUCTION

The Models ILED-XC (round plate), P/N S54370-B6-A1, and ILED-XW (rectangular plate), P/N S54370-B5-A1, Addressable Remote Lamps from Siemens Industry, Inc., are shown in Figure 1. They operate as an additional tri-color LED indicator for a device in the device loop circuit of the Desigo FC2025/FC2050/FV2025/FV2050 and Cerberus PRO FC922/FC924/FV922/FV924 Fire Alarm Systems. The ILED-X can be used when a device already has an accessory. The ILED-X can be installed at any location of a device loop, and it remotely indicates the status of the device(s) in that same loop.

Figure 1: ILED-XC and ILED-XW Remote Lamps

[Image description: Two circular devices labeled 'REMOTE ALARM LAMP'. The left one, ILED-XC, is round. The right one, ILED-XW, is rectangular.]

MODE OF OPERATION

The ILED-X must have a unique address when it works in the device loop. The ILED-X modules support two operation modes: polarity insensitive mode and isolator mode. The modules can be wired for either mode (refer to Figures 3 and 4). During the isolator mode, the built-in dual isolators will work at both sides of the module to isolate the line short in front or behind the module.

CONTROLS AND INDICATORS

The LED indicator is capable of flashing any one of three distinct colors: green, yellow, or red, based on logic in the system configuration tool.

Flash Color Condition Flash Intervals (Seconds)
Green Normal supervisory operation 10
Amber Device is in trouble 4
Red Alarm 1
No Flashes No power or need to be replaced -

NOTE: The system logic and programming determine when and what color the ILED-X will blink.

[Warning Symbol] Observe precautions for handling Electrostatic Sensitive Devices.

Document ID: A6V101055484_en--_a

Siemens Industry, Inc.
Building Technologies Division

PROGRAMMING

Refer to Figure 2 for the location of the programming holes:

Figure 2: ILED-X Printed Circuit Board

[Image description: A diagram of a circuit board with numbered points (5, 6, 1b) and labeled 'PROGRAMMING HOLES'. An arrow points to the holes with the text 'PROGRAMMING HOLES ARE POLARITY INSENSITIVE - PLUG CAN BE INSERTED IN ANY DIRECTION.']

To program the ILED-X, follow the steps listed below:

  1. Determine a unique address for the ILED-X.
  2. Connect the ILED-X to the DPU Device Programming Unit by inserting the plug from the DPU cable provided with the DPU into the programming holes on the ILED-X board at either direction (polarity insensitive).
  3. Follow the instructions in the DPU Manual, P/N 315-033260, to program the ILED-X to the desired address. Record the device address on the label located on the back of the ILED-X front panel.
  4. Desigo FC2025/FC2050/FV2025/FV2050 and Cerberus PRO FC922/FC924/FV922/FV924 Fire Alarm Systems: In the Configuration tool, assign the ILED-X to the output of a logic function. For further information, refer to the Configuration Tool Manual of Desigo FC2025/FC2050/FV2025/FV2050 and Cerberus PRO FC922/FC924/FV922/FV924 Fire Alarm Systems, Document ID A6V10315023.
  5. The ILED-X can now be installed and wired to the system.

WIRING

CAUTION: Deactivate P2 circuit by either or both of the following: Using the PMI, bypass the circuit being modified, and/or physically disconnect the circuit from the P2 source.

Warning: Disconnect BATTERY and AC prior to working on equipment.

NOTE: The ILED-X modules support two operation modes: polarity insensitive mode and isolator mode. The module can be wired for either mode (refer to Figures 3 and 4). During the isolator mode, the built-in dual isolators will work at both sides of the module to isolate the line short in front or behind the module. During the polarity insensitive mode, switching Line1 and Line2 has no effect on performance.

Recommended wire size:

Wire larger than 14 AWG can damage the connector.

Figure 3: ILED-X polarity insensitive mode wiring

[Image description: Wiring diagram showing connections for 'LINE 1' and 'LINE 2' to 'NEXT ADDRESSABLE DEVICE' and 'CONTROL PANEL OR PREVIOUS ADDRESSABLE DEVICE'. Points 5, 6, and 1b are indicated on a circuit board representation.]

Figure 4: ILED-X isolator mode wiring

[Image description: Wiring diagram similar to Figure 3, illustrating isolator mode connections for 'LINE' and 'LINE +' to 'NEXT ADDRESSABLE DEVICE' and 'CONTROL PANEL OR PREVIOUS ADDRESSABLE DEVICE'. Points 5, 6, and 1b are indicated on a circuit board representation.]

NOTES:

  1. In the device line, up to 30 of any compatible devices in polarity insensitive mode with 20 ohms max line resistance can be isolated between two modules in isolator mode in a Class A Style 6 wiring.
  2. In the device line, up to 30 of any compatible devices in polarity insensitive mode with 20 ohms max line resistance can be isolated behind one module in isolator mode in a Class B Style 4 wiring.
  3. HLIM isolator module and SBGA-34 sounder base cannot be used in the same loop with the modules in isolator mode.

INSTALLATION

NOTE: Be sure to program the ILED before installing the unit.

The ILED-X may be placed at any location on the device loop. Use a UL-listed/recognized single-gang switch box (user supplied) for mounting the ILED-XW. Use a UL-listed/recognized 4-inch octagonal conduit box (user supplied) for mounting the ILED-XC. Refer to Figures 5 and 6 for typical ILED-X installation.

Figure 5: Mounting the ILED-XW

[Image description: Diagram showing the ILED-XW mounted in a single-gang switchbox. Text indicates 'DO NOT USE REAR CONDUIT ENTRY' and 'SINGLEGANG SWITCHBOX (USER SUPPLIED)'.]

Figure 6: Mounting the ILED-XC

[Image description: Diagram showing the ILED-XC mounted in a 4-INCHES OCTAGONAL BOX, 1/8-INCHES DEEP.]

ELECTRICAL RATINGS

Operating Voltage 13 – 32 Vdc
Max. average current (RMS) 500μΑ

The number of ILED-X modules on the device loop must be included in the total count of intelligent field devices. For the restriction of the total number of devices in the device loop, refer to the device loop circuit of the Desigo FC2025/FC2050/FV2025/FV2050 and Cerberus PRO FC922/FC924/FV922/FV924 Fire Alarm Systems.

Cyber security disclaimer

Siemens products and solutions provide security functions to ensure the secure operation of building comfort, fire safety, security management and physical security systems. The security functions on these products and solutions are important components of a comprehensive security concept.

It is, however, necessary to implement and maintain a comprehensive, state-of-the-art security concept that is customized to individual security needs. Such a security concept may result in additional site-specific preventive action to ensure that the building comfort, fire safety, security management or physical security system for your site are operated in a secure manner. These measures may include, but are not limited to, separating networks, physically protecting system components, user awareness programs, defense in depth, etc.

For additional information on building technology security and our offerings, contact your Siemens sales or project department. Siemens strongly recommends customers to follow our security advisories, which provide information on the latest security threats, patches and other mitigation measures.

Learn more: http://www.siemens.com/cert/en/cert-security-advisories.htm

FCC Statement

[Warning Symbol] WARNING!

Installation and usage of equipment not in accordance with instructions manual may result in:

• Install and use equipment in accordance with instructions manual

• Read the following information

This equipment generates, uses, and can radiate radio frequency energy and if not installed and used in accordance with the instructions manual, may cause interference to radio communications.

It has been tested and found to comply with the limits for a Class A computing device pursuant to Part 15 of FCC Rules, which are designed to provide reasonable protection against such interference when operated in a commercial environment.

Operation of this equipment in a residential area is likely to cause interference in which case the user at his own expense will be required to take whatever measures may be required to correct the interference.

Models: ILED-XC, ILED-XW, ILED-XW Intelligent Remote Lamps with Dual Isolators, Intelligent Remote Lamps with Dual Isolators, Remote Lamps with Dual Isolators, Lamps with Dual Isolators, Dual Isolators

File Info : application/pdf, 8 Pages, 725.73KB

PDF preview unavailable. Download the PDF instead.

?tmstv=1676769218

References

DAVID GREENSPAN Adobe PDF Library 10.0

Related Documents

Preview Siemens XTRI-M Addressable Interface Module Installation Instructions
Installation instructions and technical details for the Siemens XTRI-M Addressable Interface Module with Dual Isolators, covering wiring, programming, mounting, and electrical ratings for fire alarm systems.
Preview Siemens FC2025/FC2050/FT2050 Fire Alarm Control Panel Installation Instructions
This document provides detailed installation instructions for the Siemens FC2025, FC2050, FT2050, FV2025, FV2050, and VR2005 Fire Alarm Control Panels. It covers system overview, electrical characteristics, module locations, wiring, and battery calculations.
Preview Siemens FS920 Fire Alarm Control Panel Installation Instructions
Comprehensive installation guide for Siemens FS920 Fire Alarm Control Panel series, including FC922, FC924, FT924, FV922, FV924, and VR2005. Covers system overview, installation, wiring, electrical characteristics, limitations, and battery calculations.
Preview Siemens Desigo Fire Safety: Comprehensive Fire Protection Solutions
Explore the Siemens Desigo Fire Safety system, a comprehensive portfolio of innovative fire detection, alarm signaling, voice communication, and operator control technologies designed for diverse environments. Learn about its scalability, advanced ASAtechnology™ detectors, and integrated solutions for total building safety.
Preview Siemens Cerberus PRO Intelligent Voice Communication System
Detailed technical data sheet for the Siemens Cerberus PRO intelligent voice communication system, outlining its advanced fire protection and integrated voice evacuation capabilities. Covers system specifications, components, and ordering information.
Preview Siemens VCA2002-A1 Card Cage Installation Instructions
Detailed installation instructions for the Siemens VCA2002-A1 Card Cage, a component of the FS20 Fire Voice Control System, covering its features, pre-installation, operation, mounting, card installation, wiring, and electrical ratings.
Preview Siemens Connect X300 Installation Instructions
This document provides installation instructions for the Siemens Connect X300 gateway, a device that connects fire alarm control panels to cloud services. It details the gateway's features, physical connections, mounting options, wiring specifications, and basic configuration steps.
Preview Siemens Cerberus PRO FC922/FC924 Addressable Fire Alarm Control Panels - Data Sheet
Data sheet detailing the Siemens Cerberus PRO FC922 (252-point) and FC924 (504-point) addressable fire alarm control panels (FACPs) for mid-size building applications. Includes specifications, system features, components, and optional accessories.