R. STAHL 8530/1-MCB-STA103N-C25-000-4 Line Protection Circuit Breaker
Article Number: 293858
System Components for System Technology
Product: Line Protection Circuit Breaker
The R. STAHL 8530 series line protection circuit breakers offer good current limitation for short circuits and high switching capacity of 10, 15, or 25 kA. This ensures minimal load on lines and high selectivity to upstream fuses. The components are modular and available in 1 to 4-pole versions for nominal currents from 0.5–63 A. The maximum installation capacity is 4.5 partial units (UP).
Key Features:
- Disconnecting function according to EN 60947-2
- Energy limitation class 3
- Easy replacement or system extension with modular circuit breakers
- Simple plug-in mounting on a DIN rail in Ex e enclosures
- Fixed thermal-magnetic releases
- Ergonomic control lever for safe switching on and off
- Padlock protection (accessories) prevents re-operation during maintenance
Technical Characteristics
Explosion Protection
- Application Area (Zones): 1, 2
- Application Area (Zones) Note: Usable in Zone 21 / 22 with Ex tb / tc enclosure protection
- IECEx Gas Certificate: IECEx FMG 19.0029U
- IECEx Gas Explosion Protection: Ex db eb IIC Gb
- ATEX Gas Certificate: FM19ATEX0191U
- ATEX Gas Explosion Protection: II 2 G Ex db eb IIC Gb
- Certificates: ATEX (FM), Brazil (ULB), China (CQST), IECEx (FM)
Electrical Characteristics
- Rated Operational Voltage AC: 230/400 V
- Rated Service Current: 25 A
- Frequency: 50/60 Hz
- Rated Switching Capacity: 10 kA
- Electrical Service Life: 2 x 104
- Mechanical Service Life: 2 x 104
- 1st Auxiliary Function: None
- 2nd Auxiliary Function: None
- Tripping Characteristic: C
- Number of Poles: 3 poles + N
Ambient Conditions
- Ambient Temperature: -40 °C ... 70 °C (-40 °F ... 158 °F)
- Ambient Temperature Note: Different ambient temperatures based on current certificates, upon request.
Mechanical Characteristics
- Degree of Protection (IP) (IEC 60529): IP2X
- Housing Material: Thermoplastic
- Minimum Connection Terminal Size: 1.5 mm²
- Maximum Connection Terminal Size: 25 mm²
- Minimum AWG Connection Terminal Size: 16 AWG
- Maximum AWG Connection Terminal Size: 4 AWG
- Minimum Connection Terminal Size 2: 1.5 mm²
- Maximum Connection Terminal Size 2: 10 mm²
- Minimum AWG Connection Terminal Size 2: 16 AWG
- Maximum AWG Connection Terminal Size 2: 8 AWG
- Minimum Tightening Torque: 2 N·m
- Maximum Tightening Torque: 3 N·m
- Connection Terminal Note: 2 conductors (upper and lower chamber) simultaneously: Upper and lower chamber max. 16 / 10 mm² (Connection can be made with a maximum difference in cross-section between the upper and lower chamber.)
- Allowed combination possibilities of connection terminals are indicated in the operating instructions.
Dimensions
- Width: 110 mm (4.33 in)
- Length: 165 mm (6.5 in)
- Mounting Depth: 138.3 mm (5.44 in)
Mounting / Installation
- Tightening Torque: 2–3 N·m
- Tightening Torque in lbf·in: 17.7 ... 26.6 lbf·in
- Auxiliary Contact Tightening Torque: 0.4–0.6 N·m
- Auxiliary Contact Tightening Torque in lbf·in: 3.5 ... 5.3 lbf·in
Technical Drawings
Technical drawings are subject to change.
Tripping Characteristic Curve C:
The graph shows the tripping characteristic for the circuit breaker, illustrating the relationship between multiples of the rated current (I/In) and tripping time in seconds for AC and DC circuits. The curve indicates the limit from the cold state.
Overall Dimensions (all dimensions in mm [inches])
Diagrams show the physical dimensions of the 8530/1 unit, indicating width, length, and mounting depth, as well as the configuration for 3 poles + N without auxiliary contact.
Accessories
Quadruple Locking Device
A locking/unlocking system that allows individual component locking using up to 4 cylinder locks.
- Part Number: 227232
Mounting Kit
- Description: A mounting kit for fixing the component to a mounting plate without a DIN rail.
- Part Number: 276618
Cylinder Lock
- Description: For locking (shackle Ø 3)
- Part Number: 107115
Technical specifications, dimensions, weights, construction types, and delivery options are subject to change. Figures are for indicative purposes only.