Bullard AC1000 Cool Climate Control Tube
Instruction Sheet
For optional use with Bullard Airline Respirators
Includes: AC1000 Cool Tube, belt bracket, nylon belt, and heat shield.
Function: The AC1000 is designed to supply a continuous flow of cool air to certain Bullard supplied air respirators.
CAUTION
AC1000 cannot be used with a low-pressure air source such as an ambient air pump.
WARNING
This climate control system is not recommended for cooling the air supply when the air temperature is less than 70°F (21°C). Since the system may cool the incoming air by more than 30°F (17°C), it is possible for ice to form in the breathing tube and reduce the airflow. Failure to observe this warning could result in death or serious injury or life-threatening delayed lung disease including but not limited to silicosis, pneumoconiosis, or asbestosis.
Air Pressure
Continually monitor the air pressure at the point-of-attachment while operating the respirator. A reliable air pressure gauge must be present to monitor the pressure.
WARNING
Failure to supply the minimum required pressure at the point-of-attachment for your hose length will reduce airflow and could result in death or serious injury or life-threatening delayed lung disease including but not limited to silicosis, pneumoconiosis, or asbestosis.
Users must always operate the Bullard climate control device within the required pressure range for the specific Bullard supplied air respirator being used. Using the correct pressure range ensures that the air flow delivered to the respirator meets NIOSH airflow requirements. Refer to the Supplied Air Pressure Tables located in the Bullard respirator user manuals to determine the correct pressure. If the respirator's user manual is unavailable, contact Bullard Customer Service.
Preparation and Use of the AC1000
- In an uncontaminated atmosphere, screw the hose connector fitting on the end of the breathing tube to the fitting on the AC1000. Tighten hose connectors firmly. (See Diagram 1)
- Lace the belt supplied with the Cool Tube through the belt bracket. Slots are provided for wearing the tube either vertically or horizontally on the waist. Refer to Heat Shield instructions.
- With the approved Bullard air supply hose connected to the air source and with air flowing into the hose, connect the quick-disconnect coupler on the air supply hose to the quick-disconnect nipple on the AC1000 Cool Tube.
- Adjust the air pressure at the point-of-attachment to within the approved pressure range. (See Diagram 2). Refer to the Supplied Air Pressure Table in the user manuals.
- Don the respirator by following the directions in the respirator instruction manual.
- To obtain cooler air, turn the air temperature control knob counterclockwise. (See Diagram 1). Maximum cooling is attained when the knob is fully open and there is maximum airflow out of the AC1000 exhaust port.
- To obtain air that is closer to ambient temperature, turn the air temperature control knob clockwise. If the knob is fully closed, the respirator will receive air at ambient temperature.
- When finished working, leave the work area wearing the respirator until in a clean air environment containing at least Grade D breathable air. With the air still flowing into the respirator, remove the respirator and then disconnect the air supply hose using the quick-disconnect coupler attached to the AC1000 Cool Tube.
Diagram 1 Description: Illustrates the AC1000 Cool Climate Control Tube with components labeled: Quick-Disconnect Nipple, Belt Bracket, Air Temperature Control Knob, Air Supply Hose, Breathing Tube, Point-of-attachment, Pressure gauge.
Diagram 2 Description: Shows the air source connection, indicating "Inlet Air Source Requires At Least Grade D Breathable Air".
Heat Shield Instructions
Assembly
- Determine whether the climate control device will be worn vertically or horizontally on the waist.
- If the device will be worn in the horizontal position, align the tube on the heat shield as shown in Image 3. If the tube will be worn in the vertical position, align the tube on the heat shield as shown in Image 4.
- Lace the belt supplied with the climate control device through both the heat shield slots and the climate control belt bracket slots.
- Use a plastic zip tie to secure the climate control unit to the heat shield.
Image 3 Description: Shows the AC1000 device worn horizontally on a belt with a heat shield.
Image 4 Description: Shows the AC1000 device worn vertically on a belt with a heat shield.
Contact Information
- Bullard Center
2421 Fortune Drive
Lexington, KY 40509 • USA
Tel: +1-859-234-6616
Fax: +1-859-246-0243 - Americas Operations
1898 Safety Way
Cynthiana, KY 41031 • USA
Tel: +1-859-234-6616
Fax: +1-859-234-8987 - Bullard GmbH
Dieselstrasse 8a
53424 Remagen • Germany
Tel: +49-2642 999980
Fax: +49-2642 9999829 - Bullard AsiaPacific Pte. Ltd.
51 Changi Business Park Central 2
#03-04 The Signature
Singapore 486066
Tel: +65 6745 0556
Website: www.bullard.com
✅ ISO 9001 certified
©2024 Bullard. All rights reserved.