Generac Protector Series Standby Generators
The Generac Protector Series offers reliable standby generators designed for liquid-cooled gaseous engine operation. These units provide essential backup power for homes and businesses.
Standard Features
- Evolution™ Controller
- Cellular Connectivity for Mobile Link® and Fleet
- Padlockable Control Panel Cover
- Quiet Operation
- Corrosion Resistant Aluminium Enclosure
- 5 Year/2,000 Hour Limited Warranty
- High Motor-Starting, Surge Capacity
- ±1% Digital Voltage Regulation
- <5% Total Harmonic Distortion Power Quality
- Fuel Efficiency
- Controller-Selectable Fuel Type - Propane or Natural Gas
- EPA Emissions Certified
- CA & MA Emissions Compliant Models
- 115 mph (185 km/h) Wind Speed Rating
- UL 2200 Listed
- SwRI Listed & Labeled allowing installation as close as 18 in (457 mm) from structure
Optional Field-Installable Features
- Push-Button Emergency Stop
- Cold Weather Operation Heaters
Generator Specifications
Generator Output
Voltage | RG04845 | RG06045 | RG08045 | |||
---|---|---|---|---|---|---|
Power (kW) | Current (A) | Power (kW) | Current (A) | Power (kW) | Current (A) | |
PROPANE | ||||||
120/240 V 1-Phase | 48 | 200 | 60 | 250 | 75 | 312 |
208/120 V 3-Phase | 48 | 167 | 60 | 208 | 75 | 260 |
240/120 V 3-Phase | 48 | 144 | 60 | 180 | 75 | 226 |
480/277 V 3-Phase | 48 | 72 | 60 | 90 | 75 | 113 |
NATURAL GAS | ||||||
120/240 V 1-Phase | 48 | 200 | 60 | 250 | 80 | 333 |
208/120 V 3-Phase | 48 | 167 | 60 | 208 | 80 | 278 |
240/120 V 3-Phase | 48 | 144 | 60 | 180 | 80 | 241 |
480/277 V 3-Phase | 48 | 72 | 60 | 90 | 80 | 120 |
Emergency Standby Power (ESP) Rating: Standby ratings apply to installations served by a reliable utility source. The ESP rating is applicable to varying loads for the duration of a power outage. The average power output over 24 hours shall not exceed 70% of the ESP rating.
Voltage Regulation
Type | Digital |
Sensing | Single Phase |
Regulation | ±1% |
Alternator System
RG04845 | RG06045 | RG08045 | ||
---|---|---|---|---|
Circuit Breaker (CB) Size (A) | 120/240 V 1-Phase | 200 | 300 | 400 |
208/120 V 3-Phase | 175 | 200 | 300 | |
240/120 V 3-Phase | 150 | 200 | 300 | |
480/277 V 3-Phase | 80 | 100 | 150 | |
Alternator Type | Synchronous | |||
Rotor Insulation Class | H | |||
Stator Insulation Class | H | |||
Telephone Interference Factor (TIF) | <50 | |||
Bearings | Sealed Ball | |||
Coupling | Flexible Disc | |||
Excitation System | Direct | |||
Total Harmonic Distortion | <5% |
Surge Capacity
Surge Amps at <0.4 Power Factor | RG04845 | RG06045 | RG08045 | |||
---|---|---|---|---|---|---|
15% Voltage Dip (A) | 30% Voltage Dip (A) | 15% Voltage Dip (A) | 30% Voltage Dip (A) | 15% Voltage Dip (A) | 30% Voltage Dip (A) | |
120/240 V 1-Phase | 100 | 300 | 150 | 413 | 283 | 600 |
208/120 V 3-Phase | 118 | 242 | 135 | 313 | 236 | 500 |
240/120 V 3-Phase | 144 | 260 | 117 | 289 | 204 | 432 |
480/277 V 3-Phase | 64 | 123 | 54 | 122 | 102 | 192 |
Engine System
RG04845 | RG06045-RG08045 | |
---|---|---|
Make | Generac | Generac |
Model | 4.5 L Inline 4-Cylinder, Naturally Aspirated | 4.5 L Inline 4-Cylinder, Turbocharged & Aftercooled |
Compression Ratio | 9.9:1 | 8.9:1 |
Lifter Type | Hydraulic | Hydraulic |
Oil Pump Type | Gear | Gear |
Oil Filter Type | Full Flow Spin-on Cartridge | Full Flow Spin-on Cartridge |
Crankcase Capacity (qt (L)) | 12 (11) | 12 (11) |
Temperature Derate | 1.7% per 10 °F above 77 °F (1.5% per 5 °C above 25 °C) | 1.7% per 10 °F above 77 °F (1.5% per 5 °C above 25 °C) |
Altitude Derate | 3% per 1,000 ft above 600 ft (1% per 100 m above 183 m) | 3% per 1,000 ft above 3,000 ft (1% per 100 m above 915 m) |
Exercise Speed (rpm) | 1,500 | 1,500 |
Operating Speed (rpm) | 1,800 | 1,800 |
Exhaust Flow at Rated Output (cfm (m³/min)) | 104 (2.9) | 181 (5.1) |
Governor
Type | Electronic |
Frequency Regulation | Isochronous |
Cooling System
RG04845 | RG06045-RG08045 | |
---|---|---|
Coolant | 50/50 (50% Ethylene Glycol) | |
Coolant System Capacity (US gal (L)) | 2.9 (11) | 4.5 (17) |
Water Pump Type | Belt Driven | |
Fan Type | Belt Driven | |
Fan Quantity | 1 | |
Maximum Ambient Air Temperature (°F (°C)) | 122 (50) |
Fuel System
Fuel Types | Liquid Propane (LP) Vapor or Natural Gas (NG) |
Fuel Type Configuration | Controller-Selected Only |
LP Vapor Pressure (in H2O (kPa)) | 7-14 (1.74-3.48) |
NG Pressure (in H2O (kPa)) | 3.5-14 (0.87-3.48) |
Fuel Shutoff Solenoid | Standard |
Fuel Consumption
Liquid Propane
Rated Load | RG04845 | RG06045 | RG08045 | |||
---|---|---|---|---|---|---|
(US gph) | (L/h) | (US gph) | (L/h) | (US gph) | (L/h) | |
Exercise | 0.7 | 2.6 | 0.9 | 3.4 | 0.9 | 3.4 |
25% | 2.9 | 11.0 | 2.1 | 7.9 | 2.6 | 9.8 |
50% | 4.2 | 15.9 | 4.4 | 16.7 | 5.7 | 21.6 |
75% | 5.3 | 20.1 | 6.8 | 25.7 | 8.3 | 31.4 |
100% | 6.6 | 25.0 | 8.4 | 31.8 | 10.8 | 40.9 |
Propane - 91,452 BTU/US gal (25.5 MJ/L); 36 ft³/US gal (0.27 m³/L); 2,540 BTU/ft³ (94.6 MJ/m³); 4.24 lb/US gal (0.508 kg/L)
Natural Gas
Rated Load | RG04845 | RG06045 | RG08045 | |||
---|---|---|---|---|---|---|
(cfh) | (m³/h) | (cfh) | (m³/h) | (cfh) | (m³/h) | |
Exercise | 101 | 2.9 | 103 | 2.9 | 103 | 2.9 |
25% | 201 | 5.7 | 257 | 7.3 | 292 | 8.3 |
50% | 336 | 9.5 | 432 | 12.2 | 534 | 15.1 |
75% | 447 | 12.7 | 618 | 17.5 | 799 | 22.6 |
100% | 607 | 17.2 | 808 | 22.9 | 1,063 | 30.1 |
Natural Gas - 1,036 BTU/ft³ (38.6 MJ/m³)
See Emissions Data Sheets for maximum fuel flow for EPA and SCAQMD permitting purposes.
Electrical System
System Voltage (V) | 12 |
Charge Alternator (A) | 35 |
Battery Charger (A) | 2.5 |
Recommended Battery (not included) | Flooded Lead Acid, Group 27, 600 CCA Minimum |
Maximum Battery Size | Flooded Lead Acid, Group 31, 750 CCA Minimum |
Enclosure
RG04845 | RG06045 | RG08045 | |
---|---|---|---|
Sound Level at Exercise Speed (dB(A) @ 23 ft [7 m]) | 68 | 68 | 68 |
Wind Speed Rating (mph (km/h)) | 115 (185) | 115 (185) | 115 (185) |
Color | Bisque |
Controller Features
- Two-Line Plain Text LCD: Simple user interface for ease of operation.
- Multi-Lingual: Supports English, French, Spanish, and Portuguese.
- Mode Switch: AUTO (Automatic Start on Utility failure. 7 day exerciser.), OFF (Stops unit. Power is removed. Control and charger still operate.), MANUAL (Start with starter control, unit stays on. If utility fails, transfer to load takes place.)
- Programmable start delay: Between 10 - 30 seconds (Standard 10 sec)
- Engine Start Sequence: Cyclic cranking: 16 sec on, 7 sec rest (90 sec maximum duration)
- Engine Warm-up: 5 sec
- Engine Cool-Down: 1 min
- Starter Lock-out: Starter cannot re-engage until 5 sec after engine has stopped.
- Smart Battery Charger: Standard
- Automatic Voltage Regulation with Over and Under Voltage Protection: Standard
- Automatic Low Oil Pressure Shutdown: Standard
- Overspeed Shutdown: Standard, 72 Hz
- High Temperature Shutdown: Standard
- Overcrank Protection: Standard
- Safety Fused: Standard
- Failure to Transfer Protection: Standard
- Low Battery Protection: Standard
- 50 Event Run Log: Standard
- Future Set Capable Exerciser: Standard
- Incorrect Wiring Protection: Standard
- Internal Fault Protection: Standard
- Common External Fault Capability: Standard
- Governor Failure Protection: Standard
Available Accessories
Control System Kits
- Generac Generator Connectivity Accessory, Cellular (GGCAC): Provides cellular connection for monitoring via Mobile Link and Fleet.
- Enclosure Mounted Emergency Stop Kit: Red push button switch replacing the generator emergency shutdown rocker switch.
- Remote Emergency Stop Kit, Surface Mount: Red push button switch with twist release, in an aluminum enclosure, mounts remotely.
- Remote Emergency Stop Kit, Flush Mount: Red push button switch with twist release, in a flush-mount aluminum enclosure.
- Remote Emergency Stop Kit, Break Glass: Spring-loaded switch behind breakable glass in an aluminum enclosure, mounts remotely.
- Generac Load Manager, 50 A: Optimizes generator performance by managing large electrical loads upon startup and shed.
- Generac Load Manager, 100 A: Optimizes generator performance by managing large electrical loads upon startup and shed.
- Generac LTE Propane Tank Fuel Level Monitor: Connects to 4G LTE cellular service to measure and report LP fuel levels.
Operating Environment Kits
- Battery Heater Kit: Recommended for temperatures below 32 °F (0 °C), externally powered by 120 VAC, 60 Hz.
- Engine Block Heater Kit: Recommended for temperatures below 0 °F (-18 °C), externally powered by 120 VAC, 60 Hz.
Installation Kits
- Base Plug Kit: Plugs for baseframe lifting holes to keep debris out.
Maintenance Kits
- 4.5 L Gaseous Engine Regular Maintenance Kit: Includes oil filter, oil funnel, air filter, and spark plugs.
- Bisque Paint Kit: For touching up generator enclosure paint.
Installation Drawings Summary
Detailed installation drawings are provided for the 48 kW and 60/80 kW models. These drawings illustrate overall dimensions, component locations (e.g., air intake, exhaust, oil fill, battery, control panel access), and mounting details. Key notes cover concrete pad requirements (e.g., minimum size and offset), service access, ventilation requirements (fresh air intake, discharge air), and compliance with applicable NFPA standards. Specific dimensions for various views (top, side, rear) are provided in millimeters and inches.