York AHE Series ECM Air Handlers Technical Guide

YORK Heating and Air Conditioning

Document ID: 697887-YTG-D-1012

Introduction

The YORK AHE Air Handler line offers advanced comfort, quiet operation, and flexible application capabilities. These units are shipped ready for installation in upflow, horizontal left, or horizontal right configurations with minimal adjustments, eliminating the need for special installation kits.

All JCI Unitary Products air handlers and coils utilize a TXV (Thermal Expansion Valve) for optimal performance and refrigerant control. While shipped with "Flex-coils" without a factory-installed metering device, an R-22 or R-410A TXV or orifice can be field-installed for refrigerant choice flexibility.

Key Features:

Note: Specifications are subject to change without notice due to continuous product improvement. Visit www.york.com for more information and www.ahridirectory.org for rating information.

Warranty: Standard 5-year limited parts warranty. Extended 10-year limited parts warranty available upon online registration within 90 days of purchase for replacement or new home construction closing.

Distribution Note: For distribution use only. Not to be used at point of retail sale.

Certifications: AHRI Certified, UL Listed (C US), ISO 9001 Certified Quality Management System.

Dimensions & Duct Connection Dimensions

Diagram showing an air handler unit with various dimensions labeled A through K. Key components indicated are Blower Compartment, Refrigerant Connections, Drain Connections (for Upflow and Horizontal Applications), Filter Access, Circuit Breaker Panel, Top Outlet Dimensions, and Bottom Inlet Dimensions.

Dimensions Table

Models Dimensions (inches) Wiring Knockouts Refrigerant Connections Line Size
Height (A) Width (B) Depth (C) D E F Power Control Liquid Vapor
AHE18B/AHE22B/AHE24B/AHE30B 46 17 1/2 21 1/2 16 1/2 13-29/32 16 1/2 7/8 (1/2) 7/8 (1/2) 3/4 3/8
AHE34C/AHE36C 52 21 21 1/2 20 17-13/32 20 1-3/8(1) - 7/8 -
AHE42D/AHE48D/AHE60D 57 24 1/2 24 1/2 23-1/2 20-29/32 23-1/2 1-23/32 (1-1/4) - 7/8 -

Note: 1. All dimensions are in inches. 2. Actual size (conduit size).

Coil Technical Data

Models Application Refrig. Conn. Types Face Area (Sq. Ft.) Rows Deep Fins Per In. Coil Size Tube Geometry Tube Dia. Fin Type
AHE18B3XH21 Cooling / Heat Pump Sweat 3.4 2 14 (2) 14 x 17.5 1 x 0.866 3/8 Enhanced
AHE22B3XH21 Cooling / Heat Pump Sweat 3.9 2 14 (2) 16 x 17.5 1 x 0.866 3/8 Enhanced
AHE24B3XH21 Cooling / Heat Pump Sweat 3.9 3 12 (2) 16 x 17.5 1 x 0.866 3/8 Enhanced
AHE30B3XH21 Cooling / Heat Pump Sweat 3.9 3 12 (2) 16 x 17.5 1 x 0.866 3/8 Enhanced
AHE34C3XH21 Cooling / Heat Pump Sweat 3.9 3 12 (2) 16 x 17.5 1 x 0.866 3/8 Enhanced
AHE36C3XH21 Cooling / Heat Pump Sweat 4.9 3 12 (2) 20 x 17.5 1 x 0.866 3/8 Enhanced
AHE42D3XH21 Cooling / Heat Pump Sweat 5.4 3 12 (2) 22 x 17.5 1 x 0.866 3/8 Enhanced
AHE48D3XH21 Cooling / Heat Pump Sweat 5.8 3 11 (2) 24 x 17.5 1 x 0.866 3/8 Enhanced
AHE60D3XH21 Cooling / Heat Pump Sweat 6.8 3 12 (2) 28 x 17.5 1 x 0.866 3/8 Enhanced

Cooling Capacity Data

The following table provides cooling capacity (MBH) data for various YORK AHE series air handlers under different evaporator temperatures and corresponding R-410A pressures. Actual capacity varies with the outdoor AC or HP used with the system.

Models Rated CFM² Entering Air Dry/Wet Bulb (°F) MBH @ Evap. Temp. and Corresponding R-410A Pressure (°F/PSIG)
35/107.9 40/118.9 45/130.7 50/143.3
AHE18B 610 85/72 37.9 33.7 28.3 23.3
80/67 31.8 27 22.5 17.6
75/62 26.4 21.5 16.7 11.6
70/57 20.7 18.4 15.8 13.5
AHE18B 850 85/72 49.7 43.2 36.9 28.4
80/67 42.1 35.1 28.8 22.5
75/62 33.7 28 21.4 14.7
70/57 26.5 23.8 20.3 16.9
AHE18B 585 85/72 37.9 33.8 29 24.4
80/67 31.7 27.7 23 22.8
75/62 26.4 22.1 19.5 15.8
70/57 20.2 18.4 16 13.5
AHE22B 795 85/72 47.7 42.6 35.3 30.3
80/67 40.1 34.7 28.9 22.8
75/62 32.7 27.1 24.7 19.1
70/57 25.7 23.5 20.5 17.1
AHE22B 985 85/72 55.5 47.5 41.6 34.4
80/67 45.8 40.1 32.5 22.8
75/62 38.1 31.7 28.2 23.2
70/57 29.9 27.8 23.9 20.3
AHE24B 585 85/72 38.7 34.4 30.1 24.7
80/67 33.6 28.9 23.9 18.9
75/62 27.2 22.7 17.8 12.8
70/57 21.2 18.6 16.2 13.7
AHE24B 795 85/72 50.8 45.2 38.4 32.0
80/67 43.7 36.8 31 24.0
75/62 35.7 29.5 23.1 16.1
70/57 27.9 24.5 21 17.6
AHE24B 985 85/72 64.9 54 45.6 37.8
80/67 52.3 44.6 36.9 28.4
75/62 42.2 35.2 26.8 19.3
70/57 33.6 29.6 25.4 21.4
AHE30B 585 85/72 38.7 34.4 30.1 24.7
80/67 33.6 28.9 23.9 18.9
75/62 27.2 22.7 17.8 12.8
70/57 21.2 18.6 16.2 13.7
AHE30B 795 85/72 50.8 45.2 38.4 32.0
80/67 43.7 36.8 31 24.0
75/62 35.7 29.5 23.1 16.1
70/57 27.9 24.5 21 17.6
AHE30B 985 85/72 64.9 54 45.6 37.8
80/67 52.3 44.6 36.9 28.4
75/62 42.2 35.2 26.8 19.3
70/57 33.6 29.6 25.4 21.4
AHE34C 730 85/72 49.4 44 37.6 31.3
80/67 42 36.4 29.5 22.9
75/62 34 28.4 25.1 20.2
70/57 26.6 23.9 20.7 17.5
AHE34C 855 85/72 55.5 50.4 42.1 35.2
80/67 48 40.3 33.3 26.4
75/62 38.8 32.5 28.6 23.1
70/57 30.6 28 23.8 19.9
AHE34C 1000 85/72 63.3 56.3 48.3 40.1
80/67 54.2 46.4 38.3 29.8
75/62 43.8 36.3 32.9 26.4
70/57 34.4 31.7 27.4 23.0
AHE34C 1190 85/72 71.3 63.5 55.1 44.8
80/67 61.3 53.1 43.5 33.7
75/62 49.8 40.3 37.5 30.2
70/57 38.8 36.5 31.5 26.7
AHE36C 730 85/72 49.3 45.2 38.3 31.4
80/67 43 37.3 31 24.0
75/62 34.7 28.8 22.8 16.2
70/57 26.8 23.4 20.4 16.9
AHE36C 855 85/72 59.1 51 44.1 36.5
80/67 49.3 42.4 35.4 27.6
75/62 39.9 33.1 26.1 18.2
70/57 31.1 26.9 23.5 19.7
AHE36C 1000 85/72 65.2 59.5 51.2 41.3
80/67 56.4 48.3 39.9 31.3
75/62 45.8 38.1 29.7 20.8
70/57 35.7 31.2 26.9 22.6
AHE36C 1190 85/72 67.5 65.9 59.8 48.7
80/67 64.9 56.7 46.2 35.7
75/62 53.5 43.2 34.1 24.0
70/57 41.4 36.6 31.5 26.2
AHE42D 820 85/72 56.6 51.1 42.8 35.6
80/67 48.6 41.1 34.8 27.6
75/62 39.4 33 26 18.3
70/57 30.5 26.6 23.1 19.6
AHE42D 1000 85/72 65.7 61 52.7 42.9
80/67 58 49.6 41.1 32.1
75/62 46.7 38.9 30.4 21.8
70/57 36.4 31.6 27.6 23.3
AHE42D 1180 85/72 67.9 71.4 60.2 48.8
80/67 65.6 56.9 47.1 37.1
75/62 53.8 45.2 34.7 24.6
70/57 42.2 37.1 31.9 27.0
AHE42D 1385 85/72 69.4 81 68 57.2
80/67 77.1 65.4 54.1 41.6
75/62 62.1 51 39.8 28.1
70/57 48.1 42.5 36.8 30.6
AHE48D 1000 85/72 69 59.8 51.3 41.5
80/67 56.5 48.2 39.7 29.9
75/62 45.1 36.8 28.3 18.9
70/57 34.4 31 26.8 22.5
AHE48D 1195 85/72 79.5 69.7 59.9 48.6
80/67 65.2 55.5 45.5 34.9
75/62 52.2 42.5 32.6 21.8
70/57 40.1 36.1 31.1 26.2
AHE48D 1385 85/72 90 78.1 66 54.5
80/67 73.5 62.7 51.3 38.7
75/62 59.2 48.2 36.9 24.0
70/57 45.2 41 35.4 29.7
AHE48D 1600 85/72 102.2 90 74.3 60.4
80/67 83.6 70.6 57.2 43.1
75/62 66.1 54 41.2 27.0
70/57 50.7 46.1 39.8 33.4
AHE60D 1190 85/72 83.6 73.7 62.9 51.6
80/67 68.2 58.4 48.4 37.1
75/62 54.9 45.3 34.8 23.9
70/57 42.2 37.3 31.9 26.9
AHE60D 1390 85/72 95.9 84.1 71.9 58.8
80/67 79.2 67.4 54.4 41.6
75/62 62.4 51.2 39.7 26.9
70/57 48 42.5 36.8 30.6
AHE60D 1565 85/72 106.3 94.2 78.5 63.5
80/67 87.6 73.9 60.2 45.9
75/62 69.3 56.8 43.5 29.7
70/57 53.1 46.9 40.5 34.1
AHE60D 1835 85/72 122.1 107.1 90.9 72.6
80/67 100.2 85.9 69.8 51.8
75/62 79.7 65.3 49.8 32.9
70/57 60.8 54.1 46.4 38.7

1. Actual capacity varies with the outdoor AC or HP that is used with the system. 2. Airflow is calculated for each system tonnage.

Physical & Electrical Data

Application Factors - Rated CFM vs. Actual CFM

% Of Rated Airflow (CFM) 80% 90% 100% 110% 120%
Capacity Factor 0.96 0.98 1.00 1.02 1.03

Physical & Electrical Data - Cooling Only

Models Blower - Diameter x Width Motor HP Nominal RPM Voltage Full Load Amps @230V Filter¹ Type Size Permanent Type Kit Shipping / Operating Weight (lbs.)
AHE18B 10 x 8 1/3 HP 1050 208/230 2.8 DISPOSABLE OR PERMANENT 16 x 20 x 1 1PF0601BK 115/103
AHE22B 10 x 8 1/3 HP 1050 208/230 2.8 120/105
AHE24B 10 x 8 1/3 HP 1050 208/230 2.8 120/105
AHE30B 10 x 8 1/3 HP 1050 208/230 2.8 120/105
AHE34C 11 x 10 1/2 HP 1050 208/230 4.1 DISPOSABLE OR PERMANENT 20 x 20 x 1 1PF0602BK 152/137
AHE36C 11 x 10 1/2 HP 1050 208/230 4.1 152/137
AHE42D 11 x 10 1/2 HP 1050 208/230 4.1 168/150
AHE48D 11 x 10 3/4 HP 1050 208/230 6.0 DISPOSABLE OR PERMANENT 22 x 20 x 1 1PF0603BK 171/153
AHE60D 11 x 10 3/4 HP 1050 208/230 6.0 174/156

1. Field supplied.

KW & MBH Conversions - For Total Power Input Requirement

For a power distribution voltage that is different than the provided nominal voltage, multiply the kW and MBH data from the table by the conversion factor in the following table.

DISTRIBUTION POWER NOMINAL VOLTAGE CONVERSION FACTOR
220V 240V 0.84

Electrical Data - Cooling Only

Models Motor FLA¹ Minimum Circuit Ampacity MOP² Minimum Wire Size (AWG)³
AHE18B/AHE22B / AHE24B/AHE30B 2.8 3.5 15 14
AHE34C/AHE36C / AHE42D 4.1 5.1 15 14
AHE48D/AHE60D 6.0 7.5 15 14

1. FLA = Full Load Amps. 2. MOP = Maximum Overcurrent Protection device; must be HACR type circuit breaker or time delay fuse. 3. 75°C, copper wire only. If wire other than non-plated, 75°C ambient, copper wire is used, consult applicable tables of the NEC and local codes.

Electrical Heat: Minimum Fan Speed

Heater Kit Models²,³ Nom. kW @240V Air Handler Models
AHE18B AHE22B AHE24B AHE30B AHE34C AHE36C AHE42D AHE48D AHE60D
6HK(0,1)6500206 2.4kW Med Low #2 Med Low #2 Low #1 Med #3 Low #1 Med Low #2
6HK(0,1)6500506 4.8kW Med Low #2 Med Low #2 Med Low #2 Med Low #2 Med #3 Med #3
6HK(0,1)6500806 7.7kW Med High #4 Med High #4 Med #3 Med #3 Med #3 Med #3
6HK(0,1)6501006 9.6kW Med High #4 Med High #4 Med High #4 Med High #4 Med High #4 Med High #4
6HK(1,2)6501306 12.5kW Med High #4 Med High #4 Med High #4 Med High #4 Med High #4 Med #3
6HK(1,2)6501506 14.4kW High #5 High #5 Med High #4 Med High #4 Med High #4 Med #3
6HK(1,2)6501806 17.3kW High #5 High #5 High #5 Med High #4 - -
6HK(1,2)6502006 19.2kW High #5 High #5 High #5 High #5 - -
6HK(1,2)6502506 24kW - - - High #5 - -

1. The referenced letter in this table is for the heat jumper tap. 2. (0,1) - 0 = no circuit breaker OR 1 = with circuit breaker. 3. (1,2) - 1 = with circuit breaker, no breaker jumper bar OR 2 = with circuit breaker & breaker jumper bar.

Electric Heat Performance Data

Electric Heat Performance Data: 208/230-1-60 & 208/230-3-60

Heater Models¹,² Nominal kW @240V Total Heat³ kW Staging
kW (208V) kW (230V) MBH (208V) MBH (230V) W1 Only (208V) W1 Only (230V) W1 + W2 (208V) W1 + W2 (230V)
6HK(0,1)6500206 2.4 1.8 2.2 6.2 7.5 1.8 2.2 1.8 2.2
6HK(0,1)6500506 4.8 3.6 4.4 12.3 15.0 3.6 4.4 3.6 4.4
6HK(0,1)6500806 7.7 5.8 7.1 19.7 24.1 5.8 7.1 5.8 7.1
6HK(0,1)6501006 9.6 7.2 8.8 24.6 30.1 7.2 8.8 7.2 8.8
6HK(1,2)6501306 12.5 9.4 11.5 32.0 39.2 3.1 3.8 9.4 11.5
6HK(1,2)6501506 14.4 10.8 13.2 36.9 45.1 3.6 4.4 10.8 13.2
6HK(1,2)6501806 17.3 13.0 15.9 44.3 54.2 6.5 7.9 13.0 15.9
6HK(1,2)6502006 19.2 14.4 17.6 49.2 60.2 7.2 8.8 14.4 17.6
6HK(1,2)6502506 24.0 18.0 22.0 61.5 75.2 7.2 8.8 18.0 22.0
6HK06501025 9.6 7.2 8.8 24.6 30.1 7.2 8.8 7.2 8.8
6HK06501525 14.4 10.8 13.2 36.9 45.1 10.8 13.2 10.8 13.2
6HK06501825 17.3 13.0 15.9 44.3 54.2 13.0 15.9 13.0 15.9
6HK16502025 19.2 14.4 17.6 49.2 60.2 7.2 8.8 14.4 17.6
6HK16502525 24.0 18.0 22.0 61.5 75.2 9.0 11.0 18.0 22.0

1. (0,1) - 0 = no circuit breaker OR 1 = with circuit breaker. 2. (1,2) - 1 = with circuit breaker, no breaker jumper bar OR 2 = with circuit breaker & breaker jumper bar. 3. For different power distributions, see conversion table on Page 5.

Electrical Data for Single Source Power Supply: 208/230-1-60

Air Handler Models Heater Models¹,² Heater Amps @240V Min. Circuit Ampacity MOP³ Min Wire Size (AWG)⁴
208V 230V 208V 230V 208V 230V 208V 230V
AHE18B 6HK(0,1)6500206 10.0 14.3 16.0 15 20 12 12
6HK(0,1)6500506 20.0 25.2 28.5 30 30 10 10
6HK(0,1)6500806 32.0 38.2 43.5 40 45 8 8
6HK(0,1)6501006 40.0 46.8 53.5 50 60 8 6
AHE22B/AHE24B/AHE30B 6HK(0,1)6500206 10.0 14.3 16.0 15 20 12 12
6HK(0,1)6500506 20.0 25.2 28.5 30 30 10 10
6HK(0,1)6500806 32.0 38.2 43.5 40 45 8 8
6HK(0,1)6501006 40.0 46.8 53.5 50 60 8 6
6HK(1,2)6501306 52.0 59.8 68.5 60 70 6 4
6HK(1,2)6501506 60.0 68.5 78.5 70 80 4 4
AHE34C/AHE36C/AHE42D 6HK(0,1)6500206 10.0 16.0 17.6 20 20 12 12
6HK(0,1)6500506 20.0 26.8 30.1 30 35 10 10
6HK(0,1)6500806 32.0 39.8 45.1 40 50 8 8
6HK(0,1)6501006 40.0 48.5 55.1 50 60 8 6
6HK(1,2)6501306 52.0 61.5 70.1 70 80 6 4
6HK(1,2)6501506 60.0 70.1 80.1 80 90 4 4
6HK(1,2)6501806 72.0 83.1 95.1 90 100 4 3
6HK(1,2)6502006 80.0 91.8 105.1 100 110 3 2
AHE48D/AHE60D 6HK(0,1)6500206 10.0 18.3 20.0 20 20 12 12
6HK(0,1)6500506 20.0 29.2 32.5 30 35 10 8
6HK(0,1)6500806 32.0 42.2 47.5 45 50 8 8
6HK(0,1)6501006 40.0 50.8 57.5 60 60 6 6
6HK(1,2)6501306 52.0 63.8 72.5 70 80 6 4
6HK(1,2)6501506 60.0 72.5 82.5 80 90 4 4
6HK(1,2)6501806 72.0 85.5 97.5 90 100 3 3
6HK(1,2)6502006 80.0 94.2 107.5 100 110 3 2

1. FLA = Full Load Amps. 2. MOP = Maximum Overcurrent Protection device; must be HACR type circuit breaker or time delay fuse. 3. 75°C, copper wire only. If wire other than non-plated, 75°C ambient, copper wire is used, consult applicable tables of the NEC and local codes.

Electrical Data for Single Source Power Supply: 208/230-1-60 (Continued)

Air Handler Models Heater Models¹,² Heater Amps @240V Min. Circuit Ampacity MOP³ Min Wire Size (AWG)⁴
208V 230V 208V 230V 208V 230V 208V 230V
AHE60D 6HK(0,1)6500206 10.0 18.3 20.0 20 20 12 12
6HK(0,1)6500506 20.0 29.2 32.5 30 35 10 8
6HK(0,1)6500806 32.0 42.2 47.5 45 50 8 8
6HK(0,1)6501006 40.0 50.8 57.5 60 60 6 6
6HK(1,2)6501306 52.0 63.8 72.5 70 80 6 4
6HK(1,2)6501506 60.0 72.5 82.5 80 90 4 4
6HK(1,2)6501806 72.0 85.5 97.5 90 100 3 3
6HK(1,2)6502006 80.0 94.2 107.5 100 110 3 2
6HK(1,2)6502506 100.0 115.8 132.5 125 150 1 1/0

1. (0,1) - maybe 0 (no circuit breaker) or 1 (with circuit breaker). 2. (1,2) maybe 1 (with circuit breaker, no breaker jumper bar) or 2 (with circuit breaker & breaker jumper bar). 3. MOP = Maximum Overcurrent Protection device; must be HACR type circuit breaker or time delay fuse. 4. Stated sizes are for 75°C, copper wire only. If wire other than non-plated, 75°C ambient, copper wire is used, consult applicable tables of the NEC and local codes.

Electrical Data for Multi-Source Power Supply: 208/230-1-60

Air Handlers Models Heater Models Total Heater Amps @240V Min. Circuit Ampacity MOP¹ Min. Wire Size (AWG)²
Circuit 1st³ 2nd 3rd 1st³ 2nd 1st³ 2nd 1st³ 2nd 1st³ 2nd
AHE22B 6HK16501306 52.0 22.2 37.6 - 24.6 43.3 - 25 40 - 25 45 - 10 8 - 10 8
6HK16501506 60.0 25.1 43.3 - 27.9 50.0 - 30 45 - 30 50 - 10 8 - 10 8
AHE24B 6HK16501306 52.0 23.3 37.6 - 25.7 43.3 - 25 40 - 30 45 - 10 8 - 10 8
6HK16501506 60.0 26.2 43.3 - 29.0 50.0 - 30 45 - 30 50 - 10 8 - 10 8
AHE34C 6HK16501806 72.0 43.5 39.0 - 49.0 45.0 - 45 40 - 50 45 - 8 8 - 8 8
6HK16502006 80.0 47.8 43.3 - 54.0 50.0 - 50 45 - 60 50 - 8 8 - 6 8
AHE36C 6HK16501306 52.0 25.4 37.6 - 27.8 43.3 - 30 40 - 30 45 - 10 8 - 10 8
6HK16501506 60.0 28.3 43.3 - 31.1 50.0 - 30 45 - 35 50 - 10 8 - 8 8
AHE42D 6HK16501806 72.0 45.6 39.0 - 51.1 45.0 - 50 40 - 60 45 - 8 8 - 6 8
6HK16502006 80.0 49.9 43.3 - 56.1 50.0 - 50 45 - 60 50 - 8 8 - 6 8
AHE48D 6HK16501306 52.0 25.4 37.6 - 27.8 43.3 - 30 40 - 30 45 - 10 8 - 10 8
6HK16501506 60.0 28.3 43.3 - 31.1 50.0 - 30 45 - 35 50 - 10 8 - 8 8
6HK16501806 72.0 45.6 39.0 - 51.1 45.0 - 50 40 - 60 45 - 8 8 - 6 8
6HK16502006 80.0 49.9 43.3 - 56.1 50.0 - 50 45 - 60 50 - 8 8 - 6 8
AHE60D 6HK16501306 52.0 25.4 37.6 - 27.8 43.3 - 30 40 - 30 45 - 10 8 - 10 8
6HK16501506 60.0 28.3 43.3 - 31.1 50.0 - 30 45 - 35 50 - 10 8 - 8 8
6HK16501806 72.0 45.6 39.0 - 51.1 45.0 - 50 40 - 60 45 - 8 8 - 6 8
6HK16502006 80.0 49.9 43.3 - 56.1 50.0 - 50 45 - 60 50 - 8 8 - 6 8
6HK16502506 100.0 49.9 43.3 21.7 56.1 50.0 25.0 50 45 25 60 50 25 8 8 10 6 8 10

1. MOP = Maximum Overcurrent Protection device; must be HACR type circuit breaker or time delay fuse. 2. Stated sizes are for 75°C, copper wire only. If wire other than non-plated, 75°C ambient, copper wire is used, consult applicable tables of the NEC and local codes. 3. 1st Circuit includes the blower motor amps.

Electrical Data for Single Source Power Supply: 208/230-3-60

Air Handler Models Heater Models Heater Amps @240V Min. Circuit Ampacity MOP¹ Min. Wire Size (AWG)²
208V 230V 208V 230V 208V 230V 208V 230V
AHE22B/AHE24B/AHE30B 6HK06501025 23.1 28.5 32.4 30 35 10 8
6HK06501525 34.6 41.0 46.8 45 50 8 8
6HK06501025 23.1 30.2 34.0 30 35 10 8
6HK06501525 34.6 42.6 48.4 45 50 8 8
6HK06501825 41.6 50.2 57.1 60 60 6 6
6HK16502025³ 46.2 55.2 62.9 60 70 6 6
AHE48D/AHE60D 6HK06501025 23.1 32.5 36.4 35 40 8 8
6HK06501525 34.6 45.0 50.8 45 60 8 6
6HK06501825 41.6 52.6 59.5 60 60 6 6
6HK16502025³ 46.2 57.6 65.3 60 70 6 4
6HK06501025 23.1 32.5 36.4 35 40 8 8
6HK06501525 34.6 45.0 50.8 45 60 8 6
6HK06501825 41.6 52.6 59.5 60 60 6 6
6HK16502025³ 46.2 57.6 65.3 60 70 6 4
6HK16502525³ 57.7 70.0 79.6 70 80 4 4

1. MOP = Maximum Overcurrent Protection device; must be HACR type circuit breaker or time delay fuse. 2. Stated sizes are for 75°C, copper wire only. If wire other than non-plated, 75°C ambient, copper wire is used, consult applicable tables of the NEC and local codes.. 3. The 20kW and 25kW heater models (6HK16502025 and 6HK16502525) come with circuit breakers standard. Single source power MCA and MOP requirements are given here only for reference if used with field installed single point power modification.

Electrical Data for Multi-Source Power Supply: 208/230-3-60

Air Handler Models Heater Models Total Heater Amps @240V Min. Circuit Ampacity MOP¹ Min. Wire Size (AWG)²
Circuit 1st³ 2nd 1st³ 2nd 1st³ 2nd 1st³ 2nd 1st³ 2nd
AHE34C/AHE36C/AHE42D 6HK16502025 46.2 30.2 25.0 34.0 28.9 35 25 35 30 8 10 8 10
6HK16502525 57.7 38.8 31.3 43.6 36.1 40 35 45 40 8 8 8 8
AHE48D 6HK16502025 46.2 32.5 25.0 36.4 28.9 35 25 40 30 8 10 8 10
6HK16502525 57.7 38.8 31.3 43.6 36.1 40 35 45 40 8 8 8 8
AHE60D 6HK16502025 46.2 32.5 25.0 36.4 28.9 35 25 40 30 8 10 8 10
6HK16502525 57.7 38.8 31.3 43.6 36.1 40 35 45 40 8 8 8 8

1. MOP = Maximum Overcurrent Protection device; must be HACR type circuit breaker or time delay fuse. 2. Stated sizes are for 75°C, copper wire only. If wire other than non-plated, 75°C ambient, copper wire is used, consult applicable tables of the NEC and local codes. 3. 1st Circuit includes the fan motor.

Typical Applications

Diagrams illustrating typical installation configurations for the air handler: Upflow, Horizontal Right, and Horizontal Left. These show the airflow direction (HEAT indicated) and the general placement of the unit.

Accessories

Refer to the Price Manual for specific model numbers where not shown.

Limitations

These units must be wired and installed in accordance with all national and local safety codes.

Voltage Limits:

Air Handler Voltage Voltage Code Normal Operating Voltage Range¹
208/230-1-60 06 187-253

1. Rated in accordance with ARI Standard 110, utilization range "A".

Airflow must be within the minimum and maximum limits approved for electric heat, evaporator coils, and outdoor units.

Air Flow Data (CFM)¹

Models Blower Motor Speed External Static Pressure (in. wc.)
0.10 0.20 0.30 0.40 0.50 0.60 0.70
AHE18B High #5 1075 1041 1003 970 930 885 842
Med High #4 895 845 808 767 709 647 561
Med #3 663 618 557 490 348 267 192
Med Low #2 629 468 356 197 175 68 23
Low #1 629 468 356 197 175 68 23
AHE22B High #5 1156 1120 1093 1056 1014 951 862
Med High #4 1021 987 952 918 873 836 787
Med #3 829 789 754 698 654 585 532
Med Low #2 681 621 575 496 435 336 262
Low #1 598 503 437 340 259 203 74
AHE24B High #5 1471 1429 1387 1337 1289 1233 1172
Med High #4 1301 1248 1198 1147 1008 999 927
Med #3 1097 1044 972 906 815 748 680
Med Low #2 943 868 768 689 617 566 520
Low #1 869 668 515 424 365 287 NA
AHE30B High #5 1465 1415 1360 1307 1246 1183 1118
Med High #4 1260 1204 1142 1075 1008 946 876
Med #3 1088 1022 939 862 782 721 626
Med Low #2 998 810 717 630 562 493 444
Low #1 903 707 411 323 265 152 NA
AHE34C High #5 1632 1589 1542 1494 1446 1391 1335
Med High #4 1430 1390 1346 1294 1238 1168 960
Med #3 1238 1198 1145 1082 993 908 805
Med Low #2 1118 1020 947 851 734 666 563
Low #1 998 772 477 418 349 NA NA
AHE36C High #5 1861 1823 1787 1750 1708 1666 1620
Med High #4 1674 1640 1599 1562 1516 1472 1432
Med #3 1442 1405 1358 1311 1262 1197 1108
Med Low #2 1257 1220 1163 1103 1031 942 864
Low #1 1153 1031 967 867 764 718 633
AHE42D High #5 2091 2053 2016 1975 1937 1906 1869
Med High #4 1903 1868 1832 1791 1748 1703 1660
Med #3 1634 1598 1562 1516 1468 1422 1350
Med Low #2 1447 1404 1361 1318 1257 1164 1092
Low #1 1268 1203 1148 1073 978 907 839

1. Air handler units have been tested to UL 1995 / CSA 22.2 standards up to 0.30" wc. external static pressure. Dry coil conditions only, tested without filters. For optimal performance, external static pressures of 0.2" to 0.5" are recommended. Applications above 0.6" are not recommended. Airflow data shown is from testing performed at 230V. AHE units use a X13 motor, and there is minimal variation of airflow at other distribution voltage values. The above data can be used for airflow at other distribution voltages.

Typical Thermostat Connection

Wiring diagrams illustrating typical thermostat connections for various YORK air handler configurations: Cooling Only, Cooling with Electric Heat (10 kW and below, 13 kW and above), and Single Stage Heat Pump and Electric Heat (10 kW and below, 13 kW and above). A specific diagram for the 6HK16501506 Heat Kit is also shown, detailing connections to the transformer, sequencers, and blower motor.

Note: To change the quantity of heat during Heat Pump defrost cycle, reverse the brown and white wire connections on the sequencers in the heater kit.

Typical Thermostat Wiring

Wiring diagram for a 2-Stage Heat Pump with ECM Blower Motor, detailing thermostat connections (R, W, Y1, Y2, G, C, O, B) and their corresponding terminals on the air handler and heat kit. It also shows connections to the X13 blower motor control and transformer.

PDF preview unavailable. Download the PDF instead.

AHE 4position Acrobat Distiller 9.0.0 (Windows)

Related Documents

Preview York Single Piece Standard ECM Air Handlers Technical Guide
Technical guide for York Single Piece Standard ECM Air Handlers, covering specifications, dimensions, electrical data, and performance for cooling and heat pump applications.
Preview York AHE Series Air Handler Technical Specification and Parts List
Detailed technical specifications and parts list for York AHE Series Single Piece Air Handlers with Standard ECM Motor and Flex Coil Models (Style A, B). Includes part numbers and model compatibility.
Preview YORK YMAE Air-to-Water Inverter Scroll Heat Pumps: Efficiency & Performance
Explore the YORK YMAE series of Air-to-Water Inverter Scroll Heat Pumps, offering optimized electric heating and cooling for superior efficiency and best-in-class performance. Learn about advanced features, sustainability, and technical specifications.
Preview York N1VS Series Variable Speed Air Handler Technical Guide
Comprehensive technical guide for York N1VS Series variable speed air handlers, detailing specifications, dimensions, features, and electrical data for cooling and heat pump systems.
Preview York Air Handler User Manual: Operation, Maintenance, and Warranty
Comprehensive user manual for York residential split air handlers, covering operation, system functions, maintenance, troubleshooting, and limited warranty information. Includes guidance on thermostat settings, filter care, and efficiency tips.
Preview YORK Altair High Wall Fixed Cooling Units: YHFE 12-24 ZJMAXAORX Series
Explore the YORK Altair High Wall Fixed Cooling units (YHFE 12-24 ZJMAXAORX series), offering efficient, quiet, and user-friendly air conditioning solutions for homes and offices. Features include 24-hour timer, child lock, multi-speed fan, and intelligent sleep mode. View specifications and benefits.
Preview YORK LX Series YC3 13.4 SEER2 Split-System Air Conditioner Technical Guide
This technical guide provides detailed specifications, installation procedures, performance data, and accessory information for YORK LX Series YC3 13.4 SEER2 single-phase split-system air conditioners.
Preview YORK Split Pared ON/OFF Air Conditioners - YHFE Series Specifications
Detailed specifications for YORK Split Pared ON/OFF air conditioners, R-410A, cooling only, models YHFE 12, 18, and 24 ZJMAXAORX, covering capacity, power, dimensions, and performance.