Product Overview

The Aldes ISONE® 2.1 fire damper is designed for fire protection in ventilation systems, maintaining the fire resistance rating of partitions. It offers a single, versatile model suitable for various partition types and fire ratings, simplifying selection and installation.

Key features include an ergonomic quick reset handle, optional stainless steel shaft for harsh environments, and compatibility with the ALDES SecurONE application for data management. The mechanism is designed for ease of use, installation, and maintenance.

Product Description

ISONE® 2.1 fire dampers are intended for tertiary buildings (public access buildings, high-rise buildings). They restore the fire resistance rating of partitions traversed by a ventilation duct. They are equipped with a default 70°C thermal fusible link and can be controlled by 24/48VDC fail-safe electromagnetic coils or 24VDC/48VDC fail-secure coils. The reset motor operates on 24-48 VDC. These dampers provide fire resistance up to 120 minutes on all standard partitions.

Available Models:

  • ISONE® 2.1 Rectangular PM: Dimensions range from 200x100 mm to 800x600 mm.
  • ISONE® 2.1 Rectangular GM: Dimensions range from 800x600 mm up to 1500x500 mm or 1000x1000 mm.

Application Areas

Suitable for new construction, renovation projects, and tertiary premises.

Installation

Installation is designed to be straightforward, including options for:

  • Installation without embedding in lightweight partitions, even with post-mounted frames.
  • Recessed mounting on concrete/slab walls, cellular concrete, plasterboard walls, and plasterboard type A (1h) or type F (2h).
  • Remote mounting on PROMAT / GEOSTAF using the EASYNSTAL kit.
  • Positioning on lightweight partitions using integrated installation brackets.
  • The Easynstall kit facilitates the installation of rectangular dampers in lightweight partitions (Type A, 60 minutes).
  • An adaptation piece is available for connection to rectangular ducts.
  • Extended recess dimensions are available according to EXAP EN 15882-2:2015, rules X.45 and X.46.
  • Installation must comply with fire classification reports.

Installation Clearances:

Detailed installation diagrams illustrate required opening sizes and clearances for various partition types:

  • Concrete Wall: Requires opening size of X+80 mm by Y+80 mm.
  • Concrete Slab: Requires opening size of X+145 mm by Y+145 mm.
  • Plasterboard Partition (120 min): Requires opening size of X+70 mm by Y+70 mm.
  • Lightweight Partition (120 min): Requires opening size of X+70 mm by Y+70 mm with a minimum clearance of 98 mm.
  • Lightweight Partition (60 min with Easynstall): Requires opening size of X+70 mm by Y+70 mm with a minimum clearance of 98 mm.

Dimensional Data

References E (mm) F (mm) G (mm) H (mm) L (mm) ZA (mm)
11040116 25 169 71 300 400 112.50

ISONE®2.1 Rectangular Footprint:

  • GM models: ≥800x600 mm up to 1500x500 / 1000² mm.
  • PM models: 200x100 mm to 800x600 mm.

Principle of Operation

The damper operates as follows:

  • The damper is normally open in standby.
  • It opens upon command from the Fire Safety Control System (CMSI) or a thermal probe, moving to the safety position (closed).
  • It is remotely resettable via motorization.

Internal components are identified as:

  • 1: Installation bracket
  • 2: Fire damper blade
  • 3: ISONE®2.1 PM mechanism
  • 4: Blade thickness (25mm for PM model, 50mm for GM model)
  • 5: 30mm connection flange

Regulations & Conformity

  • CE Certificate Number: 1812-CPR-1837
  • Certified and compliant with NF S 61937-5 and NF537.
  • CE marked according to EN 15650: 1812-CPR-1837.
  • Class C airtightness according to EN 1751 as standard.
  • Fire rating: EI 120 S -500 Pa on concrete walls and slabs, cellular concrete, type F plasterboard, and PROMAT/Geostaff remote mounting.
  • Compliant with EXAP EN 15882-2:2015: rules X.45 and X.46.

Additional Features

  • 100% upgradeable mechanism.
  • Single damper adaptable to all wall types.
  • Installation on lightweight partitions with post-mounted frames.
  • Reset handle indicates damper position.
  • Large electrical connection box.
  • Stainless steel shaft option for hostile environments.
  • Easynstall kit for easy installation in lightweight partitions.
  • Optional remote control box.
  • Low pressure drop.

PDF preview unavailable. Download the PDF instead.

FR-EXPORT-Aldes-ISONE2-1-400X300-FTE70-FDCU1-2-11040116 Adobe PDF Library 17.0 Adobe InDesign 19.5 (Windows)

Related Documents

Preview Aldes ISONE® 2.1 Rectangular Fire Damper | Model 11040037
Discover the Aldes ISONE® 2.1 rectangular fire damper (11040037). This manual damper offers up to 120 minutes of fire resistance, easy installation for various partition types, and compliance with EN 15650. Ideal for tertiary buildings.
Preview Aldes ISONE® 2.1 Fire Damper | Technical Specification
Detailed technical specifications and installation guide for the Aldes ISONE® 2.1 fire damper, model 11040007. Features include fire resistance up to EI 120, easy installation, and CE compliance for ventilation systems.
Preview ISONE® 2.1 Fire Damper - Aldes | Model 11040045 Technical Specification
Detailed technical specifications and installation guide for the Aldes ISONE® 2.1 rectangular fire damper (Model 11040045), featuring FTE70 manual release, fire resistance up to 120 minutes, and various installation options for tertiary buildings.
Preview Aldes ISONE® 2.1 Fire Damper: Technical Specifications and Installation Guide
Detailed information on the Aldes ISONE® 2.1 fire damper, including product benefits, technical specifications, installation procedures, and regulatory compliance for fire safety in tertiary buildings.
Preview Aldes ISONE® 2.1 Rectangular Fire Damper - Model 11040052
Comprehensive guide to the Aldes ISONE® 2.1 rectangular fire damper (model 11040052), detailing its features, technical specifications, installation procedures, and regulatory compliance for fire safety in buildings.
Preview Aldes ISONE® 2.1 Fire Damper: Technical Specifications and Installation
Comprehensive technical details, features, and installation guidelines for the Aldes ISONE® 2.1 fire damper, model 11040062. Learn about its applications, compliance, and operational principles.
Preview Aldes ISONE® 2.1 Fire Damper: Technical Specifications and Installation Guide
Comprehensive details on the Aldes ISONE® 2.1 rectangular fire damper, including features, certifications, installation instructions, and dimensional data for building safety applications.
Preview Aldes ISONE® 2.1 Fire Damper: Technical Data and Installation Guide
Comprehensive technical specifications, features, installation instructions, and regulatory compliance for the Aldes ISONE® 2.1 fire damper, model 11040109.