Overview and Performance
This document provides submittal data for the Pioneer Quad (4) Circuit Ducted Inverter Heat Pump Set, model YN040GLSI24M4G.
Cooling Mode Performance
Specification | Value |
---|---|
Rated Cooling | 34,000 BTU/hr |
Ambient Range | 5°F ~ 131°F |
SEER Rating | 20.0 BTU/W·h |
EER Rating | 11.7 BTU/W·h |
Performance is based on 100% Capacity @ Indoor DB 80°F/WB 67°F.
Heating Mode Performance
Specification | Value |
---|---|
Rated Heating | 36,000 BTU/hr |
Ambient Range | -13°F ~ 86°F |
HSPF2 IV (V) | 8.5 (7.3) BTU/W·h |
COP (47°F) | 3.2 (W/W) |
High Heat (47°F) = 36,000 BTU / Low Heat (17°F) = 22,400 BTU / COP (5°F) = 1.9.
Electrical Information
Specification | Value | |
---|---|---|
Cooling | Heating | |
Rated Input (W) | 2,950 | 2,650 |
Rated Current (A) | 13.2 | 11.9 |
Breaker Needed | 35A (Double-Pole) | |
Power Supply | 208~230V, 1Ph, 60Hz |
Piping and Refrigerant
Specification | Value |
---|---|
Liquid Line (OD) | 1/4" (4) |
Suction Line (OD) | 3/8" (4) |
Refrigerant Precharge | R454b (Selectable Lineset) |
Vertical Run/Elevation Diff. | 50 ft. / 33 ft. |
This combination is Energy-Star certified. ?
Exterior Unit (Condenser) Specifications
Specification | Value |
---|---|
Sound Level (dBA) | 65 |
Recommended Room Size | 700~1,350 Sq. ft. |
Minimum Room Size | 111 Sq. ft. |
Compressor | Twin-Rotary |
Dimensions (WDH) | 42"1-/4 x 18"-3/8 x 33"-1/2 |
Weight (lbs) | 145.5 |
Compatible Indoor Air Handler Units
Model | Quantity | Capacity Range |
---|---|---|
RT009GLSILCFHG (9K) | 4 (Up to 48,000 BTU) | (9K) |
RT012GLSILCFHG (12K) | (12K) | |
RT018GLSILCFHG (18K) | (18K) | |
RT024GLSILCFHG (24K) | (24K) |
Piping and Circuit Lengths
Specification | Value |
---|---|
Max Circuit Length | 80 ft. (9K) / 100 ft. (12K/18K/24K) |
Max Vertical Run | 33 ft. (9K/12K/18K/24K) |
Adjustment Charge | 0.11 oz x (L1+L2+L3+L4-100 ft.) |
Dimensional Data - Condenser Unit
Pioneer YN040GLSI24M4G (36,000 BTU / 4-Zone)
Diagram shows a rectangular outdoor unit with fan grille and access panels. Key dimensions are labeled A through E.
Label | A | B | C | D | E |
---|---|---|---|---|---|
Inches | 26" | 18-1/4" | 18-3/8" | 42-1/4" | 33-5/8" |
Millimeters | 660 mm | 462 mm | 468 mm | 1074 mm | 853 mm |
Dimensional Data - Indoor Air Handler Units
RT009GLSILCFHG
Diagrams show the indoor unit from Supply Side, Inlet Side, Side View, Above View, and Below View. Key dimensions are labeled A through M.
Label | A | B | C | D | E | F | G | H | I | J | K | L | M |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Inches | 27-5/8" | 7-7/8" | 19-3/8" | 17-3/4" | 1-3/4" | 20-1/8" | 1/8" | 5-1/2" | 23-5/8" | 7-3/8" | 1-3/8" | 29-1/8" | 11-3/4" |
Millimeters | 701.7 mm | 200 mm | 492.1 mm | 450.9 mm | 44.5 mm | 511.2 mm | 3.2 mm | 139.7 mm | 600.1 mm | 187.3 mm | 34.9 mm | 739.8 mm | 298.5 mm |
Installation Clearances
Air Inlet: ≥ 40 in (100 cm) clearance required.
Side View: ≥ 4 in (10 cm) clearance required on sides.
Front View: ≥ 10 in (25 cm) clearance required in front; ≥ 20 in (50 cm) clearance required below.
RT012GLSILCFHG
Diagrams show the indoor unit from Supply Side, Inlet Side, Side View, Above View, and Below View. Key dimensions are labeled A through M.
Label | A | B | C | D | E | F | G | H | I | J | K | L | M |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Inches | 27-5/8" | 7-7/8" | 19-3/8" | 17-3/4" | 1-3/4" | 20-1/8" | 1/8" | 5-1/2" | 23-5/8" | 7-3/8" | 1-3/8" | 29-1/8" | 11-3/4" |
Millimeters | 701.7 mm | 200 mm | 492.1 mm | 450.9 mm | 44.5 mm | 511.2 mm | 3.2 mm | 139.7 mm | 600.1 mm | 187.3 mm | 34.9 mm | 739.8 mm | 298.5 mm |
RT018GLSILCFHG
Diagrams show the indoor unit from Supply Side, Inlet Side, Side View, Above View, and Below View. Key dimensions are labeled A through M.
Label | A | B | C | D | E | F | G | H | I | J | K | L | M |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Inches | 36-1/4" | 7-7/8" | 19-3/8" | 17-3/4" | 1-3/4" | 28-3/4" | 1/8" | 5-1/2" | 32-1/4" | 7-3/8" | 1-3/8" | 37-3/4" | 11-3/4" |
Millimeters | 920.8 mm | 200 mm | 492.1 mm | 450.9 mm | 44.5 mm | 730.3 mm | 3.2 mm | 139.7 mm | 819.2 mm | 187.3 mm | 34.9 mm | 958.9 mm | 298.5 mm |
RT024GLSILCFHG
Diagrams show the indoor unit from Supply Side, Inlet Side, Side View, Above View, and Below View. Key dimensions are labeled A through M.
Label | A | B | C | D | E | F | G | H | I | J | K | L | M |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Inches | 43-3/4" | 7-7/8" | 19-3/8" | 17-3/4" | 1-1/8" | 36-5/8" | 1/8" | 5-1/2" | 40-5/8" | 7-1/4" | 1-3/8" | 37-7/8" | 14-3/8" |
Millimeters | 1110.1 mm | 200 mm | 492.1 mm | 450.9 mm | 28.6 mm | 930.3 mm | 3.2 mm | 139.7 mm | 1030.3 mm | 182.6 mm | 34.9 mm | 960.4 mm | 365.1 mm |
Combination Data and Specifications
Air Handler Specifications
Model | Airflow Rate (cfm) | Sound Level (dBA) | Auto Air Circulation | Dimensions (WDH) | Weight (lbs) |
---|---|---|---|---|---|
RT009GLSILCFHG | 335(Turbo)/305(Hi)/276(Med)/182(Lo)/182(Mute) | 42 (Turbo)/39 (Hi)/34 (Med)/28 (Lo)/28 (Mute) | 2-Way Louver (Up-Down + Left-Right) | 27"-1/2 x 19"-1/4 x 7"-1/8 | 33.1 |
RT012GLSILCFHG | 360(Turbo)/330(Hi)/270(Med)/210(Lo)/180(Mute) | 44 (Turbo)/41 (Hi)/35 (Med)/33 (Lo)/32 (Mute) | 2-Way Louver (Up-Down + Left-Right) | 27"-1/2 x 19"-1/4 x 7"-1/8 | 33.1 |
RT018GLSILCFHG | 500(Turbo)/426(Hi)/370(Med)/300(Lo)/283(Mute) | 48 (Turbo)/44 (Hi)/41 (Med)/36 (Lo)/33 (Mute) | 2-Way Louver (Up-Down + Left-Right) | 35"-1/2 x 19"-1/4 x 7"-7/8 | 39.7 |
RT024GLSILCFHG | 741(Turbo)/623(Hi)/558(Med)/529(Lo)/470(Mute) | 51 (Turbo)/49 (Hi)/46 (Med)/39 (Lo)/34 (Mute) | 2-Way Louver (Up-Down + Left-Right) | 43"-1/4 x 17"-3/4 x 7"-1/8 | 50.7 |
Matching Table (# Circuits Utilized)
Number of Circuits | Capacity Combinations |
---|---|
2-Circuits | (9000-24000) + (9000-24000) |
3-Circuits | (9000-24000) + (9000-18000) + (9000-12000) |
4-Circuits | (9000-18000) + (9000-12000) + (9000-12000) + (9000-12000) |
Piping Diameters
BTU Capacity | Line Size |
---|---|
9000 BTU | 1/4" (Liquid) - 3/8" (Suction) |
12000 BTU | 1/4" (Liquid) - 3/8" (Suction) |
18000 BTU | 1/4" (Liquid) - 1/2" Adapter Required (Suction) |
24000 BTU | 1/4" (Liquid) - 5/8" Adapter Required (Suction) |
All necessary adapters are provided with the condenser.
Note on System Operation: If the total demand from the combined group of indoor units exceeds the rated capacity of the outdoor unit, the capacity of each indoor unit will be adjusted accordingly. Each indoor unit operates at a self-regulated capacity (30% to 100% of rated capacity) based on actual zone demand, or may turn off.
Warranty Information and Features
Warranty Information and Length
Complete warranty details are available with the vendor or online at https://www.pdhvac.com/support/warranty/. This high-quality system is eligible for up to 10 years limited warranty on the compressor, and 7 years on other internal parts. To qualify for this warranty, the system must be installed within 90 days by a registered technician. Installations registered otherwise default to 5 years parts/compressor. Unregistered products qualify for only 1 year parts/compressor warranty.
Outstanding Features
- LED Display
- Energy Saving
- Ultra-Thin Design
- Dual Drain Options
- Customizable Timer
- Eco-Friendly Refrigerant
- Whisper-Quiet Operation
- Power Loss Memory Recovery
Available Accessories
Part Number | Description |
---|---|
IKT-LCVR4P-KIT | Decorative PVC Line Cover Kit |
IKT-LNBR-1/4-3/8 | BendAid Flexible Easy Bender Kit |
BRK-FRM-C-2P | Folding Mounting Bracket w/ Leveler |
IKT-UVL32UL-AG | UVC Bacterial Disinfection Kit |
IKT-SURPRK-DV2 | Ultimate Surge and Power Protection |
Document provided by Parker Davis HVAC International, Inc.