Pioneer YN040GLSI24M4G Quad-Zone Ductless Inverter Heat Pump Submittal Sheet

System Full Set Model: YN040GLSI24M4G

AHRI Reference Number: 217048768

Product: Quad (4) Circuit Ductless Inverter Heat Pump Set

Performance Data

Cooling Mode Performance

SpecificationValue
Rated Cooling35,000 BTU/hr
Ambient Range5°F ~ 131°F
SEER Rating22.5 BTU/W·h
EER Rating12.0 BTU/W·h

Note: 100% Capacity @ Indoor DB 80°F/WB 67°F

Heating Mode Performance

SpecificationValue
Rated Heating36,000 BTU/hr
Ambient Range-13°F ~ 86°F
HSPF2 IV (V)9.5 (8.2) BTU/W·h
COP (47°F)3.5 (W/W)

Notes: High Heat (47°F) = 36,000 BTU / Low Heat (17°F) = 22,400 BTU / COP (5°F) = 2.0

Electrical Information

SpecificationCoolingHeating
Rated Input (W)2,9302,680
Rated Current (A)13.112.0
Breaker Needed35A (Double-Pole)
Power Supply208~230V, 1Ph, 60Hz

Piping and Refrigerant

SpecificationValue
Liquid Line (OD)1/4" (4)
Suction Line (OD)3/8" (4)
Refrigerant PrechargeR454b (Selectable Lineset)
Vertical Run/Elevation Diff.50 ft. / 33 ft.

This combination is Energy Star Certified.

Exterior Unit (Condenser) Specifications

SpecificationValue
Sound Level (dBA)65
Recommended Room Size700~1,350 Sq. ft.
Minimum Room Size111 Sq. ft.
CompressorTwin-Rotary
Dimensions (WDH)42"-1/4 x 18"-3/8 x 33"-1/2
Weight (lbs)145.5

Compatible Indoor Air Handler Units

ModelQuantityMax Circuit LengthMax Vertical RunAdjustment Charge
UT018GLSILCFHG (18K)4 (Up to 48,000 BTU)80 ft. (18K) / 100 ft. (24K)33 ft. (18K/24K)0.11 oz x (L1+L2+L3+L4-100 ft.)
UT024GLSILSFHG (24K)

Dimensional Data

Condenser Unit (YN040GLSI24M4G)

The condenser unit's dimensions are provided in a table and diagram:

DimensionInchesMillimeters
A26"660 mm
B18-1/4"462 mm
C18-3/8"468 mm
D42-1/4"1074 mm
E33-5/8"853 mm

Diagram Description: The diagrams show the front, side, and top views of the outdoor condensing unit, indicating dimensions labeled A through E. Dimension A represents the width, B the depth, C the height, D the front profile, and E the side profile.

Indoor Unit (UT018GLSILCFHG & UT024GLSILSFHG)

The indoor units (UT018GLSILCFHG and UT024GLSILSFHG) have similar dimensional layouts and installation requirements.

Front View: 41-1/2 inches (1,053 mm) width, 26-5/8 inches (675 mm) height, 9-1/2 inches (240 mm) depth. Features include connecting points for refrigerant pipes (gas side and liquid side) and a drain point.

Side View: Shows hanging hooks and the unit's profile.

Rear View: Displays mounting points.

Installation Clearances:

Combination Data and Miscellaneous Information

UT018GLSILCFHG (Air Handler) Specifications

SpecificationValue
Airflow Rate (cfm)588 (Turbo) / 512 (Hi) / 453 (Med) / 353 (Lo) / 265 (Mute)
Sound Level (dBA)50 (Turbo) / 46 (Hi) / 44 (Med) / 40 (Lo) / 36 (Mute)
Auto Air Circulation2-Way Louver (Up-Down + Left-Right)
Dimensions (WDH)41"-1/2 x 26"-1/2 x 9"-1/4
Weight (lbs)52.9

UT024GLSILSFHG (Air Handler) Specifications

SpecificationValue
Airflow Rate (cfm)647 (Turbo) / 588 (Hi) / 517 (Med) / 470 (Lo) / 412 (Mute)
Sound Level (dBA)53 (Turbo) / 52 (Hi) / 48 (Med) / 44 (Lo) / 40 (Mute)
Auto Air Circulation2-Way Louver (Up-Down + Left-Right)
Dimensions (WDH)41"-1/2 x 26"-1/2 x 9"-1/4
Weight (lbs)57.3

Matching Table (# Circuits Utilized)

CircuitsBTU Range
2-Circuits(9000-24000) + (9000-24000)
3-Circuits(9000-24000) + (9000-18000) + (9000-12000)
4-Circuits(9000-18000) + (9000-12000) + (9000-12000) + (9000-12000)

Piping Diameters

BTUPiping Size
18000 BTU1/4" (Liquid) - 1/2" Adapter Required (Suction)
24000 BTU1/4" (Liquid) - 5/8" Adapter Required (Suction)

Note: All Necessary Adapters Provided with Condenser.

Capacity Note: If the total demand from the combined group of indoor units exceeds the rated capacity of the outdoor unit, the capacity of each indoor unit will be adjusted accordingly. Each indoor unit operates at a variable capacity (30% to 100%) based on zone demand or turns off as needed.

Warranty Information and Length

Complete warranty details are available online at https://www.pdhvac.com/support/warranty/.

This system is eligible for up to a 5-year limited warranty on the compressor and 5 years on other internal parts when installed within 90 days and registered properly. Unregistered installations qualify for a 1-year parts/compressor warranty.

Outstanding Features

Available Accessories

Part NumberDescription
IKT-LCVR4P-KITDecorative PVC Line Cover Kit
IKT-LNBR-1/4-3/8BendAid Flexible Easy Bender Kit
BRK-FRM-C-2PFolding Mounting Bracket w/ Leveler
IKT-UVL32UL-AGUVC Bacterial Disinfection Kit
IKT-SURPRK-DV2Ultimate Surge and Power Protection

PDF preview unavailable. Download the PDF instead.

YN040GLSI24M4G UT SubmittalSheet Adobe PDF library 17.00

Related Documents

Preview Pioneer Quad-Zone Ductless Inverter Heat Pump Set Submittal Sheet YN040GLSI24M4G
This document provides detailed specifications, performance data, dimensional information, and compatibility details for the Pioneer Quad-Zone Ductless Inverter Heat Pump Set, model YN040GLSI24M4G, which supports multiple indoor air handler units.
Preview Pioneer YN040GLSI24M4G Quad (4) Circuit Ducted Inverter Heat Pump Set Submittal Sheet
Comprehensive submittal sheet for the Pioneer YN040GLSI24M4G Quad (4) Circuit Ducted Inverter Heat Pump Set, detailing cooling and heating performance, electrical specifications, piping requirements, dimensional data for indoor and outdoor units, system compatibility, and warranty information.
Preview Pioneer YN050GLSI24M5G Ductless Inverter Heat Pump Set Specifications
Detailed submittal sheet for the Pioneer YN050GLSI24M5G Quint (5) Circuit Ductless Inverter Heat Pump Set, including cooling and heating performance, electrical information, exterior unit specifications, and compatible indoor air handler units.
Preview Pioneer YN050GLSI24M5G Quint (5) Circuit Ductless Inverter Heat Pump Set Submittal Sheet
Submittal sheet for the Pioneer YN050GLSI24M5G Quint (5) Circuit Ductless Inverter Heat Pump Set, detailing cooling and heating performance, electrical specifications, piping information, condenser and air handler dimensions, combination data, and warranty details. Features include high SEER/HSPF ratings, multiple indoor unit compatibility, and energy efficiency.
Preview Pioneer YN020GLSI24M2G Dual Ductless Inverter Heat Pump System Submittal Sheet
Detailed submittal sheet for the Pioneer YN020GLSI24M2G dual circuit ductless inverter heat pump system, including performance specifications, electrical data, dimensional information, installation clearances, and features for UT018GLSILCFHG and UT024GLSILSFHG indoor units.
Preview Pioneer Quantum Ultra 12,000 BTU Ductless Heat Pump System Submittal Sheet
Submittal sheet for the Pioneer Quantum Ultra 12,000 BTU 23 SEER2 wall-mounted ductless inverter heat pump system. Details cooling and heating performance, electrical specifications, unit dimensions, piping, refrigerant, warranty, features, and accessories from Parker Davis HVAC International.
Preview Pioneer YN030GLSI24M3G Triple Circuit Ductless Inverter Heat Pump Submittal Sheet
Technical specifications and performance data for the Pioneer YN030GLSI24M3G triple circuit ductless inverter heat pump system, including outdoor condenser and indoor air handler unit details.
Preview Pioneer Quint-Zone Ductless Inverter Heat Pump System Specifications
Comprehensive submittal sheet detailing the Pioneer Quint-Zone (5) Circuit Ductless Inverter Heat Pump Set (YN050GLSI24M5G / WT0xxGLSI24HLG), covering performance, electrical, piping, dimensional data, compatibility, and warranty information.