Lindab UltraLink® Controller FTCU
Technical Information
Introduction
The UltraLink FTCU is a highly accurate airflow controller. It measures the airflow with ultrasound and can be calculated and compensated to a very high accuracy within the whole airflow range. The method is very stable over time due to its design, which minimizes the contamination of the airflow sensors.
UltraLink FTCU offers the benefits of a modern demand controlled ventilation system with only a couple of UltraLinks together with Bluetooth sensors installed in your existing ventilation system. It provides significant advantages in terms of comfort and energy savings.
Overview
Application
The FTCU is suitable for measuring and controlling airflow and temperature. Communication is established with analog and/or digital signals using Modbus.
Design
The FTCU consists of a sensor body attached to a damper body with Lindab Safe gaskets. The display unit and actuator are mounted on a cup, allowing the FTCU to be insulated up to 50 mm. Two flow sensors are mounted on the sensor body and connected to a display unit, which is mounted on top of a shelf on the damper body. The sensor and damper bodies can rotate relative to each other, enabling optimal positioning of the sensors independently of the display and damper body orientation. Correct positioning of the sensor body after a disturbance is crucial for measurement accuracy (refer to pages 6-7 for mounting directions). For FTCU dimensions 400-630, a flange connects the damper and sensor bodies; this flange must be loosened by unscrewing a nut to allow rotation. The nut size is 10 mm for FTCU dimension 400 and 13 mm for dimensions 500-630.
Display Unit
Mounting
Please note
- Do not remove the transducers!
- Do not use transducers as handles when mounting the FTCU, as this may cause damage!
- Ensure the airflow arrow points in the direction of airflow.
- Rotate the sensor body to the correct position according to the "Table of mounting distance to disturbance" on pages 6-7.
- For FTCU sizes 400-630, loosen the flange nut to turn the sensor body into the desired position, then retighten the nut.
- Position the display for visibility from a suitable direction.
- Mount the FTCU into the air duct system following the mounting instructions for Lindab Safe.
- Once positioned accurately, fix the FTCU with screws to the damper body, similar to connecting ducts and fittings.
- Never use the FTCU on the outlet side of a duct fan. Place it on the inlet side, or use a flow conditioner if it must be placed on the outlet side.
- A longer distance to disturbance (longer straight duct before the UltraLink) increases measurement accuracy.
- The motor direction switch must always be set to "1" as supplied.
- Do not make any changes or adjustments to the motor or its end-stops.
- To manually turn the damper, press the manual override button on the motor and turn the damper shaft with an 8 mm wrench or similar.
Planning
Measurement accuracy depends on two main factors: distance to disturbance (longer distance yields higher accuracy) and transducer positioning (the first transducer should be placed at the inner radius of a fitting). The FTCU can be placed at a distance of two duct diameters (Ød) from a disturbance to achieve specified uncertainty. In some cases, mounting directly onto a fitting is possible, but may require corrections in the OneLink app. Obstructions like axial fans, silencers, or cleaning hatches are not allowed before the UltraLink in the airflow direction; cleaning hatches must be placed after it. These obstructions cause turbulence and airflow measurement errors.
Table of mounting distance to disturbance
The table below shows the impact of various disturbances and transducer placements on measurement uncertainty. Measurement uncertainty is expressed as ± % or X l/s, whichever is greater, for the specific product size.
Disturbance * | Placement of first flow sensor | Measurement uncertainty (2-4Ød) | Measurement uncertainty (>4-5Ød) | Measurement uncertainty (>5Ød) | Mounting directly onto fitting without distance possible |
---|---|---|---|---|---|
Bend 90° | Inner radius (Best position) | 5 | 5 | 5 | Yes |
Bend 90° | Outer radius (Not recommended) | 20 | 10 | 5 | - |
Bend 90° | Side | 10 | 5 | 5 | - |
Reducer | Duct diameter decrease | 5 | 5 | 5 | Yes |
Reducer | Duct diameter increase | 10 | 5 | 5 | Yes |
T-piece | Inner radius (Best position) | 10 | 5 | 5 | - |
T-piece | Outer radius (Not recommended) | 20 | 10 | 5 | - |
T-piece | Side | 10 | 5 | 5 | - |
Electrical Installation
Before starting
- Do not make any holes or connect screws to the FTCU body.
- The shelf, FTES, can be used for mounting equipment like electrical junction boxes or Regula Combi units.
- Never remove the blue electronics box.
- Never remove the transducers.
[Warning symbol] For cable connections, there are two options: use the premounted cable or connect directly to the PCB (Option A and B).
Option A: Connect to premounted cable
Connect the premounted cable in a junction box near the FTCU. Connect power and signal cables according to the color scheme on the premounted cable's label. For Modbus signal wires, keep the premounted cable as short as possible to maintain signal quality. Place the junction box close to the FTCU and cut the premounted cable to the shortest necessary length.
Option B: Connect directly on PCB
To access the circuit board terminals, remove the lid by pushing the two heels on the side of the blue box. To connect cords, puncture the rubber cable grommet on the backside of the display unit using an awl or a pointed object to ensure environmental tightness. Do not remove the blue box for this. Ensure cables are strain-relieved after connection and can be attached to the shelf using cable ties through cut-outs.
General information (option A and B)
Function | Cable type |
---|---|
24 V Supply | 2-wire, thickness depending on length and load, max. 1.5 mm² |
RS485 Modbus communication | 2-wire shielded twisted pair, min. 0.1 mm² (LIYCY cable) |
Using other cables for Modbus signals may cause communication problems.
Analog connection
When using analog signals, connect the FTCU's analog out signals (AO1, AO2) to the RTU's analog in terminals. Connect the FTCU's analog in signal (AIN) to the RTU's analog out terminal. Ensure the cables are connected to the same analog ground.
Digital Connection (Modbus)
Connect the RTU's A terminal to the FTCU's -A, and the RTU's B terminal to the FTCU's +B. When connecting multiple FTCUs in series, ensure -A connects to -A and +B to +B to avoid Modbus failure. Use RS485 cables with twisted pairs and shield; do not supply power in the same cable unless it's designed for it. Connect signal ground to the "GND" terminal next to the shield (SH) terminal on the PCB, and then to the corresponding terminal in the RTU.
Connecting shield
The shield in the RS485 cable should be grounded at the transformer and then continuously connected to "SH" on all UltraLinks powered by that transformer. If multiple transformers are used, the shield must be broken at each transformer, so "SH" on each product only connects to ground at its respective transformer.
Biasing
The bus master must have biasing on -A and +B. This is standard for BMS controllers. If using a conventional computer with an RS485-USB converter, ensure the converter has a bias circuit. If communication fails, add 500-1000 Ω resistors from -A to GND and from +B to the 3V3 terminal for biasing. A 120 Ω termination resistor between -A and +B on the last UltraLink is recommended to prevent signal reflections.
Repeater
If the bus exceeds 300 meters or has more than 30 devices, an RS485 repeater (FDS-R) may be needed for efficient communication.
Power Supply
Transformer sizing
The required size of 24 V AC transformer(s) is determined by summing the power consumption [VA] of all components. The transformer power must exceed this total. Use only safety isolating transformers. The current demand (I) is calculated as: I = (P1+P2+...+Pn) / U [A], where Pn is the power consumption of each component [VA] and U is the voltage (24 V). If the current demand exceeds 6 A (approx. 150 VA for a 24 V AC transformer), use multiple transformers to prevent overheating.
Supply cable sizing
Supply cable wire size is determined by calculating the resistance per meter (R). The calculation assumes a voltage drop of 2 V in the supply cable: R(per m) = Udrop / (I * L) [Ω/m], where Udrop is the accepted voltage drop (2 V), I is the current [A], and L is the longest supply cable distance [m].
The graph below shows Wire cross section Area [mm²] as a function of Copper Resistance [Ω/m]. For example, with Udrop = 2 V, I = 4 A, and L = 20 m, R = 0.025 Ω/m, corresponding to a wire cross-section area of 0.7 mm².
Power consumption
The power consumption for sizing supply cables for an UltraLink® FTCU is 0.5 VA. It is not recommended to use a transformer with a capacity higher than 150 VA.
Commissioning
Commissioning is performed using the Lindab OneLink app. Download the app by scanning or clicking the QR code. Ensure a signal strength of at least 60% for a stable connection between the UltraLink and your phone/tablet. Log in with the factory PIN (1111) and adjust settings. If the device is near a disturbance, apply correction settings in the app to compensate for measurement uncertainty (see "Correcting flow measurement for installation close to disturbance" on page 14). Change the device PIN code as described on page 14.
Demand controlled room regulation via UltraLink
Lindab Ultra BT™ Room Control System (Installation of wireless sensors)
The Ultra BT system revolutionizes demand controlled ventilation at room level. It offers a 360-degree upgrade with integrated Bluetooth Technology, improving cost-efficiency, installation simplicity, and daily operations for optimal indoor climate.
Additional heating and cooling via analog signal
Control heating and cooling sources using UltraLink and temperature sensors. For more details on Ultra BT functionalities and commissioning, refer to the Lindab Ultra BT™ Commissioning instruction, accessible via QR code or link.
Display
The display provides useful information via a green status light and parameters shown on the LCD. A blue light indicates Bluetooth status: flashing every three seconds when standby, and every second when a device is connected. Short pressing the Mode button cycles through displayed parameters. A long press (over 5 seconds) accesses the configuration menu. Arrows at the bottom of the display indicate the current parameter type and unit.
Parameter structure
The information menu appears upon powering up, defaulting to airflow in m³/h. Parameters can be toggled using the Mode button. The available parameters include:
- Actual air flow (m³/h, l/s)
- Actual air velocity (m/s)
- Actual Temperature (°C)
- Damper position (%, 100% = fully open)
- Current set point (m³/h, l/s, m/s)
- FTCU ID number
- Flow rate set point max/min (visible only with analog control and flow rate as control variable)
Status light
Green status light:
- No light: FTCU is turned off.
- Flashing every 3 seconds: Motor is regulating to reach set point.
- Flashing every 1 second: A problem has occurred; error code will be visible in the display.
- Constant light: FTCU is turned on and functioning normally.
Blue status light:
- No light: Bluetooth is turned off or the FTCU is not equipped with it.
- Flashing every 3 seconds: Bluetooth is on standby and ready to connect to a mobile device.
- Flashing every 1 second: A mobile device has been connected to the FTCU.
Correcting flow measurement for installation close to disturbance
If installation near a disturbance is necessary, corrections are made via the OneLink app. Connect to the UltraLink, navigate to "Configuration" > "Device settings", and click "Disturbance settings". Input the type of disturbance and the distance to it. The app will then automatically correct the flow measurement.
ID-numbers
Each FTCU has a unique ID-number (1-239) based on the last three digits of its serial number, found on the product label and packaging. If multiple Modbus devices share an ID, it must be changed to ensure unique identification for communication. Disconnect other devices with the same ID before changing it via the display's "Con. Set" menu (page 15) or the OneLink app. The Modbus ID register is 4x001.
PIN code
UltraLink with Bluetooth requires a PIN code for access and settings changes. The default PIN is 1111. It is crucial to change this to prevent unauthorized access. The Bluetooth radio can be disabled by setting register 4x007 to 0. The PIN can be changed via the "OneLink" application or the display's configuration menu.
Settings for override
The FTCU offers two override functions: via bus or analog input (for 2-10V or 10-2V signals). Bus control (register 4x071=0) allows forcing the damper to fully open/closed or setting flow rate to minimum/maximum (registers 4x315, 4x316). Analog control (register 4x071=1) allows forcing the damper to fully closed, irrespective of the minimum angle setting.
Override function by bus
- Normal mode: register 4x151 = 0.
- Maximum flow rate setpoint: register 4x151 = 1.
- Minimum flow rate setpoint: register 4x151 = 2.
- Fully open damper position: register 4x151 = 3.
- Fully closed damper position: register 4x151 = 4.
Overrides can be restored manually (register 4x151=0) or automatically after a timeout (register 4x150).
Analog override function
In analog mode (4x071=1), override is active if the input voltage range is 2-10V or 10-2V (4x500=2 or 3) and the control variable is flow rate (4x070=2). Override functions are: 1. Normal mode (input voltage ≥ 2 V). 2. Fully closed damper position (if input voltage is lower than register 4x511).
Firmware update
Regular firmware updates ensure optimal performance and the latest features. To update, open the OneLink app, log in, go to "Configuration" > "Device info", and click "Firmware update".
Maintenance
The FTCU requires minimal maintenance. Visible parts can be wiped with a damp cloth.
Configuration menu structure
Settings can also be adjusted via the OneLink app. The configuration menu is accessed by long-pressing the button (5 sec). Options include:
- Con.Set (Connection settings)
- Aln.Set (Analog In settings)
- Cancel (Return to information menu)
Toggle between options with a short press; long press to select. Within Con.Set, options include Protocol (Pr.), Baud rate (b.), Stop bits (bit.), Parity (P.), Modbus ID (Id.), PLA address (PLA.), ELA address (ELA.), Pin-code (Pi.), and Control by bus (Cnt.). Use "Store" to save changes and "Cancel" to exit without saving.
Within Aln.Set, options include Max flow (qH.), Min flow (qL.), and Voltage range (r.).
Digital communication settings
Registers 4x001-4x009 configure communication settings. Default settings are active upon initial contact. These include Modbus ID (last three digits of serial number), Baud rate (19200), Parity (Odd), and Stop bits (1). Changes to communication parameters require a power cycle.
Control settings
The FTCU can be controlled via analog or digital (Modbus) signals. Key registers include 4x070 for set point type (0=no control, 1=damper position, 2=flow rate) and 4x071 for Modbus control (0=bus, 1=analog). Set points are applied using registers 4x302 (damper position) and 4x314 (flow). Damper position limits are 0-100%. Flow limits have default values but can be adjusted via registers 4x315 and 4x316. Default maximum flow values ensure guaranteed accuracy.
Size Ø [mm] | 4x314 Flow Set Point [l/s] | 4x315 Flow Set Point Minimum [l/s] | 4x316 Flow Set Point Maximum [l/s] | 4x070 Damper Regulation Conf. | 4x071 Damper Input Conf. |
---|---|---|---|---|---|
100 | 24 | 0 | 118 | 2 (Flow) | 1 (Analog) |
125 | 37 | 0 | 184 | ||
160 | 60 | 0 | 302 | ||
200 | 94 | 0 | 471 | ||
250 | 147 | 0 | 736 | ||
315 | 234 | 0 | 1169 | ||
400 | 377 | 0 | 1885 | ||
500 | 589 | 0 | 2945 | ||
630 | 935 | 0 | 4676 |
Refer to the appendix for Modbus register instructions. Settings can be changed via RS485 bus or the OneLink app.
Analog communication settings
Analog in settings via modbus
For analog communication (4x071=1), specify the operational voltage range and corresponding max/min values. Configure register 4x500 for analog input level (0-10V, 10-0V, 2-10V, or 10-2V). Configure registers 4x501-504 with max/min levels for the selected voltage range, depending on whether the device is controlled by angle (4x070=1) or flow (4x070=2). If set points are controlled via bus, this step can be skipped.
Size Ø [mm] | 4x070 Damper Regulation Conf. | 4x500 Analog In Level config | 4x501 Angle Min [%] * | 4x502 Angle Max [%] * | 4x503 Flow Min [l/s] | 4x504 Flow Max [l/s] |
---|---|---|---|---|---|---|
100 | 2 (Flow) | 2 (2-10V) | 0 | 100 | 0 | 55 |
125 | 0 | 100 | 0 | 86 | ||
160 | 0 | 100 | 0 | 141 | ||
200 | 0 | 100 | 0 | 220 | ||
250 | 0 | 100 | 0 | 344 | ||
315 | 0 | 100 | 0 | 546 | ||
400 | 0 | 100 | 0 | 880 | ||
500 | 0 | 100 | 0 | 1374 | ||
630 | 0 | 100 | 0 | 2182 |
* 0% means fully closed damper position and 100% means fully open damper position.
Analog out settings via modbus
Analog out is always active. Specify data for the two ports: Configure registers 4x401 and 4x431 for variables (0=Flow, 1=Temperature, 2=Damper position, 3=Cooling, 4=Heating). Configure registers 4x400 and 4x430 for analog out level (0-10V, 10-0V, 2-10V, 10-2V). Configure registers 4x401-409 and 4x431-439 with max/min levels for the selected voltage range and variable.
Analog Out 1 Default Values:
Size Ø [mm] | 4x400 Level Conf. | 4x401 Unit Conf. | 4x402 Temp Min [°C] | 4x403 Temp Max [°C] | 4x404 Flow Min [l/s] | 4x406 Flow Max [l/s] | 4x408 Angle Min [%] * | 4x409 Angle Max [%] * |
---|---|---|---|---|---|---|---|---|
100 | 2 (2-10V) | 0 (Flow) | 0 | 50 | 0 | 55 | 0 | 100 |
125 | 0 | 50 | 0 | 86 | 0 | 100 | ||
160 | 0 | 50 | 0 | 141 | 0 | 100 | ||
200 | 0 | 50 | 0 | 220 | 0 | 100 | ||
250 | 0 | 50 | 0 | 344 | 0 | 100 | ||
315 | 0 | 50 | 0 | 546 | 0 | 100 | ||
400 | 0 | 50 | 0 | 880 | 0 | 100 | ||
500 | 0 | 50 | 0 | 1374 | 0 | 100 | ||
630 | 0 | 50 | 0 | 2182 | 0 | 100 |
Analog Out 2 Default Values:
Size Ø [mm] | 4x430 Level Config | 4x431 Unit Conf. | 4x432 Temp Min [°C] | 4x433 Temp Max [°C] | 4x434 Flow Min [l/s] | 4x436 Flow Max [l/s] | 4x438 Angle Min [%] * | 4x439 Angle Max [%] * |
---|---|---|---|---|---|---|---|---|
100 | 2 (2-10V) | 2 (Angle) | 0 | 50 | 0 | 55 | 0 | 100 |
125 | 0 | 50 | 0 | 86 | 0 | 100 | ||
160 | 0 | 50 | 0 | 141 | 0 | 100 | ||
200 | 0 | 50 | 0 | 220 | 0 | 100 | ||
250 | 0 | 50 | 0 | 344 | 0 | 100 | ||
315 | 0 | 50 | 0 | 546 | 0 | 100 | ||
400 | 0 | 50 | 0 | 880 | 0 | 100 | ||
500 | 0 | 50 | 0 | 1374 | 0 | 100 | ||
630 | 0 | 50 | 0 | 2182 | 0 | 100 |
* 0% means fully closed damper position and 100% means fully open damper position.
Refer to the appendix for Modbus register instructions.
Troubleshooting
If digital communication fails, please verify the following before contacting support:
- Check Baud rate, parity, and stop bit settings match between master and UltraLinks (configurable via OneLink app).
- Ensure -A and +B connections are continuous and correctly wired across all devices.
- Avoid "star connection" bus layouts.
- Verify power supply cables are connected identically (G to G for 24V, G0 to G0 for GND) on all products and transformers.
- The shield must be continuous along the bus and grounded only at the transformer and the last UltraLink.
- Limit devices per bus to 30; use a repeater if necessary.
- Bus length should not exceed 300 m; use a repeater for longer runs.
- Test communication with a PC using a Configuration Tool and a biased RS485-USB converter.
- Keep stub lengths (e.g., premounted cables) to a maximum of 20 meters for a 30-device bus.
If analog signals fails, make sure to doublecheck the following:
- Measure voltage on the screw terminal; it should match the BMS controller's voltage.
- If voltage is incorrect, check wire attachment to the UltraLink terminal. A loose connection may prevent signal pickup.
Problems accessing UltraLink via Bluetooth
- Ensure the UltraLink has the Bluetooth logotype on its display lid.
- Input the correct PIN code (default: 1111) to connect. Verify the PIN with an administrator if connection fails.
I cannot find the sensor model I'm trying to pair
Ensure you have the latest firmware installed on your UltraLink (see "Firmware update" on page 14).
Error codes
If an error occurs, the status light flashes, and an error code appears on the display. The table below lists common error codes, their problems, and solutions.
Error code | Problem | Comment |
---|---|---|
Err001 | Motor not working correctly | Check motor cables and connections. |
Err002 | Angle sensor not working correctly | Try to recalibrate using OneLink app. |
Err003 | Flow set point not reached | Check if the AHU is supplying enough air. |
Err004 | Problems with flow measurement | Might be caused by: something blocking flow sensors, an electronic fault, improper sensor connection, a flawed sensor body, or duct system design causing turbulence/disturbance. |
Err05 | External sensor low battery | - |
Err06 | External sensor not reporting | - |
Cloud-Based Troubleshooting Support
Lindab offers cloud service for uploading OneLink data to assist with resolving issues. Contact your local Technical Support Team for this service.
Technical data
Technical data table
Parameter | Value |
---|---|
Power supply | AC/DC 24 (19-28) V |
Cable grommet | 7 mm |
Cable (Bus recommended) | RS485 standard cable, 2-wire shielded twisted pair, 0.25 mm² (LIYCY cable) |
Power consumption (Dim. 100-315) | 2 W / 3 VA |
Power consumption (Dim. 400-630) | 3 W / 5 VA |
Premounted cable Length | 0.7 m |
Degree of protection | IP44 |
Tightness class to environment (EN 12237) | D |
Tightness class (EN 1751) | ATC 2 |
Tightness class, past closed damper | 4 |
Pressure class, p closed damper (Dim. 100-315) | C (max 5000 Pa) |
Pressure class, p closed damper (Dim. 400-630) | B (max 2500 Pa) |
Storage temperature range | -30 to +50 °C |
Maximum ambient moisture | 95 % RH |
Connection Protocol | RS485 standard or analog / Modbus |
Output | Flow, Velocity, Temperature, Damper position (0% fully closed, 100% fully open) |
Velocity range | 0.2 - 15.0 m/s |
Measurement uncertainty flow (assuming correct installation) | ±5 % or ±1.00 l/s (for Dim. 100), up to ±6.30 l/s (for Dim. 630) |
Operating temperature range | -10 to +50 °C |
Measurement uncertainty, temperature | ±1 °C |
Bluetooth radio Frequency | 2402-2480 MHz |
Bluetooth range (free line of sight) | -40 to +9 dB |
Firmware | UltraLink, Upgradable for optimal performance and new features |
Airflows
Ø [mm] | 0.2 m/s | 7.0 m/s | 15.0 m/s | |||
---|---|---|---|---|---|---|
m³/h | l/s | m³/h | l/s | m³/h | l/s | |
100 | 6 | 2 | 198 | 55 | 425 | 118 |
125 | 9 | 3 | 309 | 86 | 662 | 184 |
160 | 14 | 4 | 507 | 141 | 1087 | 302 |
200 | 23 | 6 | 792 | 220 | 1696 | 471 |
250 | 35 | 10 | 1237 | 344 | 2650 | 736 |
315 | 56 | 16 | 1964 | 546 | 4208 | 1169 |
400 | 90 | 25 | 3167 | 880 | 6786 | 1885 |
500 | 141 | 39 | 4948 | 1374 | 10603 | 2945 |
630 | 224 | 62 | 7855 | 2182 | 16833 | 4676 |
Appendix A – Modbus register
This appendix details the Modbus registers available for the UltraLink. Each entry includes Address, FTCU/FTMU availability, Name, Description, Data type, Unit, Div (scale factor), Default value, Min/Max allowed values, and Access (Read Only/Read Write).
INPUT REGISTERS
Address | FTCU | FTMU | Name | Description | Data type | Unit | Div | Default | Min | Max | Access |
---|---|---|---|---|---|---|---|---|---|---|---|
3x008 | X | X | Product Nominal Size | Nominal diameter of duct | 16bit | mm | - | - | - | - | RO |
3x013 | X | X | Unit Status | Current unit status: 0 = Normal mode; 1 = Locating flow; 2 = Override control; 3 = Error; 4 = Control loop regulating; 5 = Angle sensor calibrating | 16bit | - | - | - | - | RO | |
3x150 | X | X | Flow info | Velocity in m/s | Float | m/s | - | - | - | - | RO |
3x152 | X | X | Air flow in m³/h | Air flow in m³/h | Float | m³/h | - | - | - | - | RO |
3x154 | X | X | Air flow in l/s | Air flow in l/s | Float | l/s | - | - | - | - | RO |
3x200 | X | X | Temperature info | Current temperature in °C | 16bit | °C | 10 | - | - | - | RO |
Damper info
Address | FTCU | FTMU | Name | Description | Data type | Unit | Div | Default | Min | Max | Access |
---|---|---|---|---|---|---|---|---|---|---|---|
3x251 | X | Damper open in % | Damper actual position in percentage open. | 16bit | % | 10 | - | - | - | RO | |
3x252 | X | Damper motor action | Damper motor action: 0 = Motor stopped; 1 = Motor opening damper; 2 = Motor closing damper | 16bit | - | - | - | - | RO |
Alarms
Address | FTCU | FTMU | Name | Description | Data type | Unit | Div | Default | Min | Max | Access |
---|---|---|---|---|---|---|---|---|---|---|---|
3x400 | X | X | Alarm Register 1 | Alarms 1-32 - bitwise: 1 = Motor not working; 2 = Angle sensor not working correctly; 3 = Flow setpoint not reached; 4 = Flow measure problems; 5 = External sensor low battery; 6 = External sensor not responding; 7-31 = Reserved for future use; 32 = Factory data is corrupted. | 32bit | - | - | - | - | RO |
Other
Address | FTCU | FTMU | Name | Description | Data type | Unit | Div | Default | Min | Max | Access |
---|---|---|---|---|---|---|---|---|---|---|---|
3x500 | X | X | Signal amplification | Current signal amplification | 16bit | - | 100 | 3 | 20 | RO |
Sensor
Address | FTCU | FTMU | Name | Description | Data type | Unit | Div | Default | Min | Max | Access |
---|---|---|---|---|---|---|---|---|---|---|---|
3x2001 | X | X | Sensor Global Set Point Factor | Multiplication factor for flow set point | 16bit | - | 100 | 100 | - | - | RO |
3x2002 | X | X | Sensor Global Factored Set Point | Holding register FLOW_SET_POINT (314) multiplied with SENSOR_GLOBAL_SET_POINT_FACTOR | 16bit | l/s | - | - | - | - | RO |
3x2007 | X | X | Sensor Global State for Control | Current state of control: 0 = Off; 1 = Unoccupied; 2 = Normal; 3 = Forced; 4 = Delayed presence; 5 = Temperature increase; 6 = Temperature decrease; 7 = CO₂ decrease; 8 = Humidity increase; 9 = Humidity decrease; 10 = VOC decrease; 11 = Particles decrease; 50 = Flow slave; 100 = Clearing error; 101 = Error C1; 102 = Error C2; 103 = Error C3; 104 = Error C4; 105 = Error C5; 106 = Error C6 | 16bit | - | - | - | - | RO | |
3x2012 | X | X | Sensor Com Current Presence Sum | Current Presence based on sum from all sensors | 16bit | - | - | - | - | RO | |
3x2014 | X | X | Sensor Com Presence State | 0 = Disabled; 1 = Unoccupied; 2 = Normal; 3 = Forced; 4 = Delayed presence; 5 = Error | 16bit | - | - | - | - | RO | |
3x2021 | X | X | Sensor Com Min. Temp | Minimum Temperature | 16bit | °C | 10 | - | - | - | RO |
3x2022 | X | X | Sensor Com Max. Temp | Maximum Temperature | 16bit | °C | 10 | - | - | - | RO |
3x2023 | X | X | Sensor Com Average Temp | Average Temperature | 16bit | °C | 10 | - | - | - | RO |
3x2025 | X | X | Sensor Com Temp State | 0 = Disabled; 1 = Within deadband; 2 = Outside deadband; 3 = Error | 16bit | - | - | - | - | RO | |
3x2034 | X | X | Sensor Com Summed Flow | Summed Flow | 16bit | l/s | - | - | - | - | RO |
3x2036 | X | X | Sensor Com Flow State | 0 = Disabled; 1 = Within deadband; 2 = Outside deadband; 3 = Error | 16bit | - | - | - | - | RO | |
3x2041 | X | X | Sensor Com Min. Humidity | Minimum Humidity | 16bit | % RH | 10 | - | - | - | RO |
3x2042 | X | X | Sensor Com Max. Humidity | Maximum Humidity | 16bit | % RH | 10 | - | - | - | RO |
3x2043 | X | X | Sensor Com Average Humidity | Average Humidity | 16bit | % RH | 10 | - | - | - | RO |
3x2045 | X | X | Sensor Com Humidity State | 0 = Disabled; 1 = Within deadband; 2 = Outside deadband; 3 = Error | 16bit | - | - | - | - | RO | |
3x2051 | X | X | Sensor Com Minimum CO₂ | Minimum CO₂ | 16bit | ppm | - | - | - | - | RO |
3x2052 | X | X | Sensor Com Maximum CO₂ | Maximum CO₂ | 16bit | ppm | - | - | - | - | RO |
3x2053 | X | X | Sensor Com Average CO₂ | Average CO₂ | 16bit | ppm | - | - | - | - | RO |
3x2055 | X | X | Sensor Com CO₂ State | 0 = Disabled; 1 = Within deadband; 2 = Outside deadband; 3 = Error | 16bit | - | - | - | - | RO | |
3x2103 | X | X | Sensor 1 Battery Level | Sensor 1 battery level | 16bit | % | - | - | - | - | RO |
3x2104 | X | X | Sensor 1 RSSI | Sensor 1 RSSI | 16bit | % | - | - | - | - | RO |
3x2107 | X | X | Sensor 1 Current Presence | Sensor 1 Current Presence | 16bit | - | - | - | - | RO | |
3x2108 | X | X | Sensor 1 Temperature | Sensor 1 Temperature | 16bit | °C | 10 | - | - | - | RO |
3x2109 | X | X | Sensor 1 Flow | Sensor 1 Flow | 16bit | l/s | 10 | - | - | - | RO |
3x2110 | X | X | Sensor 1 Humidity | Sensor 1 Humidity | 16bit | % RH | 10 | - | - | - | RO |
3x2111 | X | X | Sensor 1 CO₂ | Sensor 1 CO₂ | 16bit | ppm | - | - | - | - | RO |
3x2123 | X | X | Sensor 2 Battery Level | Sensor 2 battery level | 16bit | % | - | - | - | - | RO |
3x2124 | X | X | Sensor 2 RSSI | Sensor 2 RSSI | 16bit | % | - | - | - | - | RO |
3x2127 | X | X | Sensor 2 Current Presence | Sensor 2 Current Presence | 16bit | - | - | - | - | RO | |
3x2128 | X | X | Sensor 2 Temperature | Sensor 2 Temperature | 16bit | °C | 10 | - | - | - | RO |
3x2129 | X | X | Sensor 2 Flow | Sensor 2 Flow | 16bit | l/s | 10 | - | - | - | RO |
3x2130 | X | X | Sensor 2 Humidity | Sensor 2 Humidity | 16bit | % RH | 10 | - | - | - | RO |
3x2131 | X | X | Sensor 2 CO₂ | Sensor 2 CO₂ | 16bit | ppm | - | - | - | - | RO |
3x2143 | X | X | Sensor 3 Battery Level | Sensor 3 battery level | 16bit | % | - | - | - | - | RO |
3x2144 | X | X | Sensor 3 RSSI | Sensor 3 RSSI | 16bit | % | - | - | - | - | RO |
3x2147 | X | X | Sensor 3 Current Presence | Sensor 3 Current Presence | 16bit | - | - | - | - | RO | |
3x2148 | X | X | Sensor 3 Temperature | Sensor 3 Temperature | 16bit | °C | 10 | - | - | - | RO |
3x2149 | X | X | Sensor 3 Flow | Sensor 3 Flow | 16bit | l/s | 10 | - | - | - | RO |
3x2150 | X | X | Sensor 3 Humidity | Sensor 3 Humidity | 16bit | % RH | 10 | - | - | - | RO |
3x2151 | X | X | Sensor 3 CO₂ | Sensor 3 CO₂ | 16bit | ppm | - | - | - | - | RO |
3x2163 | X | X | Sensor 4 Battery Level | Sensor 4 battery level | 16bit | % | - | - | - | - | RO |
3x2164 | X | X | Sensor 4 RSSI | Sensor 4 RSSI | 16bit | % | - | - | - | - | RO |
3x2167 | X | X | Sensor 4 Current Presence | Sensor 4 Current Presence | 16bit | - | - | - | - | RO | |
3x2168 | X | X | Sensor 4 Temperature | Sensor 4 Temperature | 16bit | °C | 10 | - | - | - | RO |
3x2169 | X | X | Sensor 4 Flow | Sensor 4 Flow | 16bit | l/s | 10 | - | - | - | RO |
3x2170 | X | X | Sensor 4 Humidity | Sensor 4 Humidity | 16bit | % RH | 10 | - | - | - | RO |
3x2171 | X | X | Sensor 4 CO₂ | Sensor 4 CO₂ | 16bit | ppm | - | - | - | - | RO |
3x2183 | X | X | Sensor 5 Battery Level | Sensor 5 battery level | 16bit | % | - | - | - | - | RO |
3x2184 | X | X | Sensor 5 RSSI | Sensor 5 RSSI | 16bit | % | - | - | - | - | RO |
HOLDING REGISTERS
Communication settings
Address | FTCU | FTMU | Name | Description | Data type | Unit | Div | Default | Min | Max | Access |
---|---|---|---|---|---|---|---|---|---|---|---|
4x001 | X | X | Communication id | Modbus address | 16bit | - | 1 | 1 | 239 | RW | |
4x002 | X | X | RS485 Baud Rate Conf. | Baudrate: 0 = 9600; 1 = 19200; 2 = 38400; 3 = 76800 | 16bit | - | 1 | 0 | 3 | RW | |
4x003 | X | X | RS485 Parity Conf. | Parity: 0 = Odd; 1 = Even; 2 = None | 16bit | - | 1 | 0 | 2 | RW | |
4x004 | X | X | RS485 Stop Bit Conf. | Number of stopbits: 1 or 2. | 16bit | - | 1 | 1 | 2 | RW | |
4x005 | X | X | RS485 Protocol Conf. | Protocol: 0 = Modbus; 1 = Not used; 2 = Pascal; | 16bit | - | 1 | 0 | 2 | RW | |
4x006 | X | X | Bluetooth Password | Password required for pairing Bluetooth devices. Can be changed via wired connection or current password via wireless. | 16bit | - | 1111 | 0000 | 9999 | RW | |
4x007 | X | X | Bluetooth Enable | Enable Bluetooth Communication: 0 = Off; 1 = On; | 16bit | - | 1 | 0 | 2 | RW | |
4x008 | X | X | PLA | ID used for Pascal | 16bit | - | 1 | 1 | 239 | RW | |
4x009 | X | X | ELA | ID used for Pascal | 16bit | - | 1 | 1 | 239 | RW | |
4x010 | X | X | Bluetooth TX Power Level | Configure TX Power Level in dBm. Accepted values: -40, -20, -16, -12, -8, -4, 0, 2, 3, 4, 5, 6, 7, 8, 9 | 16bit | - | 0 | -40 | 9 | RW |
System configuration
Address | FTCU | FTMU | Name | Description | Data type | Unit | Div | Default | Min | Max | Access |
---|---|---|---|---|---|---|---|---|---|---|---|
4x070 | X | Damper Regulation Conf. | Specifies how damper is regulated: 0 = Regulator turned off; 1 = Regulate damper angle; 2 = Regulate flow | 16bit | - | 2 | 0 | 2 | RW | ||
4x071 | X | Damper Input Conf. | Specifies input to control damper: 0 = Modbus or Pascal; 1 = Analog input | 16bit | - | 1 | 0 | 1 | RW | ||
4x072 | X | X | Installation as Extract or Supply | Specifies if device is in supply or extract: 0 = Undefined; 1 = Supply; 2 = Extract | 16bit | - | 0 | 0 | 2 | RW | |
4x073 | X | X | Installation Zone Number | Specifies in which zone the product is installed in | 16 bit | - | 0 | 0 | 65535 | RW | |
4x074 | X | X | Installation Floor Number | Specifies on which floor the product is installed in | 16bit | - | 0 | 0 | 65535 | RW | |
4x082 | X | X | Execute Factory Reset | Factory reset of all parameters. Unit will restart: 0 = Do nothing; 1 = Factory Reset | 16bit | - | 0 | 0 | 1 | RW | |
4x083 | X | X | Execute Reboot | Reboot the unit: 0 = Do nothing; 1 = Reboot the unit; | 16bit | - | 0 | 0 | 1 | RW |
Override configuration
Address | FTCU | FTMU | Name | Description | Data type | Unit | Div | Default | Min | Max | Access |
---|---|---|---|---|---|---|---|---|---|---|---|
4x150 | X | Damper Override Timeout | Time before returning to normal mode | 16bit | min | 120 | 0 | 600 | RW | ||
4x151 | X | Damper Override Conf. | 0 = Normal mode; 1 = Override control - Max open; 2 = Override control - Min open; 3 = Override control - 100% open; 4 = Override control - 100% closed | 16bit | - | 0 | 0 | 4 | RW |
Damper
Address | FTCU | FTMU | Name | Description | Data type | Unit | Div | Default | Min | Max | Access |
---|---|---|---|---|---|---|---|---|---|---|---|
4x300 | X | Execute Angle Calibration | 0 = Do nothing; 1 = Start recalibration of the angle sensor; 2 = Start recalibration when starting up; | 16bit | - | 0 | 0 | 2 | RW | ||
4x302 | X | Angle Set Point | Angle setpoint used in normal mode. (Only relevant when 4x070 is set to 1) | 16bit | % | - | 0 | 0 | 100 | RW | |
4x314 | X | Flow Set Point | Flow setpoint used in normal mode. (Only relevant when 4x070 is set to 2) | 16bit | l/s | * | - | 0 | 4700 | RW | |
4x315 | X | Flow Set Point Minimum | Flow setpoint min. | 16bit | l/s | * | - | 0 | 4700 | RW | |
4x316 | X | Flow Set Point Maximum | Flow setpoint max. | 16bit | l/s | * | - | 0 | 4700 | RW |
Analog output
Address | FTCU | FTMU | Name | Description | Data type | Unit | Div | Default | Min | Max | Access |
---|---|---|---|---|---|---|---|---|---|---|---|
4x400 | X | X | Analog Output 1 Level Conf. | Analog output config: 0 = 0-10 V; 1 = 10-0 V; 2 = 2-10 V; 3 = 10-2 V. | 16bit | - | 2 | 0 | 3 | RW | |
4x401 | X | X | Analog Output 1 Unit Conf. | Show: 0 = Flow; 1 = Temperature; 2 = Angle; | 16bit | - | 0 | 0 | 2 | RW | |
4x402 | X | X | Analog Output 1 Temp. Min. | Min temperature shown = Min output voltage (Only relevant when 4x401 is set to 1) | 16bit | °C | - | 0 | -40 | 50 | RW |
4x403 | X | X | Analog Output 1 Temp. Max. | Max temperature shown = Max output voltage (Only relevant when 4x401 is set to 1) | 16bit | °C | - | 50 | -40 | 50 | RW |
4x404 | X | X | Analog Output 1 Flow Min. | Min flow shown = Min output voltage (Only relevant when 4x401 is set to 0) | 16bit | l/s | - | 0 | -4700 | 4700 | RW |
4x406 | X | X | Analog Output 1 Flow Max. | Max flow shown = Max output voltage (Only relevant when 4x401 is set to 0) | 16bit | l/s | * | - | -4700 | 4700 | RW |
4x408 | X | Analog Output 1 % Open Min. | Min open % shown = Min output voltage (Only relevant when 4x401 is set to 2) | 16bit | % | - | 10 | 0 | 1000 | RW | |
4x409 | X | Analog Output 1 % Open Max. | Max open % shown = Max output voltage (Only relevant when 4x401 is set to 2) | 16bit | % | - | 10 | 1000 | 0 | 1000 | RW |
4x430 | X | X | Analog Output 2 Level Conf. | Analog output config: 0 = 0-10 V; 1 = 10-0 V; 2 = 2-10 V; 3 = 10-2 V. | 16bit | - | 2 | 0 | 3 | RW | |
4x431 | X | X | Analog Output 2 Unit Conf. | Show: 0 = Flow; 1 = Temperature; 2 = Angle; | 16bit | - | 2 | 0 | 2 | RW | |
4x432 | X | X | Analog Output 2 Temp. Min. | Min temperature shown = Min output voltage (Only relevant when 4x431 is set to 1) | 16bit | °C | - | 0 | -40 | 50 | RW |
4x433 | X | X | Analog Output 2 Temp. Max. | Max temperature shown = Max output voltage (Only relevant when 4x431 is set to 1) | 16bit | °C | - | 50 | -40 | 50 | RW |
4x434 | X | X | Analog Output 2 Flow Min. | Min flow shown = Min output voltage (Only relevant when 4x431 is set to 0) | 16bit | l/s | - | 0 | -4700 | 4700 | RW |
4x436 | X | X | Analog Output 2 Flow Max. | Max flow shown = Max output voltage (Only relevant when 4x431 is set to 0) | 16bit | l/s | * | - | -4700 | 4700 | RW |
4x438 | X | Analog Output 2 % Open Min. | Min open % shown = Min output voltage (Only relevant when 4x431 is set to 2) | 16bit | % | - | 10 | 0 | 1000 | RW | |
4x439 | X | Analog Output 2 % Open Max. | Max open % shown = Max output voltage (Only relevant when 4x431 is set to 2) | 16bit | % | * | 10 | 1000 | 0 | 1000 | RW |
* 0% means fully closed damper position and 100% means fully open damper position.
Analog input settings via modbus
For analog input settings (relevant when register 4x071 is set to 1): Configure 4x500 for analog input level (0-10V, 10-0V, 2-10V, 10-2V). Configure registers 4x501-504 for max/min levels based on the selected voltage range and control variable (angle or flow). If set points are controlled via bus, these settings can be skipped.
Address | FTCU | FTMU | Name | Description | Data type | Unit | Div | Default | Min | Max | Access |
---|---|---|---|---|---|---|---|---|---|---|---|
4x500 | X | Analog In Level Conf. | Analog input: 0 = 0-10 V; 1 = 10-0 V; 2 = 2-10 V; 3 = 10-2 V. | 16bit | - | 2 | 0 | 3 | RW | ||
4x501 | X | Analog In Angle Minimum | Min angle = min voltage | 16bit | % | - | 0 | 0 | 100 | RW | |
4x502 | X | Analog In Angle Maximum | Max = max voltage | 16bit | % | - | 100 | 0 | 100 | RW | |
4x503 | X | Analog In Flow Minimum | Min flow = min voltage (Must be equal or higher than register 4x315) | 16bit | l/s | - | 0 | 0 | 4700 | RW | |
4x504 | X | Analog In Flow Maximum | Max flow = max voltage (Must be equal or lower than register 4x316) | 16bit | l/s | * | - | 0 | 4700 | RW | |
4x510 | X | Analog In Override Low Trigger Min. | Lowest voltage level to activate 1st Override level (Only relevant when 4x500 is set to 2 or 3) | 16bit | V | - | 10 | 0 | 20 | RW | |
4x511 | X | Analog In Override Low Trigger Max. | Highest voltage level to activate 1st Override level (Only relevant when 4x500 is set to 2 or 3) | 16bit | V | - | 10 | 8 | 20 | RW |
Sensor
Address | FTCU | FTMU | Name | Description | Data type | Unit | Div | Default | Min | Max | Access |
---|---|---|---|---|---|---|---|---|---|---|---|
4x2100 | X | X | Sensor Presence Enable Control | 0 = Disable; 1 = Enable | 16bit | - | - | 0 | 1 | RW | |
4x2101 | X | X | Sensor Presence Trigger Time | Temporary trigger time for presence | 16bit | min | - | 1 | 0 | 60 | RW |
4x2102 | X | X | Sensor Presence Trigger Factor | Factor related to toggle 0 -> 1 | 16bit | % | - | 100 | 49 | 501 | RW |
4x2103 | X | X | Sensor Unoccupied Multiplication Factor | Multiplication factor for Unoccupied | 16bit | % | - | 100 | 50 | 501 | RW |
4x2104 | X | Sensor Presence Economy Mode | 0 = Comfort / 1 = Economy | 16bit | - | 1 | 0 | 1 | RW | ||
4x2110 | X | X | Sensor Temperature Enable Control | 0 = Disable; 1 = max; 2 = min; 3 = avg | 16bit | - | 0 | 0 | 3 | RW | |
4x2111 | X | X | Sensor Temperature Baseline | Baseline for temperature | 16bit | °C | - | 22 | -50 | 50 | RW |
4x2112 | X | X | Sensor Temperature Deviation | Allowed deviation before full factor effect | 16bit | °C | - | 2 | 0 | 50 | RW |
4x2113 | X | X | Sensor Temperature Dead Band | Dead band for sensor type Temperature | 16bit | % | - | 100 | 50 | 101 | RW |
4x2114 | X | X | Sensor Temperature Multiplication Factor | Multiplication factor for Temperature | 16bit | % | - | 100 | 150 | 501 | RW |
4x2115 | X | Sensor Temperature Baseline Minimum | Lower limit for baseline setting | 16bit | °C | - | 20 | 0 | 50 | RW | |
4x2116 | X | Sensor Temperature Baseline Maximum | Upper limit for baseline setting | 16bit | °C | - | 25 | 0 | 50 | RW | |
4x2117 | X | Sensor Temperature Difference | Minimum temperature difference before regulating | 16bit | °C | - | 1 | 0 | 5 | RW | |
4x2120 | X | X | Sensor Flow Enable Control | 0 = Disable; 1 = Sum | 16bit | - | - | 0 | 1 | RW | |
4x2121 | X | X | Sensor Flow Dead Band | Dead band for sensor type Flow | 16bit | % | - | 100 | 2 | 100 | RW |
4x2122 | X | X | Sensor Flow Multiplication Factor | Multiplication factor for Flow | 16bit | % | - | 100 | 0 | 500 | RW |
4x2123 | X | Sensor Flow Offset | Offset for Flow regulation | 16bit | l/s | - | 0 | -5000 | 5000 | RW | |
4x2124 | X | Sensor Flow Set Point Source | "0 = Use summed flow as set-point; 1 = Use current set-point reduced with summed flow; 2 = Use current set-point added with summed flow" | 16bit | - | - | 0 | 2 | RW | ||
4x2130 | X | X | Sensor Humidity Enable Control | 0 = Disable; 1 = max; 2 = min; 3 =avg | 16bit | - | 0 | 0 | 3 | RW | |
4x2131 | X | X | Sensor Humidity Baseline | Baseline for humidity | 16bit | % | - | 50 | 0 | 100 | RW |
4x2132 | X | X | Sensor Humidity Deviation | Allowed deviation before full factor effect | 16bit | % | - | 20 | 0 | 100 | RW |
4x2133 | X | X | Sensor Humidity Dead Band | Dead band for sensor type Humidity | 16bit | % | - | 100 | 50 | 101 | RW |
4x2134 | X | X | Sensor Humidity Multiplication Factor | Multiplication factor for Humidity | 16bit | % | - | 100 | 150 | 501 | RW |
4x2135 | X | X | Sensor Humidity Supplied | Estimated value of supply air humidity | 16bit | % | - | 50 | 0 | 100 | RW |
4x2136 | X | Sensor Humidity Baseline Minimum | Lower limit for baseline setting | 16bit | % | - | 30 | 0 | 100 | RW | |
4x2137 | X | Sensor Humididty Baseline Maximum | Upper limit for baseline setting | 16bit | % | - | 70 | 0 | 100 | RW | |
4x2138 | X | Sensor Humidity Difference | Minimum humidity difference before regulating | 16bit | % | - | 10 | 0 | 100 | RW | |
4x2140 | X | X | Sensor CO₂ Enable Control | 0 = Disable; 1 = max; 2 = min; 3 =avg | 16bit | - | - | 0 | 3 | RW | |
4x2141 | X | X | Sensor CO₂ Baseline | Baseline for CO₂ | 16bit | ppm | - | 600 | 400 | 2000 | RW |
4x2142 | X | X | Sensor CO₂ Deviation | Allowed deviation before full factor effect | 16bit | ppm | - | 400 | 0 | 1000 | RW |
4x2143 | X | X | Sensor CO₂ Dead Band | Dead band for sensor type CO₂ | 16bit | % | - | 100 | 50 | 101 | RW |
4x2144 | X | X | Sensor CO₂ Multiplication Factor | Multiplication factor for CO₂ | 16bit | % | - | 100 | 150 | 501 | RW |
4x2145 | X | X | Sensor CO₂ Supplied | Estimated value of supply air CO₂ | 16bit | ppm | - | 400 | 300 | 2000 | RW |
4x2146 | X | Sensor CO₂ Baseline Minimum | Lower limit for baseline setting | 16bit | ppm | - | 400 | 0 | 2000 | RW | |
4x2147 | X | Sensor CO₂ Baseline Maximum | Upper limit for baseline setting | 16bit | ppm | - | 800 | 0 | 2000 | RW | |
4x2148 | X | Sensor CO₂ Difference | Minimum CO₂ difference before regulating | 16bit | ppm | - | 50 | 0 | 500 | RW |
About Lindab
Most of us spend the majority of our time indoors. Indoor climate is crucial to how we feel, how productive we are and if we stay healthy.
Lindab's objective is to contribute to an indoor climate that improves people's lives by developing energy-efficient ventilation solutions and durable building products. Lindab also aims to contribute to a better climate for our planet by working sustainably for both people and the environment.
Lindab | For a better climate