Lindab UltraLink FTCU Controller: Technical Information and Installation Guide

Lindab UltraLink® Controller FTCU

Technical Information

Introduction

The UltraLink FTCU is a highly accurate airflow controller. It measures the airflow with ultrasound and can be calculated and compensated to a very high accuracy within the whole airflow range. The method is very stable over time due to its design, which minimizes the contamination of the airflow sensors.

UltraLink FTCU offers the benefits of a modern demand controlled ventilation system with only a couple of UltraLinks together with Bluetooth sensors installed in your existing ventilation system. It provides significant advantages in terms of comfort and energy savings.

Overview

Application

The FTCU is suitable for measuring and controlling airflow and temperature. Communication is established with analog and/or digital signals using Modbus.

Design

The FTCU consists of a sensor body attached to a damper body with Lindab Safe gaskets. The display unit and actuator are mounted on a cup, allowing the FTCU to be insulated up to 50 mm. Two flow sensors are mounted on the sensor body and connected to a display unit, which is mounted on top of a shelf on the damper body. The sensor and damper bodies can rotate relative to each other, enabling optimal positioning of the sensors independently of the display and damper body orientation. Correct positioning of the sensor body after a disturbance is crucial for measurement accuracy (refer to pages 6-7 for mounting directions). For FTCU dimensions 400-630, a flange connects the damper and sensor bodies; this flange must be loosened by unscrewing a nut to allow rotation. The nut size is 10 mm for FTCU dimension 400 and 13 mm for dimensions 500-630.

Diagram showing the Lindab UltraLink FTCU controller for dimensions 100-315mm, illustrating the display unit, damper body, premounted cable, transducer, and sensor body.
Diagram showing the Lindab UltraLink FTCU controller for dimensions 400-630mm, illustrating the display unit, damper body, transducer covers, and flange.

Display Unit

Illustration of the FTCU display unit, highlighting the QR code, Mode button, airflow direction indicator, status indicators (Status, Airflow), Bluetooth® logotype, CE-mark, IP classification, and display parameters.

Mounting

Please note

  • Do not remove the transducers!
  • Do not use transducers as handles when mounting the FTCU, as this may cause damage!
  • Ensure the airflow arrow points in the direction of airflow.
  • Rotate the sensor body to the correct position according to the "Table of mounting distance to disturbance" on pages 6-7.
  • For FTCU sizes 400-630, loosen the flange nut to turn the sensor body into the desired position, then retighten the nut.
  • Position the display for visibility from a suitable direction.
  • Mount the FTCU into the air duct system following the mounting instructions for Lindab Safe.
  • Once positioned accurately, fix the FTCU with screws to the damper body, similar to connecting ducts and fittings.
  • Never use the FTCU on the outlet side of a duct fan. Place it on the inlet side, or use a flow conditioner if it must be placed on the outlet side.
  • A longer distance to disturbance (longer straight duct before the UltraLink) increases measurement accuracy.
  • The motor direction switch must always be set to "1" as supplied.
  • Do not make any changes or adjustments to the motor or its end-stops.
  • To manually turn the damper, press the manual override button on the motor and turn the damper shaft with an 8 mm wrench or similar.
Diagram showing the FTCU unit with transducers and airflow direction arrow.
Diagram showing the FTCU with a flange for larger dimensions.
Diagram illustrating the correct mounting of the FTCU into an air duct system, showing a QR code for mounting instructions.
Diagram showing the FTCU fixed with screws to the damper body.
Diagram illustrating the placement of the FTCU on the inlet side of a duct fan, or with a flow conditioner on the outlet side.
Diagram showing a duct fan, motor direction switch, and airflow direction arrow.
Diagram showing the motor override button and damper shaft.

Planning

Measurement accuracy depends on two main factors: distance to disturbance (longer distance yields higher accuracy) and transducer positioning (the first transducer should be placed at the inner radius of a fitting). The FTCU can be placed at a distance of two duct diameters (Ød) from a disturbance to achieve specified uncertainty. In some cases, mounting directly onto a fitting is possible, but may require corrections in the OneLink app. Obstructions like axial fans, silencers, or cleaning hatches are not allowed before the UltraLink in the airflow direction; cleaning hatches must be placed after it. These obstructions cause turbulence and airflow measurement errors.

Table of mounting distance to disturbance

The table below shows the impact of various disturbances and transducer placements on measurement uncertainty. Measurement uncertainty is expressed as ± % or X l/s, whichever is greater, for the specific product size.

Disturbance * Placement of first flow sensor Measurement uncertainty (2-4Ød) Measurement uncertainty (>4-5Ød) Measurement uncertainty (>5Ød) Mounting directly onto fitting without distance possible
Bend 90° Inner radius (Best position) 5 5 5 Yes
Bend 90° Outer radius (Not recommended) 20 10 5 -
Bend 90° Side 10 5 5 -
Reducer Duct diameter decrease 5 5 5 Yes
Reducer Duct diameter increase 10 5 5 Yes
T-piece Inner radius (Best position) 10 5 5 -
T-piece Outer radius (Not recommended) 20 10 5 -
T-piece Side 10 5 5 -
Diagram showing the FTCU controller with serial number and ID details.
Diagram showing airflow direction and numbered disturbance points (1, 2, 3) related to turbulence.
Diagram showing a 90° bend in a duct and the placement of the first flow sensor at the inner radius.

Electrical Installation

Before starting

  • Do not make any holes or connect screws to the FTCU body.
  • The shelf, FTES, can be used for mounting equipment like electrical junction boxes or Regula Combi units.
  • Never remove the blue electronics box.
  • Never remove the transducers.

[Warning symbol] For cable connections, there are two options: use the premounted cable or connect directly to the PCB (Option A and B).

Option A: Connect to premounted cable

Connect the premounted cable in a junction box near the FTCU. Connect power and signal cables according to the color scheme on the premounted cable's label. For Modbus signal wires, keep the premounted cable as short as possible to maintain signal quality. Place the junction box close to the FTCU and cut the premounted cable to the shortest necessary length.

Image of the FTCU unit with premounted cable and connection points.

Option B: Connect directly on PCB

To access the circuit board terminals, remove the lid by pushing the two heels on the side of the blue box. To connect cords, puncture the rubber cable grommet on the backside of the display unit using an awl or a pointed object to ensure environmental tightness. Do not remove the blue box for this. Ensure cables are strain-relieved after connection and can be attached to the shelf using cable ties through cut-outs.

Image of the FTCU's printed circuit board (PCB) with terminal connections.

General information (option A and B)

Function Cable type
24 V Supply 2-wire, thickness depending on length and load, max. 1.5 mm²
RS485 Modbus communication 2-wire shielded twisted pair, min. 0.1 mm² (LIYCY cable)

Using other cables for Modbus signals may cause communication problems.

Analog connection

When using analog signals, connect the FTCU's analog out signals (AO1, AO2) to the RTU's analog in terminals. Connect the FTCU's analog in signal (AIN) to the RTU's analog out terminal. Ensure the cables are connected to the same analog ground.

Diagram illustrating analog connection between FTCU and RTU.

Digital Connection (Modbus)

Connect the RTU's A terminal to the FTCU's -A, and the RTU's B terminal to the FTCU's +B. When connecting multiple FTCUs in series, ensure -A connects to -A and +B to +B to avoid Modbus failure. Use RS485 cables with twisted pairs and shield; do not supply power in the same cable unless it's designed for it. Connect signal ground to the "GND" terminal next to the shield (SH) terminal on the PCB, and then to the corresponding terminal in the RTU.

Connecting shield

The shield in the RS485 cable should be grounded at the transformer and then continuously connected to "SH" on all UltraLinks powered by that transformer. If multiple transformers are used, the shield must be broken at each transformer, so "SH" on each product only connects to ground at its respective transformer.

Biasing

The bus master must have biasing on -A and +B. This is standard for BMS controllers. If using a conventional computer with an RS485-USB converter, ensure the converter has a bias circuit. If communication fails, add 500-1000 Ω resistors from -A to GND and from +B to the 3V3 terminal for biasing. A 120 Ω termination resistor between -A and +B on the last UltraLink is recommended to prevent signal reflections.

Repeater

If the bus exceeds 300 meters or has more than 30 devices, an RS485 repeater (FDS-R) may be needed for efficient communication.

Image of an RS485 repeater (FDS-R).

Power Supply

Transformer sizing

The required size of 24 V AC transformer(s) is determined by summing the power consumption [VA] of all components. The transformer power must exceed this total. Use only safety isolating transformers. The current demand (I) is calculated as: I = (P1+P2+...+Pn) / U [A], where Pn is the power consumption of each component [VA] and U is the voltage (24 V). If the current demand exceeds 6 A (approx. 150 VA for a 24 V AC transformer), use multiple transformers to prevent overheating.

Supply cable sizing

Supply cable wire size is determined by calculating the resistance per meter (R). The calculation assumes a voltage drop of 2 V in the supply cable: R(per m) = Udrop / (I * L) [Ω/m], where Udrop is the accepted voltage drop (2 V), I is the current [A], and L is the longest supply cable distance [m].

The graph below shows Wire cross section Area [mm²] as a function of Copper Resistance [Ω/m]. For example, with Udrop = 2 V, I = 4 A, and L = 20 m, R = 0.025 Ω/m, corresponding to a wire cross-section area of 0.7 mm².

Graph showing Wire cross section Area [mm²] as a function of Copper Resistance [Ω/m].

Power consumption

The power consumption for sizing supply cables for an UltraLink® FTCU is 0.5 VA. It is not recommended to use a transformer with a capacity higher than 150 VA.

Commissioning

Commissioning is performed using the Lindab OneLink app. Download the app by scanning or clicking the QR code. Ensure a signal strength of at least 60% for a stable connection between the UltraLink and your phone/tablet. Log in with the factory PIN (1111) and adjust settings. If the device is near a disturbance, apply correction settings in the app to compensate for measurement uncertainty (see "Correcting flow measurement for installation close to disturbance" on page 14). Change the device PIN code as described on page 14.

QR codes for downloading the Lindab OneLink app from the App Store and Google Play.

Demand controlled room regulation via UltraLink

Lindab Ultra BT™ Room Control System (Installation of wireless sensors)

The Ultra BT system revolutionizes demand controlled ventilation at room level. It offers a 360-degree upgrade with integrated Bluetooth Technology, improving cost-efficiency, installation simplicity, and daily operations for optimal indoor climate.

Additional heating and cooling via analog signal

Control heating and cooling sources using UltraLink and temperature sensors. For more details on Ultra BT functionalities and commissioning, refer to the Lindab Ultra BT™ Commissioning instruction, accessible via QR code or link.

Diagram illustrating the setup for demand controlled room regulation with UltraLink and wireless sensors, showing sensors, FTCU, and radiator.

Display

The display provides useful information via a green status light and parameters shown on the LCD. A blue light indicates Bluetooth status: flashing every three seconds when standby, and every second when a device is connected. Short pressing the Mode button cycles through displayed parameters. A long press (over 5 seconds) accesses the configuration menu. Arrows at the bottom of the display indicate the current parameter type and unit.

Parameter structure

The information menu appears upon powering up, defaulting to airflow in m³/h. Parameters can be toggled using the Mode button. The available parameters include:

  • Actual air flow (m³/h, l/s)
  • Actual air velocity (m/s)
  • Actual Temperature (°C)
  • Damper position (%, 100% = fully open)
  • Current set point (m³/h, l/s, m/s)
  • FTCU ID number
  • Flow rate set point max/min (visible only with analog control and flow rate as control variable)

Status light

Green status light:

  • No light: FTCU is turned off.
  • Flashing every 3 seconds: Motor is regulating to reach set point.
  • Flashing every 1 second: A problem has occurred; error code will be visible in the display.
  • Constant light: FTCU is turned on and functioning normally.

Blue status light:

  • No light: Bluetooth is turned off or the FTCU is not equipped with it.
  • Flashing every 3 seconds: Bluetooth is on standby and ready to connect to a mobile device.
  • Flashing every 1 second: A mobile device has been connected to the FTCU.
Illustration of the FTCU display showing status and airflow readings.

Correcting flow measurement for installation close to disturbance

If installation near a disturbance is necessary, corrections are made via the OneLink app. Connect to the UltraLink, navigate to "Configuration" > "Device settings", and click "Disturbance settings". Input the type of disturbance and the distance to it. The app will then automatically correct the flow measurement.

ID-numbers

Each FTCU has a unique ID-number (1-239) based on the last three digits of its serial number, found on the product label and packaging. If multiple Modbus devices share an ID, it must be changed to ensure unique identification for communication. Disconnect other devices with the same ID before changing it via the display's "Con. Set" menu (page 15) or the OneLink app. The Modbus ID register is 4x001.

PIN code

UltraLink with Bluetooth requires a PIN code for access and settings changes. The default PIN is 1111. It is crucial to change this to prevent unauthorized access. The Bluetooth radio can be disabled by setting register 4x007 to 0. The PIN can be changed via the "OneLink" application or the display's configuration menu.

Settings for override

The FTCU offers two override functions: via bus or analog input (for 2-10V or 10-2V signals). Bus control (register 4x071=0) allows forcing the damper to fully open/closed or setting flow rate to minimum/maximum (registers 4x315, 4x316). Analog control (register 4x071=1) allows forcing the damper to fully closed, irrespective of the minimum angle setting.

Override function by bus

  1. Normal mode: register 4x151 = 0.
  2. Maximum flow rate setpoint: register 4x151 = 1.
  3. Minimum flow rate setpoint: register 4x151 = 2.
  4. Fully open damper position: register 4x151 = 3.
  5. Fully closed damper position: register 4x151 = 4.

Overrides can be restored manually (register 4x151=0) or automatically after a timeout (register 4x150).

Analog override function

In analog mode (4x071=1), override is active if the input voltage range is 2-10V or 10-2V (4x500=2 or 3) and the control variable is flow rate (4x070=2). Override functions are: 1. Normal mode (input voltage ≥ 2 V). 2. Fully closed damper position (if input voltage is lower than register 4x511).

Firmware update

Regular firmware updates ensure optimal performance and the latest features. To update, open the OneLink app, log in, go to "Configuration" > "Device info", and click "Firmware update".

Maintenance

The FTCU requires minimal maintenance. Visible parts can be wiped with a damp cloth.

Configuration menu structure

Settings can also be adjusted via the OneLink app. The configuration menu is accessed by long-pressing the button (5 sec). Options include:

  • Con.Set (Connection settings)
  • Aln.Set (Analog In settings)
  • Cancel (Return to information menu)

Toggle between options with a short press; long press to select. Within Con.Set, options include Protocol (Pr.), Baud rate (b.), Stop bits (bit.), Parity (P.), Modbus ID (Id.), PLA address (PLA.), ELA address (ELA.), Pin-code (Pi.), and Control by bus (Cnt.). Use "Store" to save changes and "Cancel" to exit without saving.

Within Aln.Set, options include Max flow (qH.), Min flow (qL.), and Voltage range (r.).

Digital communication settings

Registers 4x001-4x009 configure communication settings. Default settings are active upon initial contact. These include Modbus ID (last three digits of serial number), Baud rate (19200), Parity (Odd), and Stop bits (1). Changes to communication parameters require a power cycle.

Control settings

The FTCU can be controlled via analog or digital (Modbus) signals. Key registers include 4x070 for set point type (0=no control, 1=damper position, 2=flow rate) and 4x071 for Modbus control (0=bus, 1=analog). Set points are applied using registers 4x302 (damper position) and 4x314 (flow). Damper position limits are 0-100%. Flow limits have default values but can be adjusted via registers 4x315 and 4x316. Default maximum flow values ensure guaranteed accuracy.

Size Ø [mm] 4x314 Flow Set Point [l/s] 4x315 Flow Set Point Minimum [l/s] 4x316 Flow Set Point Maximum [l/s] 4x070 Damper Regulation Conf. 4x071 Damper Input Conf.
100 24 0 118 2 (Flow) 1 (Analog)
125 37 0 184
160 60 0 302
200 94 0 471
250 147 0 736
315 234 0 1169
400 377 0 1885
500 589 0 2945
630 935 0 4676

Refer to the appendix for Modbus register instructions. Settings can be changed via RS485 bus or the OneLink app.

Analog communication settings

Analog in settings via modbus

For analog communication (4x071=1), specify the operational voltage range and corresponding max/min values. Configure register 4x500 for analog input level (0-10V, 10-0V, 2-10V, or 10-2V). Configure registers 4x501-504 with max/min levels for the selected voltage range, depending on whether the device is controlled by angle (4x070=1) or flow (4x070=2). If set points are controlled via bus, this step can be skipped.

Size Ø [mm] 4x070 Damper Regulation Conf. 4x500 Analog In Level config 4x501 Angle Min [%] * 4x502 Angle Max [%] * 4x503 Flow Min [l/s] 4x504 Flow Max [l/s]
100 2 (Flow) 2 (2-10V) 0 100 0 55
125 0 100 0 86
160 0 100 0 141
200 0 100 0 220
250 0 100 0 344
315 0 100 0 546
400 0 100 0 880
500 0 100 0 1374
630 0 100 0 2182

* 0% means fully closed damper position and 100% means fully open damper position.

Analog out settings via modbus

Analog out is always active. Specify data for the two ports: Configure registers 4x401 and 4x431 for variables (0=Flow, 1=Temperature, 2=Damper position, 3=Cooling, 4=Heating). Configure registers 4x400 and 4x430 for analog out level (0-10V, 10-0V, 2-10V, 10-2V). Configure registers 4x401-409 and 4x431-439 with max/min levels for the selected voltage range and variable.

Analog Out 1 Default Values:

Size Ø [mm] 4x400 Level Conf. 4x401 Unit Conf. 4x402 Temp Min [°C] 4x403 Temp Max [°C] 4x404 Flow Min [l/s] 4x406 Flow Max [l/s] 4x408 Angle Min [%] * 4x409 Angle Max [%] *
100 2 (2-10V) 0 (Flow) 0 50 0 55 0 100
125 0 50 0 86 0 100
160 0 50 0 141 0 100
200 0 50 0 220 0 100
250 0 50 0 344 0 100
315 0 50 0 546 0 100
400 0 50 0 880 0 100
500 0 50 0 1374 0 100
630 0 50 0 2182 0 100

Analog Out 2 Default Values:

Size Ø [mm] 4x430 Level Config 4x431 Unit Conf. 4x432 Temp Min [°C] 4x433 Temp Max [°C] 4x434 Flow Min [l/s] 4x436 Flow Max [l/s] 4x438 Angle Min [%] * 4x439 Angle Max [%] *
100 2 (2-10V) 2 (Angle) 0 50 0 55 0 100
125 0 50 0 86 0 100
160 0 50 0 141 0 100
200 0 50 0 220 0 100
250 0 50 0 344 0 100
315 0 50 0 546 0 100
400 0 50 0 880 0 100
500 0 50 0 1374 0 100
630 0 50 0 2182 0 100

* 0% means fully closed damper position and 100% means fully open damper position.

Refer to the appendix for Modbus register instructions.

Troubleshooting

If digital communication fails, please verify the following before contacting support:

  • Check Baud rate, parity, and stop bit settings match between master and UltraLinks (configurable via OneLink app).
  • Ensure -A and +B connections are continuous and correctly wired across all devices.
  • Avoid "star connection" bus layouts.
  • Verify power supply cables are connected identically (G to G for 24V, G0 to G0 for GND) on all products and transformers.
  • The shield must be continuous along the bus and grounded only at the transformer and the last UltraLink.
  • Limit devices per bus to 30; use a repeater if necessary.
  • Bus length should not exceed 300 m; use a repeater for longer runs.
  • Test communication with a PC using a Configuration Tool and a biased RS485-USB converter.
  • Keep stub lengths (e.g., premounted cables) to a maximum of 20 meters for a 30-device bus.

If analog signals fails, make sure to doublecheck the following:

  • Measure voltage on the screw terminal; it should match the BMS controller's voltage.
  • If voltage is incorrect, check wire attachment to the UltraLink terminal. A loose connection may prevent signal pickup.

Problems accessing UltraLink via Bluetooth

  • Ensure the UltraLink has the Bluetooth logotype on its display lid.
  • Input the correct PIN code (default: 1111) to connect. Verify the PIN with an administrator if connection fails.

I cannot find the sensor model I'm trying to pair

Ensure you have the latest firmware installed on your UltraLink (see "Firmware update" on page 14).

Error codes

If an error occurs, the status light flashes, and an error code appears on the display. The table below lists common error codes, their problems, and solutions.

Error code Problem Comment
Err001 Motor not working correctly Check motor cables and connections.
Err002 Angle sensor not working correctly Try to recalibrate using OneLink app.
Err003 Flow set point not reached Check if the AHU is supplying enough air.
Err004 Problems with flow measurement Might be caused by: something blocking flow sensors, an electronic fault, improper sensor connection, a flawed sensor body, or duct system design causing turbulence/disturbance.
Err05 External sensor low battery -
Err06 External sensor not reporting -

Cloud-Based Troubleshooting Support

Lindab offers cloud service for uploading OneLink data to assist with resolving issues. Contact your local Technical Support Team for this service.

Technical data

Technical data table

Parameter Value
Power supply AC/DC 24 (19-28) V
Cable grommet 7 mm
Cable (Bus recommended) RS485 standard cable, 2-wire shielded twisted pair, 0.25 mm² (LIYCY cable)
Power consumption (Dim. 100-315) 2 W / 3 VA
Power consumption (Dim. 400-630) 3 W / 5 VA
Premounted cable Length 0.7 m
Degree of protection IP44
Tightness class to environment (EN 12237) D
Tightness class (EN 1751) ATC 2
Tightness class, past closed damper 4
Pressure class, p closed damper (Dim. 100-315) C (max 5000 Pa)
Pressure class, p closed damper (Dim. 400-630) B (max 2500 Pa)
Storage temperature range -30 to +50 °C
Maximum ambient moisture 95 % RH
Connection Protocol RS485 standard or analog / Modbus
Output Flow, Velocity, Temperature, Damper position (0% fully closed, 100% fully open)
Velocity range 0.2 - 15.0 m/s
Measurement uncertainty flow (assuming correct installation) ±5 % or ±1.00 l/s (for Dim. 100), up to ±6.30 l/s (for Dim. 630)
Operating temperature range -10 to +50 °C
Measurement uncertainty, temperature ±1 °C
Bluetooth radio Frequency 2402-2480 MHz
Bluetooth range (free line of sight) -40 to +9 dB
Firmware UltraLink, Upgradable for optimal performance and new features

Airflows

Ø [mm] 0.2 m/s 7.0 m/s 15.0 m/s
m³/h l/s m³/h l/s m³/h l/s
100 6 2 198 55 425 118
125 9 3 309 86 662 184
160 14 4 507 141 1087 302
200 23 6 792 220 1696 471
250 35 10 1237 344 2650 736
315 56 16 1964 546 4208 1169
400 90 25 3167 880 6786 1885
500 141 39 4948 1374 10603 2945
630 224 62 7855 2182 16833 4676

Appendix A – Modbus register

This appendix details the Modbus registers available for the UltraLink. Each entry includes Address, FTCU/FTMU availability, Name, Description, Data type, Unit, Div (scale factor), Default value, Min/Max allowed values, and Access (Read Only/Read Write).

INPUT REGISTERS

Address FTCU FTMU Name Description Data type Unit Div Default Min Max Access
3x008 X X Product Nominal Size Nominal diameter of duct 16bit mm - - - - RO
3x013 X X Unit Status Current unit status: 0 = Normal mode; 1 = Locating flow; 2 = Override control; 3 = Error; 4 = Control loop regulating; 5 = Angle sensor calibrating 16bit - - - - RO
3x150 X X Flow info Velocity in m/s Float m/s - - - - RO
3x152 X X Air flow in m³/h Air flow in m³/h Float m³/h - - - - RO
3x154 X X Air flow in l/s Air flow in l/s Float l/s - - - - RO
3x200 X X Temperature info Current temperature in °C 16bit °C 10 - - - RO

Damper info

Address FTCU FTMU Name Description Data type Unit Div Default Min Max Access
3x251 X Damper open in % Damper actual position in percentage open. 16bit % 10 - - - RO
3x252 X Damper motor action Damper motor action: 0 = Motor stopped; 1 = Motor opening damper; 2 = Motor closing damper 16bit - - - - RO

Alarms

Address FTCU FTMU Name Description Data type Unit Div Default Min Max Access
3x400 X X Alarm Register 1 Alarms 1-32 - bitwise: 1 = Motor not working; 2 = Angle sensor not working correctly; 3 = Flow setpoint not reached; 4 = Flow measure problems; 5 = External sensor low battery; 6 = External sensor not responding; 7-31 = Reserved for future use; 32 = Factory data is corrupted. 32bit - - - - RO

Other

Address FTCU FTMU Name Description Data type Unit Div Default Min Max Access
3x500 X X Signal amplification Current signal amplification 16bit - 100 3 20 RO

Sensor

Address FTCU FTMU Name Description Data type Unit Div Default Min Max Access
3x2001 X X Sensor Global Set Point Factor Multiplication factor for flow set point 16bit - 100 100 - - RO
3x2002 X X Sensor Global Factored Set Point Holding register FLOW_SET_POINT (314) multiplied with SENSOR_GLOBAL_SET_POINT_FACTOR 16bit l/s - - - - RO
3x2007 X X Sensor Global State for Control Current state of control: 0 = Off; 1 = Unoccupied; 2 = Normal; 3 = Forced; 4 = Delayed presence; 5 = Temperature increase; 6 = Temperature decrease; 7 = CO₂ decrease; 8 = Humidity increase; 9 = Humidity decrease; 10 = VOC decrease; 11 = Particles decrease; 50 = Flow slave; 100 = Clearing error; 101 = Error C1; 102 = Error C2; 103 = Error C3; 104 = Error C4; 105 = Error C5; 106 = Error C6 16bit - - - - RO
3x2012 X X Sensor Com Current Presence Sum Current Presence based on sum from all sensors 16bit - - - - RO
3x2014 X X Sensor Com Presence State 0 = Disabled; 1 = Unoccupied; 2 = Normal; 3 = Forced; 4 = Delayed presence; 5 = Error 16bit - - - - RO
3x2021 X X Sensor Com Min. Temp Minimum Temperature 16bit °C 10 - - - RO
3x2022 X X Sensor Com Max. Temp Maximum Temperature 16bit °C 10 - - - RO
3x2023 X X Sensor Com Average Temp Average Temperature 16bit °C 10 - - - RO
3x2025 X X Sensor Com Temp State 0 = Disabled; 1 = Within deadband; 2 = Outside deadband; 3 = Error 16bit - - - - RO
3x2034 X X Sensor Com Summed Flow Summed Flow 16bit l/s - - - - RO
3x2036 X X Sensor Com Flow State 0 = Disabled; 1 = Within deadband; 2 = Outside deadband; 3 = Error 16bit - - - - RO
3x2041 X X Sensor Com Min. Humidity Minimum Humidity 16bit % RH 10 - - - RO
3x2042 X X Sensor Com Max. Humidity Maximum Humidity 16bit % RH 10 - - - RO
3x2043 X X Sensor Com Average Humidity Average Humidity 16bit % RH 10 - - - RO
3x2045 X X Sensor Com Humidity State 0 = Disabled; 1 = Within deadband; 2 = Outside deadband; 3 = Error 16bit - - - - RO
3x2051 X X Sensor Com Minimum CO₂ Minimum CO₂ 16bit ppm - - - - RO
3x2052 X X Sensor Com Maximum CO₂ Maximum CO₂ 16bit ppm - - - - RO
3x2053 X X Sensor Com Average CO₂ Average CO₂ 16bit ppm - - - - RO
3x2055 X X Sensor Com CO₂ State 0 = Disabled; 1 = Within deadband; 2 = Outside deadband; 3 = Error 16bit - - - - RO
3x2103 X X Sensor 1 Battery Level Sensor 1 battery level 16bit % - - - - RO
3x2104 X X Sensor 1 RSSI Sensor 1 RSSI 16bit % - - - - RO
3x2107 X X Sensor 1 Current Presence Sensor 1 Current Presence 16bit - - - - RO
3x2108 X X Sensor 1 Temperature Sensor 1 Temperature 16bit °C 10 - - - RO
3x2109 X X Sensor 1 Flow Sensor 1 Flow 16bit l/s 10 - - - RO
3x2110 X X Sensor 1 Humidity Sensor 1 Humidity 16bit % RH 10 - - - RO
3x2111 X X Sensor 1 CO₂ Sensor 1 CO₂ 16bit ppm - - - - RO
3x2123 X X Sensor 2 Battery Level Sensor 2 battery level 16bit % - - - - RO
3x2124 X X Sensor 2 RSSI Sensor 2 RSSI 16bit % - - - - RO
3x2127 X X Sensor 2 Current Presence Sensor 2 Current Presence 16bit - - - - RO
3x2128 X X Sensor 2 Temperature Sensor 2 Temperature 16bit °C 10 - - - RO
3x2129 X X Sensor 2 Flow Sensor 2 Flow 16bit l/s 10 - - - RO
3x2130 X X Sensor 2 Humidity Sensor 2 Humidity 16bit % RH 10 - - - RO
3x2131 X X Sensor 2 CO₂ Sensor 2 CO₂ 16bit ppm - - - - RO
3x2143 X X Sensor 3 Battery Level Sensor 3 battery level 16bit % - - - - RO
3x2144 X X Sensor 3 RSSI Sensor 3 RSSI 16bit % - - - - RO
3x2147 X X Sensor 3 Current Presence Sensor 3 Current Presence 16bit - - - - RO
3x2148 X X Sensor 3 Temperature Sensor 3 Temperature 16bit °C 10 - - - RO
3x2149 X X Sensor 3 Flow Sensor 3 Flow 16bit l/s 10 - - - RO
3x2150 X X Sensor 3 Humidity Sensor 3 Humidity 16bit % RH 10 - - - RO
3x2151 X X Sensor 3 CO₂ Sensor 3 CO₂ 16bit ppm - - - - RO
3x2163 X X Sensor 4 Battery Level Sensor 4 battery level 16bit % - - - - RO
3x2164 X X Sensor 4 RSSI Sensor 4 RSSI 16bit % - - - - RO
3x2167 X X Sensor 4 Current Presence Sensor 4 Current Presence 16bit - - - - RO
3x2168 X X Sensor 4 Temperature Sensor 4 Temperature 16bit °C 10 - - - RO
3x2169 X X Sensor 4 Flow Sensor 4 Flow 16bit l/s 10 - - - RO
3x2170 X X Sensor 4 Humidity Sensor 4 Humidity 16bit % RH 10 - - - RO
3x2171 X X Sensor 4 CO₂ Sensor 4 CO₂ 16bit ppm - - - - RO
3x2183 X X Sensor 5 Battery Level Sensor 5 battery level 16bit % - - - - RO
3x2184 X X Sensor 5 RSSI Sensor 5 RSSI 16bit % - - - - RO

HOLDING REGISTERS

Communication settings
Address FTCU FTMU Name Description Data type Unit Div Default Min Max Access
4x001 X X Communication id Modbus address 16bit - 1 1 239 RW
4x002 X X RS485 Baud Rate Conf. Baudrate: 0 = 9600; 1 = 19200; 2 = 38400; 3 = 76800 16bit - 1 0 3 RW
4x003 X X RS485 Parity Conf. Parity: 0 = Odd; 1 = Even; 2 = None 16bit - 1 0 2 RW
4x004 X X RS485 Stop Bit Conf. Number of stopbits: 1 or 2. 16bit - 1 1 2 RW
4x005 X X RS485 Protocol Conf. Protocol: 0 = Modbus; 1 = Not used; 2 = Pascal; 16bit - 1 0 2 RW
4x006 X X Bluetooth Password Password required for pairing Bluetooth devices. Can be changed via wired connection or current password via wireless. 16bit - 1111 0000 9999 RW
4x007 X X Bluetooth Enable Enable Bluetooth Communication: 0 = Off; 1 = On; 16bit - 1 0 2 RW
4x008 X X PLA ID used for Pascal 16bit - 1 1 239 RW
4x009 X X ELA ID used for Pascal 16bit - 1 1 239 RW
4x010 X X Bluetooth TX Power Level Configure TX Power Level in dBm. Accepted values: -40, -20, -16, -12, -8, -4, 0, 2, 3, 4, 5, 6, 7, 8, 9 16bit - 0 -40 9 RW
System configuration
Address FTCU FTMU Name Description Data type Unit Div Default Min Max Access
4x070 X Damper Regulation Conf. Specifies how damper is regulated: 0 = Regulator turned off; 1 = Regulate damper angle; 2 = Regulate flow 16bit - 2 0 2 RW
4x071 X Damper Input Conf. Specifies input to control damper: 0 = Modbus or Pascal; 1 = Analog input 16bit - 1 0 1 RW
4x072 X X Installation as Extract or Supply Specifies if device is in supply or extract: 0 = Undefined; 1 = Supply; 2 = Extract 16bit - 0 0 2 RW
4x073 X X Installation Zone Number Specifies in which zone the product is installed in 16 bit - 0 0 65535 RW
4x074 X X Installation Floor Number Specifies on which floor the product is installed in 16bit - 0 0 65535 RW
4x082 X X Execute Factory Reset Factory reset of all parameters. Unit will restart: 0 = Do nothing; 1 = Factory Reset 16bit - 0 0 1 RW
4x083 X X Execute Reboot Reboot the unit: 0 = Do nothing; 1 = Reboot the unit; 16bit - 0 0 1 RW
Override configuration
Address FTCU FTMU Name Description Data type Unit Div Default Min Max Access
4x150 X Damper Override Timeout Time before returning to normal mode 16bit min 120 0 600 RW
4x151 X Damper Override Conf. 0 = Normal mode; 1 = Override control - Max open; 2 = Override control - Min open; 3 = Override control - 100% open; 4 = Override control - 100% closed 16bit - 0 0 4 RW

Damper

Address FTCU FTMU Name Description Data type Unit Div Default Min Max Access
4x300 X Execute Angle Calibration 0 = Do nothing; 1 = Start recalibration of the angle sensor; 2 = Start recalibration when starting up; 16bit - 0 0 2 RW
4x302 X Angle Set Point Angle setpoint used in normal mode. (Only relevant when 4x070 is set to 1) 16bit % - 0 0 100 RW
4x314 X Flow Set Point Flow setpoint used in normal mode. (Only relevant when 4x070 is set to 2) 16bit l/s * - 0 4700 RW
4x315 X Flow Set Point Minimum Flow setpoint min. 16bit l/s * - 0 4700 RW
4x316 X Flow Set Point Maximum Flow setpoint max. 16bit l/s * - 0 4700 RW

Analog output

Address FTCU FTMU Name Description Data type Unit Div Default Min Max Access
4x400 X X Analog Output 1 Level Conf. Analog output config: 0 = 0-10 V; 1 = 10-0 V; 2 = 2-10 V; 3 = 10-2 V. 16bit - 2 0 3 RW
4x401 X X Analog Output 1 Unit Conf. Show: 0 = Flow; 1 = Temperature; 2 = Angle; 16bit - 0 0 2 RW
4x402 X X Analog Output 1 Temp. Min. Min temperature shown = Min output voltage (Only relevant when 4x401 is set to 1) 16bit °C - 0 -40 50 RW
4x403 X X Analog Output 1 Temp. Max. Max temperature shown = Max output voltage (Only relevant when 4x401 is set to 1) 16bit °C - 50 -40 50 RW
4x404 X X Analog Output 1 Flow Min. Min flow shown = Min output voltage (Only relevant when 4x401 is set to 0) 16bit l/s - 0 -4700 4700 RW
4x406 X X Analog Output 1 Flow Max. Max flow shown = Max output voltage (Only relevant when 4x401 is set to 0) 16bit l/s * - -4700 4700 RW
4x408 X Analog Output 1 % Open Min. Min open % shown = Min output voltage (Only relevant when 4x401 is set to 2) 16bit % - 10 0 1000 RW
4x409 X Analog Output 1 % Open Max. Max open % shown = Max output voltage (Only relevant when 4x401 is set to 2) 16bit % - 10 1000 0 1000 RW
4x430 X X Analog Output 2 Level Conf. Analog output config: 0 = 0-10 V; 1 = 10-0 V; 2 = 2-10 V; 3 = 10-2 V. 16bit - 2 0 3 RW
4x431 X X Analog Output 2 Unit Conf. Show: 0 = Flow; 1 = Temperature; 2 = Angle; 16bit - 2 0 2 RW
4x432 X X Analog Output 2 Temp. Min. Min temperature shown = Min output voltage (Only relevant when 4x431 is set to 1) 16bit °C - 0 -40 50 RW
4x433 X X Analog Output 2 Temp. Max. Max temperature shown = Max output voltage (Only relevant when 4x431 is set to 1) 16bit °C - 50 -40 50 RW
4x434 X X Analog Output 2 Flow Min. Min flow shown = Min output voltage (Only relevant when 4x431 is set to 0) 16bit l/s - 0 -4700 4700 RW
4x436 X X Analog Output 2 Flow Max. Max flow shown = Max output voltage (Only relevant when 4x431 is set to 0) 16bit l/s * - -4700 4700 RW
4x438 X Analog Output 2 % Open Min. Min open % shown = Min output voltage (Only relevant when 4x431 is set to 2) 16bit % - 10 0 1000 RW
4x439 X Analog Output 2 % Open Max. Max open % shown = Max output voltage (Only relevant when 4x431 is set to 2) 16bit % * 10 1000 0 1000 RW

* 0% means fully closed damper position and 100% means fully open damper position.

Analog input settings via modbus

For analog input settings (relevant when register 4x071 is set to 1): Configure 4x500 for analog input level (0-10V, 10-0V, 2-10V, 10-2V). Configure registers 4x501-504 for max/min levels based on the selected voltage range and control variable (angle or flow). If set points are controlled via bus, these settings can be skipped.

Address FTCU FTMU Name Description Data type Unit Div Default Min Max Access
4x500 X Analog In Level Conf. Analog input: 0 = 0-10 V; 1 = 10-0 V; 2 = 2-10 V; 3 = 10-2 V. 16bit - 2 0 3 RW
4x501 X Analog In Angle Minimum Min angle = min voltage 16bit % - 0 0 100 RW
4x502 X Analog In Angle Maximum Max = max voltage 16bit % - 100 0 100 RW
4x503 X Analog In Flow Minimum Min flow = min voltage (Must be equal or higher than register 4x315) 16bit l/s - 0 0 4700 RW
4x504 X Analog In Flow Maximum Max flow = max voltage (Must be equal or lower than register 4x316) 16bit l/s * - 0 4700 RW
4x510 X Analog In Override Low Trigger Min. Lowest voltage level to activate 1st Override level (Only relevant when 4x500 is set to 2 or 3) 16bit V - 10 0 20 RW
4x511 X Analog In Override Low Trigger Max. Highest voltage level to activate 1st Override level (Only relevant when 4x500 is set to 2 or 3) 16bit V - 10 8 20 RW

Sensor

Address FTCU FTMU Name Description Data type Unit Div Default Min Max Access
4x2100 X X Sensor Presence Enable Control 0 = Disable; 1 = Enable 16bit - - 0 1 RW
4x2101 X X Sensor Presence Trigger Time Temporary trigger time for presence 16bit min - 1 0 60 RW
4x2102 X X Sensor Presence Trigger Factor Factor related to toggle 0 -> 1 16bit % - 100 49 501 RW
4x2103 X X Sensor Unoccupied Multiplication Factor Multiplication factor for Unoccupied 16bit % - 100 50 501 RW
4x2104 X Sensor Presence Economy Mode 0 = Comfort / 1 = Economy 16bit - 1 0 1 RW
4x2110 X X Sensor Temperature Enable Control 0 = Disable; 1 = max; 2 = min; 3 = avg 16bit - 0 0 3 RW
4x2111 X X Sensor Temperature Baseline Baseline for temperature 16bit °C - 22 -50 50 RW
4x2112 X X Sensor Temperature Deviation Allowed deviation before full factor effect 16bit °C - 2 0 50 RW
4x2113 X X Sensor Temperature Dead Band Dead band for sensor type Temperature 16bit % - 100 50 101 RW
4x2114 X X Sensor Temperature Multiplication Factor Multiplication factor for Temperature 16bit % - 100 150 501 RW
4x2115 X Sensor Temperature Baseline Minimum Lower limit for baseline setting 16bit °C - 20 0 50 RW
4x2116 X Sensor Temperature Baseline Maximum Upper limit for baseline setting 16bit °C - 25 0 50 RW
4x2117 X Sensor Temperature Difference Minimum temperature difference before regulating 16bit °C - 1 0 5 RW
4x2120 X X Sensor Flow Enable Control 0 = Disable; 1 = Sum 16bit - - 0 1 RW
4x2121 X X Sensor Flow Dead Band Dead band for sensor type Flow 16bit % - 100 2 100 RW
4x2122 X X Sensor Flow Multiplication Factor Multiplication factor for Flow 16bit % - 100 0 500 RW
4x2123 X Sensor Flow Offset Offset for Flow regulation 16bit l/s - 0 -5000 5000 RW
4x2124 X Sensor Flow Set Point Source "0 = Use summed flow as set-point; 1 = Use current set-point reduced with summed flow; 2 = Use current set-point added with summed flow" 16bit - - 0 2 RW
4x2130 X X Sensor Humidity Enable Control 0 = Disable; 1 = max; 2 = min; 3 =avg 16bit - 0 0 3 RW
4x2131 X X Sensor Humidity Baseline Baseline for humidity 16bit % - 50 0 100 RW
4x2132 X X Sensor Humidity Deviation Allowed deviation before full factor effect 16bit % - 20 0 100 RW
4x2133 X X Sensor Humidity Dead Band Dead band for sensor type Humidity 16bit % - 100 50 101 RW
4x2134 X X Sensor Humidity Multiplication Factor Multiplication factor for Humidity 16bit % - 100 150 501 RW
4x2135 X X Sensor Humidity Supplied Estimated value of supply air humidity 16bit % - 50 0 100 RW
4x2136 X Sensor Humidity Baseline Minimum Lower limit for baseline setting 16bit % - 30 0 100 RW
4x2137 X Sensor Humididty Baseline Maximum Upper limit for baseline setting 16bit % - 70 0 100 RW
4x2138 X Sensor Humidity Difference Minimum humidity difference before regulating 16bit % - 10 0 100 RW
4x2140 X X Sensor CO₂ Enable Control 0 = Disable; 1 = max; 2 = min; 3 =avg 16bit - - 0 3 RW
4x2141 X X Sensor CO₂ Baseline Baseline for CO₂ 16bit ppm - 600 400 2000 RW
4x2142 X X Sensor CO₂ Deviation Allowed deviation before full factor effect 16bit ppm - 400 0 1000 RW
4x2143 X X Sensor CO₂ Dead Band Dead band for sensor type CO₂ 16bit % - 100 50 101 RW
4x2144 X X Sensor CO₂ Multiplication Factor Multiplication factor for CO₂ 16bit % - 100 150 501 RW
4x2145 X X Sensor CO₂ Supplied Estimated value of supply air CO₂ 16bit ppm - 400 300 2000 RW
4x2146 X Sensor CO₂ Baseline Minimum Lower limit for baseline setting 16bit ppm - 400 0 2000 RW
4x2147 X Sensor CO₂ Baseline Maximum Upper limit for baseline setting 16bit ppm - 800 0 2000 RW
4x2148 X Sensor CO₂ Difference Minimum CO₂ difference before regulating 16bit ppm - 50 0 500 RW

About Lindab

Most of us spend the majority of our time indoors. Indoor climate is crucial to how we feel, how productive we are and if we stay healthy.

Lindab's objective is to contribute to an indoor climate that improves people's lives by developing energy-efficient ventilation solutions and durable building products. Lindab also aims to contribute to a better climate for our planet by working sustainably for both people and the environment.

Lindab | For a better climate

Models: 100, 315, 400, 630, 100 Ultra Link Ftcu, 100, Ultra Link Ftcu, Link Ftcu, Ftcu

File Info : application/pdf, 28 Pages, 5.97MB

PDF preview unavailable. Download the PDF instead.

Technical-FTCU4 heating and cooling ?t=501554531

References

Adobe PDF Library 17.0 Adobe InDesign 19.5 (Windows)

Related Documents

Preview Lindab UltraLink® FTCU Controller: Technical Data and Specifications
Discover the Lindab UltraLink® FTCU Controller for precise air flow and temperature management. This document details its technical specifications, dimensions, Modbus/Bluetooth connectivity, performance graphs, and features for HVAC applications.
Preview Lindab Ultra BT™ Room Control System Commissioning Instruction
This document provides a comprehensive guide for commissioning the Lindab Ultra BT™ Room Control System, detailing setup, sensor pairing, room regulation configuration, and end-user app integration using the OneLink and OneSet apps.
Preview Lindab AL Grilles Global Version - Technical Data and Specifications
Comprehensive technical documentation for Lindab's AL Grilles, Global version. Covers product description, dimensions, frame and grid options, installation methods, accessories, materials, and performance data for supply and extract air applications. Features include quick selection tables and technical diagrams.
Preview Lindab DAU, DA2EU, DAVU Constant-/Variable Flow Dampers - Technical Data
Comprehensive technical specifications for Lindab's DAU, DA2EU, and DAVU series of constant and variable flow dampers, covering dimensions, performance characteristics, and acoustic data for ventilation systems.
Preview Lindab Atrium Loggia / -H / -C Heating and Cooling Panels | Installation & Overview
Comprehensive guide to Lindab Atrium Loggia / -H / -C heating and cooling panels, covering delivery control, mounting options, water connections, and false ceiling integration. Learn about Lindab's energy-efficient HVAC solutions for improved indoor climate.
Preview Lindab LTDP/LTDP(F) Slotdiffuser/Panel Installation Guide
Comprehensive installation guide for Lindab LTDP and LTDP(F) slotdiffusers and panels, covering dimensions, symbols, mounting methods, and maintenance.
Preview Lindab OLC Overflow Unit - Installation Guide
Comprehensive installation instructions for the Lindab OLC overflow unit, including dimensions, accessories, and step-by-step mounting guidance for OLC and OLCZ models.
Preview Lindab Ventilation Grill F50/51: Environmental Product Declaration
Environmental Product Declaration (EPD) for Lindab's F50/51 ventilation grill, detailing its life cycle assessment, environmental impact data, and sustainability aspects according to EN 15804+A2 and ISO 14025.