Honeywell Sensepoint Pro
Comprehensive monitoring of flammable, toxic and oxygen gas hazards in potentially explosive atmospheres
The Sensepoint Pro
The Sensepoint Pro provides comprehensive monitoring of flammable, toxic and oxygen gas hazards in potentially explosive atmospheres, both in and out of doors. Users can modify detector operation using the remote control provided without ever needing to open the unit. This enables one man, non-intrusive, operation and reduces routine maintenance time and costs.
All detectors are supplied pre-configured and include two programmable alarm relays as well as an industry standard 4-20mA output. The scale, range, calibration, relay operation and alarm set points of the detector may all be adjusted via the transmitters' backlit LCD and an intrinsically safe remote control that is also suitable for use in potentially explosive atmospheres. Outputs are automatically inhibited during adjustment thereby reducing the risk of false alarm at the control panel during maintenance.
Sensepoint Pro is supplied with all necessary accessories for easy installation. The detector can be mounted on a wall or round support pole using the universal bracket provided. The detector is ideal for use with either conduit or steel wire armored cable and glands. A 3/4"NPT entry and M20 adaptor are included as standard. A weatherproof cap is also included for use in the harshest outdoor conditions.
Overall, the Sensepoint Pro ensures easy installation and the fastest routine operation by removing the need for hot work permits in hazardous areas. Using an easy to replace plug-in sensor, downtime is also reduced and on-going costs are minimized through the use of poison resistant flammable sensors and patented Surecell™ toxic sensor technology.
Sensepoint Pro meets the more demanding user requirements but assures you of the most cost effective solution to your gas detection needs in the long run.
firealarmresources.com
Key Features
One-Stop Shop
- Flammable, toxic and oxygen versions available
- Suitable for indoor or outdoor use
- IP65 as standard
Proven Sensor Technology
- Surecell™ electrochemical sensors
- Poison resistant catalytic bead
- Fast and reliable
- Typical 2 to 5 years operational life
Global Certifications*
- US, Canada and Europe
- Compliant with UL, CSA and ATEX standards
- Includes hazardous area AND performance approval
Convenient to Use
- Backlit LCD for dark environments
- Fully configurable via IR remote control
- 4-20mA and relay operation
- Auto-inhibit during maintenance
Cost Effective
- Minimal training required
- Non-intrusive, one-man operation
- Plug-in sensor replacement
- All necessary accessories included
Friendly Installation
- Universal mounting bracket
- 3/4" NPT and M20 entries included as standard
- Suitable for conduit or SWA cable/ glands installations
Range of Accessories
- Flow adaptor
- Duct mounting kit
- Collecting cone
*Pending - Contact Honeywell Analytics for more information
Installation Details
Sensepoint Pro is designed for use in potentially explosive atmospheres. As such, installation should follow national guidelines using suitably approved steel wire armored cable and glands (M20 or 3/4"NPT) or conduit (3/4"NPT).
Use 0.5mm² (20AWG) to 2.5mm² (14AWG) cross sectional area cable, as needed to ensure minimum operating voltage at the detector, depending upon installed cable length.
Various accessories are available for different applications.
Mounting Options
- Pole Mount
- Wall Mount
- Duct Mount
- Collecting Cone
Dimensions
Overall Height: 150.0mm / 5.9"
Width: 102.0mm / 4.0"
Depth: 36.0mm / 1.4"
Mounting Bracket Height: 20.0-80.0mm / 0.8"-3.2"
Electrical Connections
The detector uses a 3-wire system for 4-20mA output and relays. It features a terminal block for connections and an LCD unit connector.
firealarmresources.com
Technical Summary
General Specification
Use: 3 wire, 4-20mA, fixed point gas detector with built-in alarm relays for the protection of personnel and plant from flammable, toxic and oxygen gas hazards. Incorporating transmitter with local display and fully configurable via remote handheld control.
Detectable Gases
Ident | Name | Measuring Range 1 | Measuring Range 2 | Measuring Range 3 | Operating Temperature Min | Operating Temperature Max |
---|---|---|---|---|---|---|
F | Flammable | 0-100% LEL | -20°C/-4°F | 50°C/122°F | ||
O | Oxygen | 0-25% VOL | -15°C/5°F | 40°C/104°F | ||
C | Carbon Monoxide* | 0-200ppm | 0-500ppm | -20°C/-4°F | 50°C/122°F | |
H | Hydrogen Sulfide* | 0-50ppm | 0-20ppm | 0-100ppm | -20°C/-4°F | 50°C/122°F |
G | Hydrogen | 0-1000ppm | -5°C/23°F | 40°C/104°F |
*Surecell™ Sensor Technology
#Standard range
*Check certified temperature
Electrical
General: 3 wire connection, 12-30Vdc, 4-20mA (source), common 0Vdc. 7 x screw terminals for 0.5mm² (20AWG) to 2.5mm² (14AWG) wire. Maximum operating current: 300mA (flammable), 150mA (toxic and oxygen). Maximum peak in rush current: 600mA.
Signal: Maximum over range: 22mA. Normal operation: 4-20mA. Output inhibited (2mA or 17.4mA for oxygen): 0mA. Fault: 0mA.
Alarm Relays
2 x 3A@240Vac alarm relays. User configurable alarm trip point, normally energized/de-energized operation. Link selectable output as NO or NC.
Construction
Material: Main body: Powder coated aluminum (ADC12). Sensor: 316 stainless steel. Weatherproof cap: Aluminum, 316 stainless steel mesh.
Weight: 1450g
Certification
Sensepoint Pro | Sensepoint Pro Remote Control ZHC1 | |
---|---|---|
ATEX | Ex II 2G EEx d IIC T4 (Tamb= -20°C to +50°C / -4°F to +122°F) | Ex II 2G EEx ib IIC T4 (Tamb= -20°C to +50°C / -4°F to +122°F) |
UL | Class 1, Div 1, Groups B, C, D (Tamb= -20°C to +50°C / -4°F to +122°F) | Class 1, Div 1, Groups A, B, C, D (Tamb= -20°C to +50°C / -4°F to +122°F) |
Applicable Standards
North America: UL1203. Europe: CE, ATEX, EMC (EN50270). Contact Honeywell Analytics for latest information.
Environmental
IP Rating: IP65 as standard in accordance with EN60529:1992.
Operating Temperature: Dependent upon gas type and certification.
Operating Humidity Range: Continuous: 20-90%RH (non condensing), Intermittent: 10-99%RH (non condensing).
Operating Pressure: 90-110kPa.
Storage Conditions: Instrument -40°C to +50°C (-40°F to +122°F).
* Oxygen detection products must only be used to detect oxygen depletion in air.
firealarmresources.com
Ordering Information
Example: SP PR U X F 1 A = SPPRUXF1A
STANDARDS | RANGE | GAS TYPE | ADD'L INFO |
---|---|---|---|
U: USA (UL) | 1: Refer to Table Above | F: Flammable | A: ATEX |
A: Europe (ATEX) | 2: Detectable Gases | O: Oxygen | |
3: | C: Carbon Monoxide | ||
H: Hydrogen Sulfide | |||
G: Hydrogen |
Standard Supply
Each detector is supplied complete with IS remote control, 3/4"NPT entry, 3/4"NPT to M20 adaptor, wall mounting bracket, pole mounting bracket, weatherproof cap, necessary Allen keys and instruction manual all sealed in a plastic bag inside a shipping carton.
Shipping Details
Shipping carton dimensions: L312mm (12.3") x W223mm (8.8") x D110mm (4.3"). Approximate weight: 1.5Kg (3.3lbs).
Optional Accessories
- SPPPCC Collecting cone
- SPPPCAL Flow adaptor
- SPPPDM Duct mounting kit
Calibration Equipment
Contact Honeywell Analytics Representative.
firealarmresources.com
The Zareba Range of Fixed Gas Detection
As world leaders in gas detection solutions, Honeywell Analytics' Zareba range of gas detection systems has been designed to provide efficient, practical and cost-effective equipment to protect people from a variety of forms of hazardous gas. The equipment is also simple to install and easy to operate and maintain.
Product Overview
- Sensepoint: Designed for industrial use, the Sensepoint range provides an easy way of ensuring legislative requirements are met.
- Sensepoint Plus: (Image description: A yellow gas detector unit with a clear display and sensor.)
- Sensepoint Pro: (Image description: A yellow gas detector unit with a clear display and sensor, similar to Sensepoint Plus but with additional features.)
- Touchpoint 1: (Image description: A compact, wall-mounted gas detection unit with a simple interface.)
- Touchpoint 4: (Image description: A multi-channel gas detection system with a digital display and controls.)
- Metro: (Image description: A small, circular sensor unit.)
- Metro controller: (Image description: A control unit for the Metro system, likely wall-mounted.)
- Unipoint: Unipoint is a simple DIN rail mounted controller offering integrators a flexible and low cost solution to incorporate flammable, toxic or oxygen gas detection into their control systems. From car parks and boiler houses to analyzer shelters or crane cabs in offshore facilities.
Find out more
Customer business centre
Europe and the rest of the world
Honeywell Analytics AG
Wilstrasse 11-U11
CH-8610 Uster
Switzerland
Tel: +41 (0)44 943 4300
Fax: +41 (0)44 943 4398
sales@zelana.co.uk
Americas
Honeywell Analytics Distribution, Inc.
400 Sawgrass Corporate Pkwy
Suite 100
Sunrise, FL 33325
USA
Tel: +1 954 514 2700
Toll free: +1 800 538 0363
Fax: +1 954 514 2784
sales@zelana.com
Please Note: While every effort has been made to ensure accuracy in this publication, no responsibility can be accepted for errors or omissions. Data may change, as well as legislation, and you are strongly advised to obtain copies of the most recently issued regulations, standards, and guidelines. This publication is not intended to form the basis of a contract. ©2005 Honeywell Analytics
H_Sensepoint Pro_DS0328_V1 12/05
Honeywell