Toshiba AS3 Application Note 2.9.1: Sleep Function (PID control)

How to program the drive to shut down under certain conditions to save energy in PID mode.

Estimated Time: 10-20 Minutes

Level: 3

Prerequisite:

STEP A: Theory of Operation

The sleep function on the AS3 is used for energy saving and extending the lifespan of the pump. This function puts the drive to sleep when there is no demand for mass flow, which would decrease the run time for the motor and prolong the lifespan.

The Sleep function will automatically decelerate and bring the drive to a stop when programmed conditions have been met.

The drive's Sleep function begins once the output frequency is at the programmed <LL: Lower Limit frequency>.

The drive will continue to run at the <LL: Lower Limit frequency> for the specified time in the <F256: Run Sleep detection time> parameter prior to the drive's sleep cycle.

Once the drive has met these conditions, the screen will display “LStP” while the drive is in “sleep” mode.

You can also enable a feature with the Sleep function that will automatically stop the drive after a time period programmed in <F259: Run Sleep detection time at start-up> if the output frequency does not increase past the <LL: Lower Limit frequency> due to load error at start-up.

The drive will begin to run after the sleep cycle based on the value set in <F393: Wakeup feedback>. This parameter is not based on time, it is based on the feedback value reaching the set value and it will begin to run immediately once the feedback has done so.

Note: Refer to Section 6.9 in the AS3 PID Control Instruction Manual E6582112 for additional information on the Sleep function.

STEP B: Explanation

The sleep function during operation is shown in the diagram below.

Diagram Description:

The top graph shows 'Output frequency' on the Y-axis and time on the X-axis. The output frequency starts above [LL] + [F398], then drops to [LL]. It stays at [LL] for a duration indicated by [F256], after which it enters sleep mode.

The bottom graph shows 'Feedback' on the Y-axis and time on the X-axis. The feedback starts high, then drops below [F393]. The AS3 wakes up when feedback reaches [F393], and the output frequency increases based on demand.

This diagram shows the output frequency falling below the <LL: Lower Limit frequency>. The output frequency would go into the sleep state after running for a duration based on <F256: Run Sleep detection time>. The second graph shows the time interval during the operation. The AS3 will wake up based on the <F393: Wakeup feedback> and the output frequency will increase based on the demand of your application.

Check Your Work

✔️ Check your understanding of the condition required to enable or disable the Sleep function.

STEP C: Programming

1. Program the Lower Limit Frequency. The lower limit frequency will determine the frequency at which the drive will go to sleep.

Parameter Description Default Value New Value
F013 LL: Lower Limit Frequency 0.0 Choose New LL Value

2. Program the Sleep detection time. The drive will need to run at the lower limit for the set period of time to go into a sleep state.

Parameter Description Default Value New Value
F256 Sleep Detection Time 0.0 Choose New Value

3. Program the Wakeup Feedback. This is the set value at which the drive will wake up from its sleep state.

Parameter Description Default Value New Value
F393 Wakeup Feedback 0.0 Choose New Value

4. (If applicable) Program the Run Sleep detection at start-up. This is the set time value at which the drive will go into a sleep state if the output frequency does not increase to the value of Lower Limit Frequency due to a load error.

Parameter Description Default Value New Value
F259 Run Sleep detection at start-up 0.0 Choose New Value

Check Your Work

✔️ Verify parameter change was made by verifying new value programmed.

✔️ Ensure the drive is properly programmed for PID, otherwise the drive will not go into a sleep state nor wake up from the sleep state correctly. Refer to the AS3 App Note 2.1.0 PID Setup for additional information.

Models: AS3 General Purpose Motors Drives, AS3, General Purpose Motors Drives, Purpose Motors Drives, Motors Drives, Drives

File Info : application/pdf, 3 Pages, 145.98KB

PDF preview unavailable. Download the PDF instead.

AS3 App Note 2.9.1 Sleep Function PID

References

Microsoft Publisher for Microsoft 365

Related Documents

Preview Toshiba AS3 Sleep Function (Non-PID Control): Programming and Operation Guide
Learn how to program and operate the Toshiba AS3 variable frequency drive's Sleep Function (Non-PID control) for energy saving and motor lifespan extension. This guide covers setup, parameters, and verification.
Preview Toshiba VFAS3 Sleep Function Programming Guide
This guide explains how to program and operate the Toshiba VFAS3 variable frequency drive's sleep function for energy saving and motor lifespan extension. It covers parameter settings, explanations, and verification steps.
Preview TOSVERT VF-AS3 PCL002Z Instruction Manual - Function Setting Tool
Comprehensive instruction manual for the TOSHIBA TOSVERT VF-AS3 inverter's PCL002Z function setting tool. Learn to export/import parameters, create logic sequences, monitor real-time data, and configure communication settings for optimal inverter operation.
Preview Toshiba S15 Application Note 2.1.1: PID Setup Guide
A comprehensive guide to setting up and running the PID control loop on the Toshiba S15 drive, covering connections, parameter configuration, and tuning for optimal process control.
Preview Toshiba AS3 Ethernet IP Basic Tutorial
A guide to connecting a Toshiba AS3 Variable Frequency Drive (VFD) to an Allen Bradley PLC using Ethernet IP for command and feedback. This tutorial covers IP address configuration, RSLogix 5000 project setup, and testing with controller tags.
Preview TOSVERT VF-AS3 Trace Tool PCT003Z-E Instruction Manual for Inverter Communication
This instruction manual provides comprehensive guidance for using the TOSVERT VF-AS3 Trace Tool PCT003Z-E software. Learn how to export/import parameters, read inverter information, display trace data graphically, and store trace data for TOSHIBA VF-AS3 inverters via RS-485 communication.
Preview Toshiba S15 Basic Preset Speed Control via Discrete Inputs
Learn how to control the Toshiba S15 variable frequency drive using discrete inputs for basic preset speed selection. This guide covers wiring, programming, and verification steps.
Preview Toshiba AS3 Ethernet IP Basic Tutorial: Connecting AS3 to PLC
Learn how to connect a Toshiba AS3 Adjustable Speed Drive (ASD) to a Programmable Logic Controller (PLC) over Ethernet/IP for command and feedback. This tutorial provides a basic setup guide for configuring static IP addresses, creating RSLogix 5000 projects, and testing controller tags for AS3 drives.