TOSVERT VF-AS3 Trace Tool PCT003Z-E Instruction Manual

E6582155

TOSHIBA INDUSTRIAL PRODUCTS AND SYSTEMS CORPORATION

NOTICE

  1. Read this manual before installing or operating. Keep this instruction manual on hand for the end user, and make use of this manual in maintenance and inspection.
  2. All information contained in this manual will be changed without notice. Please contact your Toshiba distributor to confirm the latest information.

1. Introduction

The trace tool PCT003Z-E for VF-AS3 is software that performs the following functions when used with an inverter connected to a computer via an RS-485 communications device. This manual should be read carefully along with the instruction manual for VF-AS3 before using PCT003Z-E to ensure correct operation.

  • Exporting and Importing trace function-related parameters
  • Reading information on the inverter
  • Reading trace data
  • Displaying read trace data in graphic form
  • Storing trace data

*1 PCT003Z-E does not support any inverters other than VF-AS3.

*2 To use PCT003Z-E, the USB converters unit shown in the connection example are required.

*3 PCT003Z-E uses the TOSHIBA inverter protocol. Therefore, set the TOSHIBA protocol (F807 = 0) or (F827=0) for the inverter's protocol selection.

Connection Example of USB Converters Unit

The connection involves:

  • USB converters unit (represented by a device labeled 'USB Option Unit' with RS485 and USB ports)
  • Inverter interconnect cable (connecting the inverter to the RS485 port of the USB Option Unit)
  • Computer interconnect cable (a standard USB A-B cable connecting the USB Option Unit to a laptop computer)

The USB communication conversion unit is Type-form: USB001Z (optional).

Inverter Interconnect Cable (optional)

Type-formCable length
CAB00111.2m
CAB00133.6m
CAB00154.8m

A commercially available USB cable (USB1.1/2.0-compliant) is required for the USB cable (A-B connection type). The recommended cable length is 1m.

System Requirements

A personal computer with Microsoft® Excel® installed is required. A USB port is necessary for the computer to connect to the inverter. It is recommended to use a mouse or a similar pointing device for operation.

*5 PCT003Z-E may not run normally on some types of PC-98 series computers.

*6 It has been confirmed that PCT003Z-E runs normally on the software listed below:

SoftwareCompatibility
Microsoft Excel English versionMS-Excel 2007 32bit

*7 Connect the optional USB communication converter before starting PCT003Z-E. Do not plug or unplug the connector when PCT003Z-E is running.

How to Install PCT003Z-E

To install PCT003Z-E, extract the zip file and move it into the desired folder. Take the following precautions when installing PCT003Z-E:

  • Exit running application programs.
  • When updating the latest PCT003Z-E, uninstall the old version of PCT003Z-E. (The version of PCT003Z-E is shown in the Opening window (section 2.3).)

How to Uninstall PCT003Z-E

To uninstall PCT003Z-E, remove the folder containing PCT003Z-E from the computer.

The specifications of this software are subject to change without notice.

Toshiba Schneider Inverter assumes no responsibility for damage caused directly or indirectly by the use or a malfunction of this software product.

These system requirements are minimum conditions required for the use of PCT003Z-E. They do not guarantee that all functions of PCT003Z-E are performed normally.

Windows® is listed as the abbreviation for a Microsoft® Windows® operating system. Microsoft® Windows® and Microsoft® Excel® are registered trademarks or trademarks of the US Microsoft Corporation in the USA and other countries.

PC-98 series is a trademark or registered trademark of NEC Corporation.

The symbols used in this manual have the following meanings:

  • [ ]: Buttons or radio buttons in windows of PCT003Z-E or Microsoft Windows
  • ': Menus items of PCT003Z-E

2. How to use PCT003Z-E

2.1. Enabling Macros

When PCT003Z-E is started for the first time, a dialog box (similar to a 'Security Alert - Macros & ActiveX' or 'Security Warning' message) may appear. If it appears, click the [Enable Macros] or [Enable Content] button, as PCT003Z-E uses macros. The security alert typically warns that active content might contain viruses or security hazards and advises enabling only if the source is trusted. The option to 'Enable this content' should be selected.

2.2. License Agreement

When PCT003Z-E is started for the first time or after macros have been enabled, the PCT003Z-E license agreement window appears. This window states: "We shall not be liable for any direct and indirect damages that are caused by use or disability to use of this software product." Read the contents carefully and click [I Agree] if you wish to use PCT003Z-E. Clicking [I Do Not Agree] closes the Excel book.

2.3. Opening Window

When macros are executed, the Opening sheet appears. This sheet displays "The Trace tool for VF-AS3 PCT003Z-E V100" and a note: "In order to have this tool used correctly, please read an 'instructions manual' (E6582155) well being used." After reading this manual carefully, click [To setting >] in the top-right of the window to make necessary settings. The Setting sheet is shown by clicking this button.

2.4. Setting Sheet

The Setting sheet allows for configuring communications between the inverter and the computer, and for exporting and importing related parameters.

Communication Setting

This section includes fields for COM Port, Baud rate (F800, F820), Parity (F801, F821), and Inverter number (F802). A 'Set value' column allows input, and a 'Present set value' column displays current settings.

Communication settingSet value
COM Port1
Baud rate (F800, F820)01 (19200 bps)
Parity (F801, F821)01 (Even parity)
Inverter number (F802)none
  • 'COM Port': Specify the COM port number of the computer.
  • 'Baud rate': Specify the baud rate (F800, F820) of the inverter.
  • 'Parity': Specify the parity (F801, F821) of the inverter.
  • 'Inverter number': Specify the number (F802) assigned to the inverter.

Communication can proceed by disregarding the inverter number when setting the Inverter number of PCT003Z-E to "none".

*1 If a parameter other than those set for the inverter or computer is selected, a communication error may occur.

*2 Set the parameters of the RS485 port (1 or 2) to be used.

Table of Settings for Communications with Inverter

TitleContentAdjustment rangeDefault setting
F800, F820Baud rate0:9600bps 1:19200bps 2:38400bps1
F801, F821Parity0:Non parity 1:Even parity 2:Odd parity1
F802Inverter number0~990

*2 Communication errors might occur depending on the setting of communication function parameters (F803-F808) other than those listed above. Refer to "TOSVERT VF-AS3 Detailed manual: E6582062" for details.

*3 Since PCT003Z-E uses the Toshiba inverter protocol ASCII mode, only a number between 0 and 99 can be assigned to an inverter.

Parameter Concerning Trace Function

This section allows setting trace parameters such as Trace selection (F740), Trace cycle (F741), and Trace data1 to 4 (F742 to F745). A 'Writing set value' column allows selection from dropdowns, and a 'Present set value' column displays current settings.

  • 'Trace selection(F740)': Selects the trace data acquisition timing (e.g., At tripping).
  • 'Trace cycle(F741)': Selects the trace cycle (e.g., 100ms).
  • 'Trace data1 to 4(F742 to F745)': Selects the type of data to trace (e.g., Output frequency (Hz), Frequency command value (Hz), Output current (%), Input voltage (DC detection) (%)).

*4 Set all trace-related parameters before operating the inverter. If these are changed after the inverter has tripped or triggered, that data cannot be read.

Table of Parameters Concerning Trace Functions

TitleContentAdjustment rangeDefault setting
F740Trace selection0:Deselect 1:At tripping 2:At triggering 3:1+21
F741Trace cycle0:4ms 1:20ms 2:100ms 3:1s 4:10s2
F742Trace data10-1620
F743Trace data20-1621
F744Trace data30-1622
F745Trace data40-1623

[F742] to [F745] Setting: Trace Data (Monitor Data) and Communication Unit

Set valueCommunication numberTrace data (Monitor data)Communication unit at trace
0FD00Output frequency0.01Hz
1FD02Frequency command value0.01Hz
2FD03Output current0.01%
3FD04Input voltage (DC detection)0.01%
4FD05Output voltage0.01%
5FD15Stator frequency0.01Hz
6FD16Speed feedback frequency (real time)0.01Hz
7FD17Speed feedback frequency (1-second filter)0.01Hz
8FD18Torque0.01%
9FD19Torque command0.01%
10FD99Output frequency during run. Frequency command value during stop.0.01Hz
11FD20Torque current0.01%
12FD21Exciting current0.01%
13FD22PID feedback value0.01Hz
14FD23Motor overload factor (OL2 data)0.01%
15FD24Inverter overload factor (OL1 data)0.01%
16FD25Braking resistor overload factor (OLr data)1%
17FD28Braking resistor load factor (%ED)1%
18FD29Input power0.01kW
19FD30Output power0.01kW
20FE76Input cumulative power[F749] setting
21FE77Output cumulative power[F749] setting
24FE35Terminal RR input value0.01%
25FE36Terminal RX input value0.01%
26FE37Terminal II input value0.01%
27FD94Motor speed command1min⁻¹
34FD26Motor load factor1%
35FD27Inverter load factor1%
62FD48PID result frequency0.01Hz
63FD58PID set value0.01Hz
64FD50Light-load high-speed switching load torque0.01%
65FD51Light-load high-speed torque during constant speed run0.01%
71FD90Motor speed (estimated value)1min⁻¹
76FE56Terminal S4/S5 pulse train input value1pps
79FD87Dancer control PID result frequency0.01Hz
120FD83Internal temperature 1-
124FE78Power circuit board temperature-
130FD96External PID3 set value-
131FD97External PID3 feedback value-
132FD98External PID3 result value-
133FE96External PID4 set value-
134FE97External PID4 feedback value-
135FE98External PID4 result value-
155FD18Signed torque0.01%
156FD19Signed torque command0.01%
158FD20Signed torque current0.01%
160FE37Signed terminal RX input value0.01%
161FE38Signed terminal AI4 input value0.01%
162FE39Signed terminal AI5 input value0.01%

Inverter Individual Information

This section displays details about the inverter, including:

Inverter individual informationValue
Inverter type-formVFAS3-2022P
Serial number0001000200030004
CPU1 Ver102
CPU2 Ver1101
Inverter operating time0 hour
  • 'Inverter type-form': Displays the type of the inverter.
  • 'Serial number': Displays the serial number of the inverter.
  • 'CPU1 Ver': Displays the version of the inverter's CPU1.
  • 'CPU2 Ver': Displays the version of the inverter's CPU2.
  • 'Inverter operating time': Displays the operating time of the inverter.

Parameter Export and Import

  • [Parameter export]: The values set for the trace-related parameters (as shown in the parameter concerning trace function section) are exported into the inverter by clicking this button. After this, the values set for the trace-related parameters and information on the inverter are imported.
  • [Parameter import]: The values set for the trace-related parameters and information on the inverter are imported by clicking this button.

[To graph >]

The Graphic sheet is shown by clicking this button.

2.5. Graphic Sheet

The Graphic sheet allows users to read trace data and display it in graphic form. The graphic display shows output frequency, frequency command value, output current, and input voltage (DC detection) over time. It also indicates maximum and minimum values for these data types and the cause for a trip.

Reset Approval

When attempting to read trace data of the last trip, a 'Reset approval' dialog box appears, stating: "In order to read the trace data of the last trip, it is necessary to reset an inverter once and to read trace data. Do you agree to reset the inverter?" Users can click [I Agree] or [I Do Not Agree].

  • [Trace data reading]: The trace data stored in the inverter is read and displayed graphically by clicking this button. When F740 is set to 1 or 3 and data is read until a trip occurs, execute reading in the trip state for correct data acquisition. Alternatively, if trace data is recorded with a trigger, read the data before resetting the power supply.
  • [Trace trigger]: When F740 is set to 1 or 3, the trace data stored in the inverter up to that time is read and displayed graphically by clicking this button. At this time, the trace selection on the inverter side is temporarily disabled. If communications are interrupted halfway, the trace selection will be set to "disabled". In such a case, set the former value again.
  • 'Graph': Displays acquired data in graphic form.
  • 'Max' 'Min': Displays the maximum and minimum values of 4 kinds of data acquired.
  • 'Cause for trip': Displays the cause of tripping of the inverter.
  • [< To setting]: The Setting sheet is shown by clicking this button.
  • [To data >]: The Data sheet is shown by clicking this button.
  • [To trip >>]: The Trip history sheet is shown by clicking this button.
  • [I Agree]: Resets the inverter and reads trace data by clicking this button.
  • [I Do Not Agree]: Stops operation without resetting the inverter (no trace data is read, but detailed history of past trips are read from inverter) by clicking this button.

2.6. Data Sheet

The Data sheet lists 4 kinds of acquired numerical data (data 1 through 4) in groups of 100 each. The table includes columns for Time(s), Output frequency (Hz), Frequency command value (Hz), Output current (%), and Input voltage (DC detection) (%).

[Trace data save]

Click this button to automatically name and save the file. The file name consists of the date and time when data is saved. The file name can be changed when saving the file.

Example of File Name Assigned Automatically

Current date and timeName assigned to the file
9:30 A.M. on Apr. 5, 2012TRACE-040520120930.xls
  • 'Time(s)': Displays the time at the same intervals as the trace cycle.
  • "4 kinds of data acquired": Displays 4 kinds of data acquired in groups of 100 each.
  • [< To graph]: The Graphic sheet is shown by clicking this button.
  • [<< To setting]: The Setting sheet is shown by clicking this button.

2.7. Trip History Sheet

The Trip sheet lists acquired details on past trips, from trip 1 to 8. The table includes details such as Operation Frequency (Hz), Inverter Status (bit), Frequency setting value (Hz), Output current (%), Input voltage (%), Output voltage (%), Status of input terminal, Status of output terminal, Cumulative operation time (h), Year/Month/Day, Time(hh:mm), and Trip name.

  • "Past trip detailed history": Displays acquired details on a past trip of trips 1 to 8.
  • [Reload]: The detailed history is read from the inverter by clicking this button. The detailed history will then be updated on the sheet.
  • [< The Graph sheet is shown by clicking this button.
  • [HELP]: The Inverter Status help is shown by clicking this button.

3. Troubleshooting

This section explains problems that may occur when PCT003Z-E is used.

Q1: Although the [Trace data reading] button is clicked, time-out occurs.
A1: Communication between the inverter and the computer is not established. Check whether the cable is connected properly and all settings for communications are made correctly.
Q2: Although trace data is acquired, no data is displayed or other data is displayed.
A2: Check whether "Deselect" is selected for 'Trace selection'.
Q3: The trace tool software has started, but it does not respond to the click of any button.
A3: This phenomenon occurs if Excel's macro setting is set at "Disable all macros without notification". To solve this problem, set the macro setting to "Disable all macros with notification".
Q4: The instruction manual for VF-AS3 states that any number up to 248 can be assigned to an inverter (F802), but only a number up to 99 can be assigned with PCT003Z-E.
A4: Since PCT003Z uses the Toshiba inverter protocol ASCII mode, only a number between 0 and 99 can be assigned to an inverter.
Q5: Communication error occurs when PCT003Z and PCM001Z are used together.
A5: Because PCM001Z occupies the communication port, PCM001Z and PCT003Z cannot be used at the same time. Use PCT003Z after PCM001Z has ended, or use a different port for PCM001Z. When setting parameters with PCM tool for VFAS3, use PCM002Z. PCM001Z is not compatible with VFAS3.

Outline of the Trace Tool Function

ItemContent
Number of sampling100 points
Trace cycle (F741) / Tracing time4ms / 400ms, 20ms / 2s, 100ms / 10s, 1s / 100s, 10s / 1000s
Number of trace data4 data. These are set by parameter F742 to F745.
Trace object (F742 to F745)Refer to Table2 Parameter concerning trace functions
Trip (F740=1)The trace data is constantly updated, and update is stopped at trip. When the inverter is doing trip or stopping, the trace data recorded by trip can be read. However, data cannot be read while the inverter is driving.
Input terminal (F740=2)The acquisition of the trace data begins on the terminal input (No.76 or No.77), and after the data of 100 points is acquired, the update of the trace data is stopped.
1+2 (F740=3)The trace data is constantly updated, and update is stopped at trip or when the input terminal function (No.76 or No.77 (negative logic)) is enabled.
Conservation form'.xls' file format
COM port1 to 30
Baud rate9600bps, 19200bps, 38400bps (Match it to setting on inverter side. (F800, F820))
ParityNon parity, Even parity or Odd parity (Match it to setting on inverter side. (F801, F821))
Inverter numbernone or 00 to 99 (Match it to setting on inverter side. (F802))

PDF preview unavailable. Download the PDF instead.

VFAS3 TraceTool manual e6582155 GPL Ghostscript 9.07

Related Documents

Preview TOSVERT VF-A7 High-Performance Inverter Instruction Manual
This instruction manual provides detailed information on the TOSVERT VF-A7 high-performance industrial inverter, covering safety precautions, installation, operation, wiring, and technical specifications for optimal use.
Preview TOSVERT VF-AS3 PCL002Z Instruction Manual - Function Setting Tool
Comprehensive instruction manual for the TOSHIBA TOSVERT VF-AS3 inverter's PCL002Z function setting tool. Learn to export/import parameters, create logic sequences, monitor real-time data, and configure communication settings for optimal inverter operation.
Preview Toshiba TOSVERT VF-S11 Industrial Inverter Instruction Manual
Comprehensive instruction manual for the Toshiba TOSVERT VF-S11 industrial inverter, covering safety precautions, installation, operation, basic and extended parameters, troubleshooting, and disposal. This guide is essential for users to safely and effectively operate the inverter with 3-phase induction motors.
Preview TOSHIBA RKP001Z-0 Extended Panel Operation Manual
Operation manual for the TOSHIBA RKP001Z-0 Extended Panel, detailing its functions, connection, installation, specifications, and warranty. Designed for use with TOSVERT series inverters.
Preview TOSVERT VF-AS1/PS1 PROFIBUS-DP Option Instruction Manual (PDP002Z)
Instruction manual for the Toshiba TOSVERT VF-AS1/PS1 PROFIBUS-DP Option (PDP002Z). Covers installation, connection, parameters, operation, specifications, and warranty for integrating VF-AS1/PS1 inverters with PROFIBUS networks.
Preview TOSHIBA TOSVERT VF-S15 Industrial Inverter Instruction Manual
Comprehensive instruction manual for the TOSHIBA TOSVERT VF-S15 Industrial Inverter, designed for 3-phase motors. This guide covers safety precautions, installation, operation, parameter settings, and maintenance for industrial applications.
Preview TOSHIBA TOSVERT VF-S15 Industrial Inverter Instruction Manual
Comprehensive instruction manual for the TOSHIBA TOSVERT VF-S15 industrial inverter. Covers safety, installation, operation, parameter settings, and specifications for 3-phase induction motors.
Preview Toshiba TOSVERT VF-AS3 Industrial Inverter Instruction Manual
Comprehensive instruction manual for the Toshiba TOSVERT VF-AS3 industrial inverter, detailing installation, wiring, operation, safety precautions, and maintenance for 3-phase motors. Covers high-performance speed control applications.