Toshiba S15 Application Note 1.3.1: Basic Preset Speed Control

How to control the S15 with preset speeds via discrete inputs.

Estimated Time: 10 Minutes | Level: 1 | Prerequisite: S15 Application Note 1.1.1 Navigating Menus & Parameters

STEP A: Connections

The S15 can be controlled via a preset speed command wired to a discrete input. To illustrate the binary nature of these inputs, only one switch is closed at a time in this example.

Connections for basic preset speed control are shown below:

Wiring Diagram Description: The diagram illustrates connections for SW1 (SOURCE) and SW2 (SINK). SW1 is connected to PLC terminals like FLA, FLB, FLC, FY, FC. SW2 is connected to terminals VIB, VIA, VIB, CC, PTC, S4, S3, F, VIC. Common connections are shown for discrete inputs S1, S2, S3, and RES. This setup allows for binary selection of preset speeds and run signals using normally open switches.

Check Your Work

STEP B: Programming

In this example, program Preset Speed #1 to be 30 Hz and Preset Speed #2 to be 60 Hz.

Program Preset Speed #1 for 30 Hz

Parameter Description Default Value New Value
Sr1 Preset Speed #1 0Hz 30Hz

Program Preset Speed #2 for 60 Hz

Parameter Description Default Value New Value
Sr2 Preset Speed #2 0Hz 60Hz

Note: Preset speed inputs are binary, and follow the sequence of the table below.

Preset-speed logic input signal example: Slide switch SW1 = SINK side. O: ON - -: OFF (Speed commands other than preset-speed commands are valid when all are OFF)

Preset-speed 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
S1-CC O
S2-CC O
S3-CC O
RES-CC O

Note: Refer to Section 5.7 in the S15 Instruction Manual (E6582175) for additional information.

Check Your Work

STEP C: Verification

Follow these steps to verify operation of preset speed commands.

  1. Close switch 3 to give the drive a forward run signal.
  2. Close switch 1 or 2. (Only one of these two switches should be closed at any time.)
  3. The drive should run to the corresponding speed shown in the table below.
Switch Function Display
3 Fwd Run F highlights in top right corner.
1 Preset Speed #1 Output frequency is 10.0 Hz.
2 Preset Speed #2 Output frequency is 30.0 Hz.

Drive Display Description: A control panel display shows "60.0" Hz with the "RUN" indicator lit. Buttons labeled "RUN", "STOP", "EASY", and "MODE" are visible.

Check Your Work

Models: S15_App_Note_1.3.1, S15 Basic Preset Speed Control, S15, Basic Preset Speed Control, Speed Control, Control

File Info : application/pdf, 3 Pages, 422.67KB

PDF preview unavailable. Download the PDF instead.

S15 App Note 1.3.1 Preset Speed Control

References

Microsoft Publisher for Microsoft 365

Related Documents

Preview Toshiba S15 Application Note 2.8.1: Motor Auto-tuning Guide
A technical guide detailing the process of motor auto-tuning for induction motors using the Toshiba S15 drive, covering background information, programming steps, and troubleshooting common errors.
Preview Toshiba S15 Heavy Duty Variable Speed Drive Overview
This document provides a comprehensive overview of the Toshiba S15 Heavy Duty Variable Speed Drive, detailing its advanced features, compact design, suitability for harsh environments, extensive control capabilities, communication options, and technical specifications for industrial applications.
Preview TOSHIBA TOSVERT VF-S15 Industrial Inverter Instruction Manual
Comprehensive instruction manual for the TOSHIBA TOSVERT VF-S15 industrial inverter. Covers safety, installation, operation, parameter settings, and specifications for 3-phase induction motors.
Preview Toshiba S15 VFD: Navigating Menus and Parameters Guide
A comprehensive guide to navigating the menus and parameters of the Toshiba S15 Variable Frequency Drive (VFD), covering Standard Mode, Program Mode, and Monitor Mode operations.
Preview TOSHIBA TOSVERT VF-S15 Industrial Inverter Quick Start Manual
This Quick Start Manual provides essential information for the safe and efficient installation, operation, and maintenance of the TOSHIBA TOSVERT VF-S15 Industrial Inverter. Designed for 3-phase induction motors, this inverter incorporates critical safety functions to ensure reliable performance in industrial applications.
Preview Toshiba S15 Application Note 2.1.1: PID Setup Guide
A comprehensive guide to setting up and running the PID control loop on the Toshiba S15 drive, covering connections, parameter configuration, and tuning for optimal process control.
Preview TOSHIBA TOSVERT VF-S15 Industrial Inverter Instruction Manual
Comprehensive instruction manual for the TOSHIBA TOSVERT VF-S15 Industrial Inverter, designed for 3-phase motors. This guide covers safety precautions, installation, operation, parameter settings, and maintenance for industrial applications.
Preview Toshiba AS3 Sleep Function (Non-PID Control): Programming and Operation Guide
Learn how to program and operate the Toshiba AS3 variable frequency drive's Sleep Function (Non-PID control) for energy saving and motor lifespan extension. This guide covers setup, parameters, and verification.